UPS INSTALLATION PLAN AND UNPACKING
Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual
S
P-164000500 Rev 4
www.eaton.com/powerquality
3-27
Table 3‐21. 415V /400V/380V Power Cable Conduit Requirements
UPS Model
Voltage
Terminal
Number of Wires
in Conduit
Minimum Conduit
Trade Size
Number of
Conduits
Eaton 9395P-1200/1100
415 Vac
415 Vac
400 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
8
415 Vac
400 Vac
380 Vac
AC Input to Bypass and Output
(A, B, C, Neutral, Ground)
5
5
3
3
6
8
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
7
4
4
Eaton 9395P-1200/1000
415 Vac
400 Vac
380 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
4
3
3
8
6
415 Vac
400 Vac
380 Vac
AC Input to Bypass and Output
(A, B, C, Neutral, Ground)
5
3
6
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
7
4
4
Eaton 9395P-1200/900
415 Vac
400 Vac
380 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
8
415 Vac
400 Vac
380 Vac
AC Input to Bypass and Output
(A, B, C, Neutral, Ground)
5
5
3
3
6
8
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
7
4
4
Eaton 9395P-1200/825
415 Vac
400 Vac
380 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
8
415 Vac
400 Vac
380 Vac
AC Input to Bypass and Output
(A, B, C, Neutral, Ground)
5
5
3
3
6
8
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
7
4
4