Eaton’s Crouse-Hinds Business
Cooper Crouse-Hinds Pte Ltd
No. 2 Serangoon North Ave 5 #06-01
Singapore 554911
tel: + 65 6645 9888
fax: +65 6297 4819
Page 39
If the Segment diagnosis symbol in the application area does
not correspond to the symbol in
the Navigation area (see following screenshot), the navigation area shows a propagated
symbol from a lower hierarchy layer. Click on the white arrow ( ) next to the respective
segment in the Navigation area, so that the lower layer devices are shown.
The Navigation area shows the blue oil can for Segment 8, but the application area for the
segment shows a green symbol for Segment Diagnosis. This means that the segment
parameter are ok, and the problem occurs at a lower layer, which are the field instruments.
Check the Navigation area for field instrument that show an error, and investigate the
respective field instrument(s).