Pow-R-Line X Retrofit Panelboards 

Pow-R-Line X RetRofit PaneLboaRds

   MN014011EN   January 2020   eatoncanada.ca

WARNING

DO NOT ATTEMPT TO RE-ENERGIZE PANELBOARD 
OVERCURRENT DEVICES AFTER ELECTRICAL EVENTS, 
SUCH AS SHORT-CIRCUITS, GROUND-FAULTS AND 
OVERLOADS,
UNTIL THE CAUSE OF THE EVENT HAS BEEN IDENTIFIED 
AND CORRECTED.

Water Damage

DO NOT WORK ON SURFACES OR FLOORS WHERE 
THERE IS STANDING WATER.  
DO NOT WORK ON WET ENERGIZED ELECTRICAL 
EQUIPMENT.

Major accumulation of water or moisture on any part of 

the panelboard can cause catastrophic damage to the 

panelboard. If a panelboard has been submerged by more 

than 2 inches or where running or standing water has 

had contact with current carrying parts, it has sustained 

significant damage.
The panelboard and its components may be damaged 

beyond repair and may need replacement.

1.  Do not attempt to clean or repair water-damaged 

equipment or components.

2.  De-energize the panelboard at its source.
3.  Do not energize.
4.  Contact Eaton for replacement.

Minor accumulations of moisture, such as condensation, 

over a short period of time may be corrected using heat.  

De-energize panelboard. Apply approximately 250 watts 

per vertical section for a sufficient period of time until 

the moisture disappears, then remove all heat sources 

and materials used for drying.  Inspect for damage 

to components and any corrosion.  If any damage or 

corrosion is present, contact Eaton. DO NOT RE-ENERGIZE 

PANELBOARD.  After the panelboard has completely dried, 

remove all materials and tools from the equipment. Inspect 

all connections for damage and torque. Re-install all covers, 

fillers, dead-front assemblies and side sheets. Conduct 

panelboard insulation resistance testing described in this 

publication.

Renewal Parts

To ensure safety and to maintain ULTM listing and CSATM 

approval, it is essential that only new parts and components 

from Eaton be utilized.  When ordering renewal parts 

or when requesting information on the panelboard, it is 

essential to include as much information as possible.
Each panelboard will have a nameplate and other 

identification marks with details that will help expedite 

information requests and orders.
The following may be required to help identify parts and 

information requests.

 

Catalog number of the panelboard 

 

Description of the equipment

 

Supply voltage

 

Equipment ratings

 

Description of the part

 

Style number of part, if available

 

Rating of part(s)

Electrical distribution equipment has a limited life span.  As 

such, the manufacturer cannot guarantee the availability of 

obsolete equipment or parts. Equipment replacement may 

be recommended. 

DANGER

WET PANELBOARDS PRESENT A HAZARDOUS CONDITION 
AND MAY CAUSE INJURY OR DEATH. DE-ENERGIZE POWER 
TO ALL EQUIPMENT BEFORE SERVICING.

DANGER

DO NOT WORK ON PANELBOARDS OR ENTER AREAS THAT 
HAVE STANDING WATER. DE-ENERGIZE ALL EQUIPMENT 
IN AREAS WITH STANDING WATER.

WARNING

PANELBOARD COMPONENTS, INCLUDING CIRCUIT 
BREAKERS, FUSIBLE SWITCHES, METERING, ETC., 
SUBJECTED TO WATER OR MOISTURE MAY BE RENDERED 
UNSAFE. REPLACEMENT IS REQUIRED.

Содержание P1RX 240Vac Max

Страница 1: ...Pow R Line X Retrofit Panelboards Instruction Manual MN014011EN Effective January 2020 P1RX 240Vac Max P2RX 347 600Vac Max...

Страница 2: ......

Страница 3: ...1EN January 2020 eatoncanada ca Table of Content Installation Criteria 2 Safety Measures 3 Pre Installation Receiving Handling and Storage 4 Removal of Existing Panelboard Interior 4 Installation of R...

Страница 4: ...2 1067 Lug 24 400 48 1219 20 0 508 5 75 127 30 42 Table 2 P2RXL P2RXB Panelboards Main Device Circuits Current Amperes Minimum Height in mm Minimum Width in mm Minimum Depth in mm Lug 18 100 19 5 495...

Страница 5: ...ade all reasonable efforts to ensure that the instructions in this document are adequate and free of material errors and omissions Eaton will if necessary explain issues which may not be covered by th...

Страница 6: ...TALL AND OR SERVICE THIS EQUIPMENT Removal of Existing Panelboard Interior DO NOT work on electrical equipment while energized Verify power entering the equipment is de energized at the source Follow...

Страница 7: ...maintained per NECTM CECTM Care must be taken to ensure that the trim will completely cover openings in the enclosure If not using existing mounting hardware mark minimum of 8 mounting locations on th...

Страница 8: ...conductor into lug so the bare conductor fills the full length of the lug body Tighten lug then torque to levels indicated on the panelboard label If compression lugs are utilized and supplied with th...

Страница 9: ...uire ground fault protection for this installation Other GFP applications may be used including multi level ground fault protection Refer to the panelboard drawings and electrical construction drawing...

Страница 10: ...trim parts on the panelboard using hardware supplied by the manufacturer Take caution that conductors are not pinched between parts when installing the dead front cover and trim All parts should be al...

Страница 11: ...e all control power fusing and connections to products which will be damaged in this test This includes all components with control wire fusing Transient Voltage Surge Suppression Surge Protective Dev...

Страница 12: ...o maintain the equipment in satisfactory condition Maintain a permanent record of all maintenance activities and testing for future reference The condition of each panelboard should be recorded as a g...

Страница 13: ...RE ENERGIZE PANELBOARD After the panelboard has completely dried remove all materials and tools from the equipment Inspect all connections for damage and torque Re install all covers fillers dead fro...

Страница 14: ...le 4 Wire Bending Space Requirements for Cable Sizes Bolt Size Torque inch pounds Torque foot pounds Torque Newton Meters 10 30 2 5 3 4 65 5 4 7 3 5 16 130 10 8 14 7 3 8 240 20 27 1 600 50 67 8 Nation...

Страница 15: ...11 Pow R Line X Retrofit Panelboards Pow R Line X Retrofit Panelboards MN014011EN January 2020 eatoncanada ca Notes...

Страница 16: ...evard Cleveland OH 44122 United States Eaton com 2020 Eaton All Rights Reserved Printed in USA Publication No MN014011EN January 2020 Eaton is a registered trademark All trademarks are property of the...

Отзывы: