UPS INSTALLATION PLAN AND UNPACKING
Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual
S
P-164000500 Rev 4
www.eaton.com/powerquality
3-15
Table 3‐7. 480V Input/Output Ratings and External Wiring Requirements for the Three UPM – Common Battery
Basic Unit Rating
Units
Rating
50/60 Hz
Rating
50/60 Hz
Rating
50/60 Hz
Rating
50/60 Hz
Rating
50/60 Hz
kVA
kW
675
675
750
750
825
825
900
825
900
900
Input and Output Voltage
Volts
480/480
480/480
480/480
480/480
480/480
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
A
Amps
1002
1113
1225
1225
1336
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(6)
500
(6)
500
(6)
500
(6)
500
(6)
AC Input to UPS Bypass
Full Load Current
(3) Phases, (1) Ground
B
Amps
812
902
992
1083
1083
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(5)
500
(5)
500
(5)
500
(5)
500
(5)
DC Input from Battery Disconnect to UPS
(1) Positive, (1) Negative
C
Total Amps
1480
1645
1809
1809
1974
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
500
(12)
500
(12)
500
(12)
500
(12)
500
(12)
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Ground
D
Amps
812
902
992
1083
1083
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(5)
500
(5)
500
(5)
500
(5)
500
(5)
NOTE
Callout letters
A
,
B
,
C
, and
D