Eaton PDI WaveStar Color Monitor Setup and Operation Manual P-164001109—Rev 01
31
Figure 25. Readings: BCMS (Normal)
Select
BCMS device name
in list (
BCMS
in this list). Device
name turns blue when selected and device name displays
in header.
Touch
READINGS
to see BCMS power monitoring data.
Measurements and Alarms, individual
panelboard circuits
(42 circuits):
NO
= Circuit Number
AMPS
= Amperes
CB
= Circuit breaker rating (Amps)
MIN
= Lowest current read
MAX
= Highest current read
ZERO
: OK = Current has not dropped to 0
since last reset; ACTIVE = Current has
read 0 after having read a minimum current
WARNING
: OK = No warning outstanding;
ACTIVE = warning outstanding
ALARM
: OK = No alarm outstanding;
ACTIVE = Alarm is outstanding
Panelboard totals,
using main feeds or
BCMS computed measurements:
PB Amps
: Total panelboard
measurements, phases ABCNG
% Load:
Percent of maximum PB load as
specified by user in points list
Both PBs
: Sum of phase ABCN
measurements for both panelboards
(not available if PBs operate at different
voltages)
Frequency
: Measurement in Hz
Panelboard instantaneous readings:
Voltage
AB, BC, etc., to panelboard with
THD (Total Harmonic Distortion %) by
phase:
Line 1 = voltage source 1
Line 2 = voltage source 2, if present
Panelboard power
measurements by
phases ABC and total:
KW
KVA
KVAR
PF
Panelboard cumulative reading
:
KWH
panelboard total
Clear
= Reset KWH to 0.
Содержание PDI WaveStar
Страница 1: ...p n P 164001109 Revision 01 Setup and Operation Manual Eaton PDI WaveStar Color Monitor...
Страница 4: ......
Страница 8: ...viii Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 List of Figures...
Страница 10: ...x Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 List of Tables...
Страница 12: ...2 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Safety...
Страница 30: ...20 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Setup Monitor and Network...
Страница 60: ...50 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Web Pages...
Страница 62: ...52 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Glossary...
Страница 64: ...54 Eaton PDI WaveStar Color Monitor Setup and Operation Manual P 164001109 Rev 01 Bibliography...
Страница 68: ...P 16400110901 P 164001109 01...