UPS INSTALLATION PLAN AND UNPACKING
Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual
S
P-164000500 Rev 4
www.eaton.com/powerquality
3-29
Table 3‐22. Recommended Input Circuit Breaker Ratings (100% Load Rating)
UPS Model
Input Rating
480V, 415V, 400V, 380V
Eaton 9395P-1200/1200
Eaton 9395P-1200/1100
Eaton 9395P-1200/1000
Eaton 9395P-1200/900
Eaton 9395P-1200/825
Eaton 9395P-1200/750
Eaton 9395P-1200/675
See Note
2000A
2000A
1600A
1600A
1600A
1600A
1200A
C
A
U
T
I
O
N
To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current
ratings from Table 3‐22 in accordance with the NEC, ANSI/NFPA 70.
MISE EN GARDE!
Pour réduire le risque d’incendie, ne brancher qu’à un circuit avec le courant nominal maximal du disjoncteur
d’entrée indiqué dans le tableau 3-19, conformément à la norme ANSI/NFPA 70 du NEC.
Table 3‐23. Recommended Bypass, Output, and MOB Circuit Breaker Ratings (100% Load Rating)
UPS Model
Output kW
480V
415V
400V
380V
Eaton 9395P-1200/1200
1600A
—
—
—
Eaton 9395P-1200/1100
1600A
1600A
1600A
2000A
Eaton 9395P-1200/1000
1600A
1600A
1600A
1600A
Eaton 9395P-1200/900
1200A
1600A
1600A
1600A
Eaton 9395P-1200/825
1000A
1200A
1200A
1600A
Eaton 9395P-1200/750
1000A
1200A
1200A
1200A
Eaton 9395P-1200/675
See Note
1000A
1000A
1000A
1200A
NOTE
Bypass breakers are not required for IOM configurations.
There is no manual DC disconnect device within the UPS.
A battery disconnect switch is required for battery systems and may also be required
by NEC or local codes. The battery disconnect switch should be installed between the
battery and the UPS.
Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC.
Rated battery current is computed at 2 volts per cell.
The battery wiring used between the battery and the UPS should not allow a voltage
drop of more than 1% of nominal DC voltage at rated battery current.