Page 24
I.L. 17562
PR 0.3 Effective 8/99
Line
No.
Display
Help Message
Setpoint
Range/ Value
Selection
Value as
shipped
Selected Value
4
MB T XXX
MOTOR BEARING TRIP
0-199°C, OFF /
32-390°F, OFF
(1°increments)
100
5
MB A XXX
MOTOR BEARING ALARM
0-199°C, OFF /
32-390°F, OFF
(1°increments)
80
6
LB T XXX
LOAD BEARING TRIP
0-199°C, OFF /
32-390°F, OFF
(1°increments)
100
7
LB A XXX
LOAD BEARING ALARM
0-199°C, OFF /
32-390°F, OFF
(1°increments)
80
8
AX T XXX
AUXILIARY TRIP
0-199°C, OFF /
32-390°F, OFF
(1°increments)
100
9
AX A XXX
AUXILIARY ALARM
0-199°C, OFF /
32-390°F, OFF
(1°increments)
80
10
DIAG ON
or
DIAG OFF
ALARM ON RTD FAILURE
DIAGNOSTIC
Toggles between
DIAG ON and
DIAG OFF
DIAG ON
Page 3 SP TRIP SETPOINTS FOR TRIP SETTINGS
1
GFT XXX
GROUND FAULT TRIP LEVEL
IN % OF GROUND CT RATIO
NUMERATOR
2-55% of Ground
Ct ratio
numerator, OFF
(1% increments)
24%
2
GFSD XX
GROUND FAULT START
DELAY IN CYCLES
2-60 ac cycles (1
cycle
increments)
5
3
GFRD XX
GROUND FAULT RUN DELAY
IN CYCLES
0-60 ac cycles (1
cycle
increments)
2
4
IOC XXXX
INSTANTANEOUS
OVERCURRENT IN % FLA
300-1600%, OFF
(1% increments)
OFF
5
IOCSD XX
INSTANTANEOUS
OVERCURRENT START
DELAY IN CYCLES
2-60 ac cycles (1
cycle
increments)
3
6
JMT XXXX
JAM TRIP LEVEL IN % FLA
100-1200%, OFF
(1% increments)
1000%
7
JMSD XXX
JAM TRIP AND ALARM START
DELAY IN SECONDS
0-1200 sec. (1
sec. increments)
60
8
JMTR XXX
JAM TRIP RUN DELAY IN
SECONDS
0-240 sec. (1
sec. increments)
2
9
ULT XXX
UNDERLOAD TRIP LEVEL IN
% FLA
6-90%, OFF (1%
increments)
OFF
10
ULSD XXX
UNDERLOAD TRIP AND
ALARM START DELAY IN
SECONDS
0-120 sec. (1
sec. increments)
60
11
ULTR XXX
UNDERLOAD TRIP RUN
DELAY IN SECONDS
0-240 sec. (1
sec. increments)
10
12
UBT XXX
PHASE UNBALANCE TRIP
LEVEL
4-40%, OFF (1%
increments)
OFF
13
UBSD XXX
PHASE UNBALANCE TRIP
AND ALARM START DELAY IN
SECONDS
0-120 sec. (1
sec. increments)
10
Содержание MP-3000
Страница 18: ...Page 18 I L 17562 PR 0 3 Effective 8 99 Figure 4 1 MP 3000 Pushbuttons...
Страница 19: ...I L 17562 Page 19 PR 0 3 Effective 8 99 Figure 4 2 MP 3000 LED Indicators...
Страница 72: ...Page 72 I L 17562 PR 0 3 Effective 8 99 Figure 6 1 Panel Cutout Dimensions...
Страница 73: ...I L 17562 Page 73 PR 0 3 Effective 8 99 Figure 6 2 Faceplate Dimensions...
Страница 74: ...Page 74 I L 17562 PR 0 3 Effective 8 99 Figure 6 3 MP 3000 Case Depth Dimensions...
Страница 75: ...I L 17562 Page 75 PR 0 3 Effective 8 99 Figure 6 4 Universal RTD Module Mounting Dimensions...
Страница 76: ...Page 76 I L 17562 PR 0 3 Effective 8 99 Figure 6 5 Rear Panel Terminals...
Страница 77: ...I L 17562 Page 77 PR 0 3 Effective 8 99 Figure 6 6 Typical Ct Circuits and Motor Control Wiring...
Страница 78: ...Page 78 I L 17562 PR 0 3 Effective 8 99 Figure 6 7 Typical ac Supply and URTD Wiring...
Страница 79: ...I L 17562 Page 79 PR 0 3 Effective 8 99 Figure 6 8 Alternatives for Discrete Input Wiring...
Страница 80: ...Page 80 I L 17562 PR 0 3 Effective 8 99 Figure 6 9 RTD Wiring to URTD Module...
Страница 88: ...Page 88 I L 17562 PR 0 3 Effective 8 99 Figure 8 1 System Overview Figure 8 2 Torques from Sequence Currents...
Страница 100: ...Page 100 I L 17562 PR 0 3 Effective 8 99 Figure 9 1 Rotor Temperature Tracking...
Страница 101: ...I L 17562 Page 101 PR 0 3 Effective 8 99 Figure 9 2 Motor Protection Curve...
Страница 102: ...Page 102 I L 17562 PR 0 3 Effective 8 99 Figure 9 3 Underload Jam Protection Curve...
Страница 103: ...I L 17562 Page 103 PR 0 3 Effective 8 99 Figure 9 4 Motor Protection Curve Example without RTDs...
Страница 104: ...Page 104 I L 17562 PR 0 3 Effective 8 99 Figure 9 5 Motor Protection Curve Example with RTDs...
Страница 105: ...I L 17562 Page 105 PR 0 3 Effective 8 99 Figure 9 6 Motor Start and Run Cycles...
Страница 109: ...I L 17562 Page 109 PR 0 3 Effective 8 99 P5L8 40 Incomplete Sequence time 1 60s OFF 1 240s...