IB01602011E
For more information visit: www.Eaton.com
Instructional Booklet
Effective: March 2007
Page
5
Fixed and Drawout Magnum Transfer Switches
Figure 4.Typical Bypass Isolation Switch Schematic.
Table 1. Withstand Ratings
Tested in accordance with UL1008.
Eaton Drawout Magnum Transfer Switch will coordinate with a power switching device short time rating. Contact factory for details.
SOURCE 1
SOURCE 1
SOURCE 1
SOURCE 1
BYPASS
SOURCE 1
SOURCE 1
SOURCE 1
AVAILABLE
SOURCE 2
ISOLATED
ISOLATED
POSITION
SOURCE 2
POSITION
SOURCE 2
AVAILABLE
SOURCE 2
SOURCE 2
SOURCE 2
INCOMING
ATS
BYPASS
BYPASS
ATS
LOAD
SOURCE 2
BYPASS
INCOMING
A
A
RATING WHEN USED WITH UPSTREAM CIRCUIT BREAKER
RATING WHEN USED WITH UPSTREAM FUSE
Transfer Switch
Amp Rating
3 Cycle
600V
(kA)
30 Cycle
600V
(kA)
800
100
85
1000
100
85
1200
100
85
1600
100
85
2000
100
85
2500
100
85
3200
100
85