Page 41
Parameter
Symbol / Alert
Remedy
Peak low
frequency
noise
High PreAlert
High Alert
If frequent alarms, check:
1.
Fieldbus screen is correctly cut back and taped at each of the fieldbus
devices;
2.
Fieldbus screen connections are correctly made in fieldbus wiring block
junction box, intermediate junction boxes, in marshalling cabinet and
correctly connected to ground;
3.
No AC cabling close to fieldbus cabling;
4.
Wire terminations are properly secured.
Peak
in-band
frequency
noise
(fieldbus
frequency)
High PreAlert
High Alert
If frequent alarms, check:
1.
For operation of radios with Effective Radiated Power (ERP) up to 5W
being used within 1.5m of fieldbus devices, junction box or cabling;
2.
Fieldbus screen is correctly cut back and taped at each of the fieldbus
devices;
3.
Fieldbus screen connections are correctly made in fieldbus wiring block
junction box, intermediate junction boxes, in marshalling cabinet and
correctly connected to ground;
4.
No AC cabling close to fieldbus cabling;
5.
Wire terminations are properly secured;
6.
For welding in the plant;
7.
Poor grounding of frequency controlled drives.
Peak high
frequency
noise
High PreAlert
High Alert
If frequent alarms, check:
1.
For operation of radios with Effective Radiated Power (ERP) up to 5W
being used within 1.5m of fieldbus devices, junction box or cabling;
2.
For welding in the plant;
3.
Poor grounding of frequency controlled drives.