Parameter setting
43
11/04 MN01219002Z-EN
All outputs are separately isolated relay outputs and can
therefore also be used to switch different circuits and loads.
For technical data refer to
a
section “Technical data”,
Page 68.
I Assignment
In this menu you determine if the I0 input is used for
acknowledging trips or if the motor protection alarm is used.
h
Outputs Q4 and Q5 are used for switching the motor when
using a motor operator for the circuit-breaker.
h
If a motor starter function has been selected for the DMI,
some or all of the outputs Q0 to Q3 are used for
controlling the contactors.
h
If any outputs of the DMI are configured for signalling
circuit-breaker alarm conditions (trip, load warning,
overload, etc.) and the connection to the NZM is
interrupted while one of these outputs is set, the affected
outputs remain set. This allows the use of an alternative
circuit controlled by these outputs.
The diagnostic data can be read out from the NZM with a
laptop and the NZM-XPC-Soft software, which requires
the connection between DMI and NZM to be terminated.
Outputs that are not directly controlled by the NZM are not
affected. This includes outputs that are permanently set to
On or Off, that are controlled though the bus and a
”parameter” output.