Pow-R-Line X  Retrofit Panelboards

Pow-R-Line X RetRofit PaneLboaRds

   MN014011EN   January 2020   eatoncanada.ca

WARNING

TO PREVENT DAMAGE TO GROUND FAULT CONTROL 
CIRCUITS, METERING CIRCUITS, TRANSIENT VOLTAGE 
SURGE PROTECTION (TVSS) OR OTHER CONTROL 
CIRCUITS, WHEN MEGGERING PANELBOARD, ISOLATE 
CIRCUITS FROM PANELBOARD SYSTEM BEFORE 
BEGINNING THE MEGGER OPERATION. BE SURE TO 
RECONNECT THOSE CIRCUITS AFTER MEGGER TESTS ARE 
COMPLETED.
NOTEe: SOME GROUND FAULT CIRCUITS MAY NOT BE 
FUSED, THEREFORE ISOLATION OF THOSE CIRCUITS 
REQUIRES DISCONNECTING WIRING FROM BUS BARS.

WARNING

DO NOT USE ALTERNATING CURRENT (AC) DIELECTRIC/
MEGGER TESTING. DAMAGE TO COMPONENTS WILL 
OCCUR.

WARNING

DO NOT USE COMPRESSED AIR TO CLEAN OR BLOW OUT 
DEBRIS OR DUST IN PANELBOARDS.

WARNING

TO PREVENT DAMAGE TO GROUND FAULT CONTROL 
CIRCUITS, METERING CIRCUITS, TRANSIENT VOLTAGE 
SURGE PROTECTION (TVSS) OR OTHER CONTROL 
CIRCUITS, WHEN 
MEGGERING PANELBOARD, ISOLATE CIRCUITS FROM 
PANELBOARD SYSTEM BEFORE BEGINNING THE MEGGER 
OPERATION. BE SURE TO RECONNECT THOSE CIRCUITS 
AFTER MEGGER TESTS ARE COMPLETED. 
 
NOTEe: SOME GROUND FAULT CIRCUITS MAY NOT BE 
FUSED, THEREFORE ISOLATION OF THOSE CIRCUITS 
REQUIRES DISCONNECTING WIRING FROM BUS BARS.

WARNING

DO NOT USE ALTERNATING CURRENT (AC) DIELECTRIC/
MEGGER TESTING. DAMAGE TO COMPONENTS WILL 
OCCUR.

Secondary Wiring

Check all wiring connections for tightness, including those 

at the current and potential transformers, if present, and at 

all terminal blocks. Check all secondary wiring connections 

to ensure they are properly connected to the panelboard 

ground bus, where indicated. Look for broken wire strands 

and pinched or damaged insulation.

Ventilation

Check all grills and ventilation ports for obstructions and 

accumulations of dirt. Clean ventilation ports, if necessary.  

For panelboards installed outdoors, inspect the air space 

under the panelboard to be sure that it is clean and clear of 

debris, leaves and obstructions.

Records

It is essential to maintain the equipment in satisfactory 

condition. 

Maintain a permanent record of all maintenance activities 

and testing for future reference.  The condition of each 

panelboard should be recorded as a guide for anticipating 

the need for any replacement parts or components or 

special attention at the next regular maintenance period. 

It is recommended that a series of inspections be made 

at quarterly intervals until the progressive effects of local 

conditions can be analyzed to determine a regular schedule.

Panelboard Events and Service Interruptions

Short-Circuits, Ground-Faults and Overloads

A thorough assessment, identification and correction of the 

event origin must be completed. An additional assessment 

of the conductor insulation and other insulating materials 

should be made. Replace all damaged insulation materials, 

conductors and overcurrent devices. Original panelboard 

parts, insulators, insulation material and overcurrent devices 

must be replaced with renewal parts from Eaton.  (Refer to 

your local Eaton Sales Representative for support.)
Do not attempt to re-energize panelboard overcurrent 

components after electrical events, such as short-circuits, 

ground-faults and overloads, until the cause of the event has 

been identified and corrected.

After the event has been rectified, test equipment per 

the maintenance process described in this publication.

Physical Damage

Any physical damage to the panelboard that occurs after 

the panelboard is installed must be corrected. A thorough 

inspection, which includes the exterior enclosure and dead-

front, plus interior components in the damaged portion of 

the panelboard, should be conducted. Replace all damaged 

parts and components. Ensure that there are no gaps in 

the panelboard enclosure that could cause exposure to 

live parts.  Contact Eaton for renewal parts and assistance.  

After the physical damage has been corrected, test 

equipment per the maintenance process described in this 

publication.

DANGER

HAZARDOUS VOLTAGE WILL CAUSE SEVERE INJURY 
OR DEATH. DE-ENERGIZE BOARD PRIOR TO SERVICING 
FUSIBLE DEVICES.

WARNING

NEVER USE COMPRESSED AIR TO CLEAN OR BLOW OUT 

DEBRIS OR DUST IN PANELBOARDS.

Содержание P1RX 240Vac Max

Страница 1: ...Pow R Line X Retrofit Panelboards Instruction Manual MN014011EN Effective January 2020 P1RX 240Vac Max P2RX 347 600Vac Max...

Страница 2: ......

Страница 3: ...1EN January 2020 eatoncanada ca Table of Content Installation Criteria 2 Safety Measures 3 Pre Installation Receiving Handling and Storage 4 Removal of Existing Panelboard Interior 4 Installation of R...

Страница 4: ...2 1067 Lug 24 400 48 1219 20 0 508 5 75 127 30 42 Table 2 P2RXL P2RXB Panelboards Main Device Circuits Current Amperes Minimum Height in mm Minimum Width in mm Minimum Depth in mm Lug 18 100 19 5 495...

Страница 5: ...ade all reasonable efforts to ensure that the instructions in this document are adequate and free of material errors and omissions Eaton will if necessary explain issues which may not be covered by th...

Страница 6: ...TALL AND OR SERVICE THIS EQUIPMENT Removal of Existing Panelboard Interior DO NOT work on electrical equipment while energized Verify power entering the equipment is de energized at the source Follow...

Страница 7: ...maintained per NECTM CECTM Care must be taken to ensure that the trim will completely cover openings in the enclosure If not using existing mounting hardware mark minimum of 8 mounting locations on th...

Страница 8: ...conductor into lug so the bare conductor fills the full length of the lug body Tighten lug then torque to levels indicated on the panelboard label If compression lugs are utilized and supplied with th...

Страница 9: ...uire ground fault protection for this installation Other GFP applications may be used including multi level ground fault protection Refer to the panelboard drawings and electrical construction drawing...

Страница 10: ...trim parts on the panelboard using hardware supplied by the manufacturer Take caution that conductors are not pinched between parts when installing the dead front cover and trim All parts should be al...

Страница 11: ...e all control power fusing and connections to products which will be damaged in this test This includes all components with control wire fusing Transient Voltage Surge Suppression Surge Protective Dev...

Страница 12: ...o maintain the equipment in satisfactory condition Maintain a permanent record of all maintenance activities and testing for future reference The condition of each panelboard should be recorded as a g...

Страница 13: ...RE ENERGIZE PANELBOARD After the panelboard has completely dried remove all materials and tools from the equipment Inspect all connections for damage and torque Re install all covers fillers dead fro...

Страница 14: ...le 4 Wire Bending Space Requirements for Cable Sizes Bolt Size Torque inch pounds Torque foot pounds Torque Newton Meters 10 30 2 5 3 4 65 5 4 7 3 5 16 130 10 8 14 7 3 8 240 20 27 1 600 50 67 8 Nation...

Страница 15: ...11 Pow R Line X Retrofit Panelboards Pow R Line X Retrofit Panelboards MN014011EN January 2020 eatoncanada ca Notes...

Страница 16: ...evard Cleveland OH 44122 United States Eaton com 2020 Eaton All Rights Reserved Printed in USA Publication No MN014011EN January 2020 Eaton is a registered trademark All trademarks are property of the...

Отзывы: