Instructional Booklet

Effective: March 2007

Page

 

3

Fixed and Drawout Magnum Transfer Switches

Section 1:  Introduction

1.1  Preliminary Comments and Safety Precautions

This technical document is intended to cover most aspects associ-

ated with the installation, application, operation, and maintenance 

of transfer switch equipment with ratings from 800 through

3200 amperes (A), except for the specific logic used to control 

the equipment.  It is provided as a guide for authorized and quali-

fied personnel only.  Please refer to the specific WARNING and 

CAUTION in Section 1.1.2 before proceeding.  If further informa-

tion is required by the purchaser regarding a particular installation, 

application, or maintenance activity, contact an Eaton representa-

tive.  For information associated with the control, refer to the sep-

arate instruction book pertaining to the logic package installed in 

the switch.

1.1.1 Warranty and Liability Information

No warranties, expressed or implied, including warranties of fit-

ness for a particular purpose of merchant-ability, or warranties 

arising from course of dealing or usage of trade, are made regard-

ing the information, recommendations and descriptions contained 

herein.  In no event will Eaton be responsible to the purchaser or 

user in contract, in tort (including negligence), strict liability or 

otherwise for any special, indirect, incidental or consequential 

damage or loss whatsoever, including but not limited to damage or 

loss of use of equipment, plant or power system, cost of capital, 

loss of power, additional expenses in the use of existing power 

facilities, or claims against the purchaser or user by its customers 

resulting from the use of the information and descriptions con-

tained herein.

1.1.2  Safety Precautions

All safety codes, safety standards, and/or regulations must be 

strictly observed in the installation, operation, and maintenance of 

this device.

.

 

1.2  General Information

Transfer switches are used to protect critical electrical loads 

against loss of power.  The Source 1 power source of the load is 

backed-up by a Source 2 power source.  A transfer switch is con-

nected to both the Source 1 and Source 2 power sources and sup-

plies the load with power from one of these two sources.  In the 

event that power is lost from the Source 1 power source, the 

transfer switch transfers the load to the Source 2 power source.  

This transfer can be automatic or manual, depending upon the 

type of transfer switch equipment being used.  Once Source 1 

power is restored, the load is automatically or manually trans-

ferred back to the Source 1 power source, again depending upon 

the type of transfer equipment being used (Figure 

2

).

In addition, the Eaton closed transition transfer switch may be 

applied where it is desirable to avoid any momentary power inter-

ruptions.  Although the closed transition switch is not a substitute 

for an uninteruptable power source (UPS), it does eliminate power 

interruptions to loads except to those caused by power sources or 

equipment external to the transfer switch.  If both sources are 

acceptable as determined by the IQ Transfer logic, a make-before-

break transfer is performed during a transfer test or retransfer 

operation.

1.2.1  Transfer Switch Types

There are four types of transfer switch equipment.

Automatic Transfer Switch

Automatic transfer switches (ATSs) automatically perform the 

transfer function.  They consist of three basic elements:

1. Main contacts to connect and disconnect the load to and from 

the source of power.

2. Intelligence/supervisory circuits to constantly monitor the con-

dition of the power sources and thus provide the intelligence 

necessary for the switch and related circuit operation.

3. A transfer mechanism to effect the transfer of the main con-

tacts from source to source.

 

WARNING

THE WARNINGS AND CAUTIONS INCLUDED AS PART OF THE PRO-

CEDURAL STEPS IN THIS DOCUMENT ARE FOR PERSONNEL SAFETY 

AND PROTECTION OF EQUIPMENT FROM DAMAGE.  AN EXAMPLE 

OF A TYPICAL WARNING LABEL HEADING IS SHOWN ABOVE TO 

FAMILIARIZE PERSONNEL WITH THE STYLE OF PRESENTATION.  

THIS WILL HELP TO INSURE THAT PERSONNEL ARE ALERT TO 

WARNINGS, WHICH APPEAR THROUGHOUT THE DOCUMENT.  IN 

ADDITION, CAUTIONS ARE ALL UPPER CASE AND BOLDFACE.

 

CAUTION

COMPLETELY READ AND UNDERSTAND THE MATERIAL PRESENTED 

IN THIS DOCUMENT BEFORE ATTEMPTING INSTALLATION, OPERA-

TION, OR APPLICATION OF THE EQUIPMENT.  IN ADDITION, ONLY 

QUALIFIED PERSONS SHOULD BE PERMITTED TO PERFORM ANY 

WORK ASSOCIATED WITH THE EQUIPMENT.  ANY WIRING 

INSTRUCTIONS PRESENTED IN THIS DOCUMENT MUST BE FOL-

LOWED PRECISELY.  FAILURE TO DO SO COULD CAUSE PERMA-

NENT EQUIPMENT DAMAGE.

 

WARNING

THE CLOSED TRANSITION PRODUCT CONTAINS A SPECIAL CON-

TACT ARRANGEMENT (OVERLAPPING CONTACTS).  MISUSE CAN 

RESULT IN DEATH, SEVERE PERSONAL INJURY, AND/OR PROPERTY 

DAMAGE.

Содержание Magnum Transfer Switch

Страница 1: ...ction Booklet New Information Description Page Introduction 3 Receiving Handling and Storage 10 Equipment Description 10 Installation and Wiring 16 Operation 20 Drawout and Fixed Switching Devices 22...

Страница 2: ...RISE DURING INSTALLATION OPERATION OR MAINTENANCE AND ALL DETAILS AND VARIA TIONS OF THIS EQUIPMENT DO NOT PURPORT TO BE COVERED BY THESE INSTRUCTIONS IF FURTHER INFORMATION IS DESIRED BY THE PURCHASE...

Страница 3: ...t from the Source 1 power source the transfer switch transfers the load to the Source 2 power source This transfer can be automatic or manual depending upon the type of transfer switch equipment being...

Страница 4: ...The ATS non automatic transfer switch electrically operated and bypass isolation transfer switch are the available types for the configuration described in this manual Operation of the ATS and the by...

Страница 5: ...ing device short time rating Contact factory for details SOURCE 1 SOURCE 1 SOURCE 1 SOURCE 1 BYPASS SOURCE 1 SOURCE 1 SOURCE 1 AVAILABLE SOURCE 2 ISOLATED ISOLATED POSITION SOURCE 2 POSITION SOURCE 2...

Страница 6: ...g con figurations Table 2 Magnum Transfer Switch Configurations All Magnum switching devices are 100 rated Underwriters Lab oratories UL listed and are built and tested in an ISO 9002 certi fied facil...

Страница 7: ...is connects to provide for the drawout functioning The operating mechanism is a two step stored energy mechanism either manu ally or electrically operated When withdrawn on the extendable carriage rai...

Страница 8: ...ted mounting holes to facilitate mounting 1 4 Transfer Switch Catalog Number Identification Transfer switch equipment catalog numbers provide a significant amount of relevant information that pertains...

Страница 9: ...Position 9 12 0200 200A 0300 300A 0400 400A 0600 600A 0800 800A 1000 1000A 1200 1200A 1600 1600A 2000 2000A 2500 2500A 3200 3200A ENCLOSURE Position 14 K Open S NEMA 1 R NEMA 3R T Thru Door Design LIS...

Страница 10: ...2 2 Handling As previously mentioned the transfer switch equipment is pack aged for fork lift movement Protect the equipment from impact at all times and DO NOT double stack Once the equipment is at t...

Страница 11: ...rmal and short circuit protection in either or both switching devices is available Section 3 6 These continuous duty devices are rated for all classes of loads In addition they have high dielectric st...

Страница 12: ...witching device has been closed and an indicator on the switch shows whether it is in the OPEN or CLOSED posi tion and the status of the stored energy mechanism The switching device is closed by energ...

Страница 13: ...15 Voltage Selection Panel Figure 16 North American Market Voltage Selection Terminals Shown Connected to the 120 Vac Taps 3 3 2 International Voltage Selection 208 220 240 380 415 and 600 V 50 60 Hz...

Страница 14: ...the logic scheme refer to the specific logic document associated with the type of logic selected 14 Relay Auxiliary Contacts Provides Form C relay auxiliary contacts E Source 1 Available Provides one...

Страница 15: ...1 Source 2 and Load Circuit rear accessible bus stabs with provision for bus bar connection 21A Optional Power Cable Connection Terminals Provides alternate power cable connection terminals Consult E...

Страница 16: ...witches are factory wired and tested Installation requires solidly mounting the enclosed unit and connecting the power cables and auxiliary pilot circuits Physical mounting proce dures and power cable...

Страница 17: ...ing side and rear covers when applicable See Section 9 3 for cover removal instructions Step 2 Gently maneuver the switch into its location using all of the supplied lift brackets Step 3 Bolt the enc...

Страница 18: ...odate the power cables being used Also verify that the cables comply with local electrical codes Standard trans fer switch equipment as supplied from the factory will accommo date the wire sizes shown...

Страница 19: ...r changing the taps on both transformers replace the trans former pack cover and tighten all four screws 4 7 Mounting the Switching Device in the Drawout Mechanism In structures equipped for drawout c...

Страница 20: ...tarts timing when both sources are paralleled Refer to the IQ Transfer instruction book for additional alarms Section 5 Operation 5 1 General A transfer switch provides main contacts to connect and di...

Страница 21: ...PTION 6H IT CAN BE TURNED TO THE OFF POSITION MAKING IT UNNECESSARY TO UNPLUG THE LOGIC IN THE CASE OF THE ATS DESIGN ANY ATTEMPT TO OPERATE THE MANUAL HANDLE WITHOUT FIRST ISOLATING THE CONTROL CIRCU...

Страница 22: ...be completed 6 1 1 Switching Device Positioning The Magnum drawout switching device has four normal positions REMOVE Withdrawn Figure 28 DISCONNECT Figure 31 TEST Figure 30 CONNECT Figure 29 The REMO...

Страница 23: ...om Instructional Booklet Effective March 2007 Page 23 Fixed and Drawout Magnum Transfer Switches Figure 29 Switching Device in the CONNECT Position Figure 30 Switching Device in the TEST Position Figu...

Страница 24: ...ors See Figure 29 through 32 Red Connect Yellow Test and Green Disconnect To remove the switching device from its compartment follow the procedure just described using a counter clockwise ratcheting m...

Страница 25: ...replacement The bypass isolation switch has two operator panels with switches and lights Figure 35 The following descriptions are for those features that are standard with the bypass isolation switch...

Страница 26: ...luminate 3 Open and rack out the Source 1 switching device see Section 6 The Source 1 isolated light will illuminate and the Source 1 position energized light will no longer be illuminated 4 Inspect a...

Страница 27: ...Cutler Hammer Phase Phase Phase Phase Ground Digitrip 3000 Operatio High Commun Time Overcurrent Curve Shape Pickup x In Time Multiplier Time Program Phase Ground RMS Settings Test Time Trip Cause Sho...

Страница 28: ...elector switch to the OFF position to avoid nuisance starting of the generator while work is being performed on the Source 2 switching device 3 Open the Source 2 switching device 4 Close the Source 1...

Страница 29: ...he electrical operation of the switch IF A TEST SWITCH IS PROVIDED ALWAYS RETURN THE SWITCH TO THE AUTO POSITION AFTER THE TEST IS COMPLETE 8 2 Problem Solving A basic problem solving effort is the fi...

Страница 30: ...Source 1 switching device charged If YES Continue with the other procedures If NO Go through section 8 2 4 first before continuing Step 3 Is the Source 2 switch OPEN If YES Proceed to Step 5 If NO Pr...

Страница 31: ...ontrol power is switched off and the logic plugs are disconnected b Inspect the structure area for any safety hazards or potential mainte nance problems Inspect the area especially where switching dev...

Страница 32: ...eplacement instructions 9 3 1 Cover Removal and Replacement A 3 8 wrench or socket and ratchet is required to perform this procedure Cover Removal Step 1 Locate the bolts used to secure the cover to t...

Страница 33: ...efer to Figure 42 through 45 for assistance with selecting and ordering selected ATS renewal parts Example To order Logic Harness for an ATVIMGB33200XRU transfer switch order Catalog Number T5MGH01 as...

Страница 34: ...e March 2007 Fixed and Drawout Magnum Transfer Switches Figure 43 Figure 44 SERVICE ENTRANCE FUSE BLOCK HARNESS TSMGH16 CLOSED TRANSITION HARNESS TSMGH04 MAGNUM NON AUTO TRANSFORMER PACK TSMGT01 MAGNU...

Страница 35: ...on visit www Eaton com Instructional Booklet Effective March 2007 Page 35 Fixed and Drawout Magnum Transfer Switches Figure 45 SENSING HARNESS TSMGH02 500 KCMIL NEUTRAL TERMINAL I80C046G02 OR 750 KCMI...

Страница 36: ...ntract between the pur chaser and Eaton NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WAR RANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MER CHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEALING OR...

Отзывы: