PROFIBUS-DPV1 functions
157
11/04 MN01219002Z-EN
Assignment of the outputs with motor-starter
functions
The following table indicates the possible assignment of
outputs Q0 to Q3 with motor-starter functions and the
corresponding value for the Octets 1 to 4 of the Object.
Table 38: Motor-starter function and its values
Value for output
assignment
(decimal)
Motor-starter function
Occupy outputs
17
Direct-on-line starter
Q0
18
Reversing starter
Q0, Q1
19
Star-delta starter
Q0, Q2, Q3
20
Reversing star-delta starter
Q0, Q1, Q2, Q3
h
Please note that the motor-starter function can only be
parameterized in conjunction with the circuit-breaker type
-ME which is intended for this purpose. If you do not
observe this, you will receive a fault indication when
writing to the object.
h
Please note that only the respective value may be
parameterized on the stated outputs with the desired
motor-starter function. All stated outputs are to be
parameterized with the same intended value for the
respective motor starter function. If you do not observe
these conditions, you will receive a fault indication when
writing to the object.
h
Information concerning the connection of motor
contactors can be found in
a
section “Motor starter”,
Page 44.