Pre-Installation: Receiving, Handling and
Storage
Receiving
Upon delivery, use the packing list to confirm the number
of items against what was received to ensure that the
shipment is complete. Any discrepancies should be noted
on the freight bill before signing. Report any shortages or
damage to the freight carrier immediately.
Immediately upon receipt of the panelboard interior and
trim, the packaging should be carefully removed and a
thorough inspection of each section should be made to
detect any damage incurred during shipment. Any damage
should be noted on the bill of lading (freight bill) and the
consignee receiving the equipment should notify the freight
carrier.
FAILURE TO NOTIFY THE FREIGHT CARRIER OF DAMAGE
IN A TIMELY MANNER MAY RESULT IN THE CONSIGNEE
ASSUMING THE COSTS ASSOCIATED WITH REPAIR OR
REPLACEMENT OF DAMAGED EQUIPMENT.
After inspection, the components should be returned to its
packaging until it is ready for installation.
Handling
Depending on the configuration, panelboards may weigh
in excess of 100 pounds. Before moving or lifting, verify
that the panel is within safe limits of the installers lifting
capacity.
Storage
Panelboards, which cannot be immediately installed and
energized, should be stored in an indoor dry, clean and
heated environment.
Do not store in areas where conditions such as dampness,
changes in temperature, cement dust or a corrosive
atmosphere is present.
WARNING
HAZARDOUS VOLTAGE. WILL CAUSE SEVERRE INJURY OR
DEATH
WARNING
ONLY THOSE PROFESSIONALS TRAINED AND QUALIFIED
ON ELECTRICAL DISTRIBUTION PANELBOARDS SHOULD
INSTALL AND/OR SERVICE THIS EQUIPMENT
Removal of Existing Panelboard Interior
DO NOT work on electrical equipment while energized.
Verify power entering the equipment is de-energized at
the source.
Follow appropriate lockout procedure to this panel before
starting work.
Electrical Disconnection of Existing Panelboard
After panel has been de-energized and the feeder device is
locked out, removal procedure can begin.
Carefully identify all connections, load and line paying
particular attention to main incoming phasing.
Identify correct phasing on the mains and disconnect all
phases, neutral and ground connections.
Identify and disconnect all load wires (line & neutral)
connected to existing branch breakers, noting current
values. Before proceeding, it is important to verify that the
line and load cables (phase, neutrals and grounds) are long
enough to connect to the new interior.
Proceed to disconnect all electrical connections attached to
the existing interior. Once the conductors are disconnected
from the old interior, the cables should be formed in the
space provided. Care should be taken in forming insulated
cables to ensure that no insulation is forced permanently
against the edges of any metal parts.
Removal of Existing Interior
Remove all chassis mounting hardware. Carefully remove
chassis to ensure that cable insulation is not damaged by
sharp edges.
To allow for adequate bonding, all attempts should be made
to utilize existing mounting studs/system in the enclosure
If it is not feasible to use existing mounting system, remove
all protrusions to allow for a flat mounting surface.
Installation of RetroFit Panelboard Interior
Removal of Dead-front cover
Remove the interior from packaging.Place on a solid work
surface, remove qty 4 ¼-20 screws that fasten the dead-
front cover to the chassis – (see Fig. A). Place dead-front
cover and hardware in a safe location to prevent damage.