4.
4.1.
The DTM can be run from within a distributed control system (DCS), or from a stand-alone
lar. Consult your DCS vendor on how to
employ the FDT frame application and consequently run the DTM, respectively how to
execute DTMs from within the DCS engineering station.
4.2.
When the DTM is brought from offline to online, it performs an automatic upload. This is
different from manual uploading, because it updates the device data set (i.e. the parameter
values in the diagnostic module) and instance data set with the diagnostic module's data, but
keep unchanged the working data set (the parameter values that the user is currently working
with).
Note: Manual uploading will synchronize both the instance data set and the working data set
from the F809F device data set. If a "downloading" job is in progress then both manual and
automatic uploading commands will be ignored.
4.3.
each with a tree view and an application area.