PROFIBUS-DPV0 functions
111
11/04 MN01219002Z-EN
Overflow of additional
diagnosis information
The additional diagnosis data
(status) is larger than the memory
reserved for it in the DP master
Check the configuration of the
DP master
Parameterization fault
The DP master has sent an invalid
parameterization telegram to the
NZM-XDMI-DPV1
Check the configuration of the
DP master
Parameterization query
The NZM-XDMI-DPV1 waits for the
parameterization telegram of the DP
master
Temporary state
Parameterized motor-
starter function changed
or deactivated
A motor starter function which has
already been parameterized in the
DMI is changed or deactivated
–
Remote operator not
parameterized in DMI
The remote operator in the DMI is
not parameterized, the switch state
of the circuit-breaker can not be
controlled via the PROFIBUS
Parameterize the remote
operator in the DMI
Slave deactivated
The DP master has removed the
NZM-XDMI-DPV1 from its cyclic
process routine (deactivated)
Intended user action
Slot number
Contains the slot number from which
the additional diagnosis information
(status) originates:
hexadecimal 00
–
Static diagnosis
The communication between the
NZM-XDMI-DPV1 and DMI is
interrupted
Check the connection between
the DMI and NZM-XDMI-DPV1
Station not existent
A station does not answer at the
station address used
Inspect the configuration of the
DP master and the address
setting on the DMI
Station not ready
The NZM-XDMI-DPV1 is not yet
ready for communication
(initialization phase)
Temporary state
Designation
Meaning
Clarification/Hint