Web/SNMP Adapter (E Model) Quick Start Instructions 164950186 Rev A

7

Section 3

Connect the Adapter

NOTE

If you used the serial cable labeled “PC” in the

ConnectUPS-E installation, temporarily remove the cable from
the UPS and adapter. When configuration is complete, plug the
serial cable back into the UPS (X101/male port) and the
ConnectUPS-E UPS port.

To connect the adapter to the computer and start the
configuration:

1.

Plug the RJ-45 end of the supplied serial cable (labeled “PC”)
into the PC port on the adapter.

Verify that you have used the port labeled “PC.” The other
port on the adapter will not work for configuration.

2.

Plug the other end of the serial cable into the serial COM port
on the computer.

3.

Open your terminal emulation program (such as HyperTerminal).

4.

Select the appropriate serial connection (such as COM1). See
Figure 9.

5.

Set the serial line to 9600 baud, No parity, 8 data bits, 1 stop
bit, and no flow control (see Figure 10).

6.

Verify that the UPS is turned on.

Содержание Powerware 9305 UPS

Страница 1: ...onnectUPSt Web SNMP Adapter S Male DB 9 to RJ 45 Serial Cable with Detachable DC Power Cable S Female DB 9 to RJ 45 Serial Cable labeled PC S External Power Supply with Detachable Power Cord S Softwar...

Страница 2: ...nistrator must set up the DHCP server to provide a static address each time the adapter makes a DHCP request Provide the network administrator with the adapter s MAC address on the bottom of the adapt...

Страница 3: ...ronment set DIP switch 2 to the 1 on position 2 Open or remove the UPS front cover and locate the female 9 pin RS 232 port labeled X100 See Figure 2 3 If the X100 port is available use the supplied un...

Страница 4: ...ected receptacle 5 Replace the UPS front cover 6 Connect an active Ethernet cable supplied to the network connector on the ConnectUPS E 7 To configure the adapter locally using the supplied serial cab...

Страница 5: ...DIP switch 2 to the 1 on position 2 Remove the UPS front cover and locate the female 9 pin RS 232 port see Figure 6 3 If the female port is available use the supplied unlabeled serial cable to connect...

Страница 6: ...8 Replace the UPS front cover 9 Connect an active Ethernet cable supplied to the network connector on the ConnectUPS E 10 To configure the adapter locally using the supplied serial cable continue to...

Страница 7: ...UPS port To connect the adapter to the computer and start the configuration 1 Plug the RJ 45 end of the supplied serial cable labeled PC into the PC port on the adapter Verify that you have used the p...

Страница 8: ...owing conditions S Verify the serial line is set to 9600 baud No parity 8 data bits 1 stop bit and no flow control S If the serial line settings are correct check the cabling to verify all connections...

Страница 9: ...o set the Gateway Address and Network Mask 6 Change any other options as needed for your particular configuration by typing the corresponding number shown in the menu Each Configuration Menu setting i...

Страница 10: ...guides for instructions Use the following procedure to install NetWatch software after you have installed and configured the adapter 1 Insert the Software Suite CD into the computer s CD ROM drive Th...

Страница 11: ...ect Next 12 Verify the configuration settings are correct and select Finish see Figure 22 13 A pop up message indicates that communication with the adapter is established see Figure 23 Select Clear to...

Страница 12: ...BERS UNITED STATES 1 800 356 5737 or 919 870 3149 CANADA 1 800 461 9166 ext 260 www powerware com ALL OTHER COUNTRIES Call your local sales representative 2006 Eaton Corporation All Rights Reserved 16...

Отзывы: