Fixed and Drawout Magnum Transfer Switches

4.5 Power Cable Connections

 

 

Proceed with the following steps:

Step 1:

Verify that the line and load cables comply with  applica-

ble electrical codes.

Step 2:

Verify that the transfer switch rated current and voltage 

(see identification plate on the door of the transfer 

switch) agree with system current and voltage.

Step 3:

After the transfer switch is mounted, provide the conduit 

or cable openings as required. Ensure that no metal filings 

contaminate the transfer switch components.

Step 4:

Test all power cables before connecting them to the unit 

to insure that the conductors or the cable insulation have 

not been damaged while being pulled into position.

Step 5:

Carefully strip the insulation from the power cables.  

Avoid nicking or ringing of the conductor strands.  Pre-

pare the stripped conductor termination end by cleaning 

it with a wire brush.  If aluminum conductors are used, 

apply an appropriate joint compound to the clean conduc-

tor surface area.  Refer to Figure 13

 

for the approximate 

locations of the power connections.

Power cables are to be connected to solderless screw type lugs 

located on the transfer switch switching devices.  Refer to the 

separate Customer Wiring Diagrams supplied with the transfer 

switch equipment for power termination.  Verify that the lugs sup-

plied will accommodate the power cables being used.  Also verify 

that the cables comply with local electrical codes.  Standard trans-

fer switch equipment, as supplied from the factory, will accommo-

date the wire sizes shown in Table

 

5.

Table 5.   Wire Size for Available Power Cable 

Connections.  

  

 

  

Step 6:

  Tighten the cable lugs to the torque identified on the label 

affixed to the door. 

Step 7:  

Make the necessary connections of any options using the 

wiring diagrams supplied with the unit.

Step 8: 

 Connect the engine start wires to the logic connector

J5-1 & J5-2 on the ATC-600/ATC-800 Controller.

 

WARNING

POWER CONDUCTORS MAY HAVE VOLTAGE PRESENT THAT CAN 

CAUSE SEVERE PERSONAL INJURY OR DEATH.  DE-ENERGIZE ALL 

POWER OR CONTROL CIRCUIT CONDUCTORS TO BE CONNECTED 

TO THE TRANSFER SWITCH EQUIPMENT BEFORE BEGINNING TO 

WORK WITH THE CONDUCTORS AND/OR TERMINATING THEM TO 

THE EQUIPMENT.

 

CAUTION

USE OF CABLE LUGS NOT DESIGNED FOR THE TRANSFER SWITCH 

APPLICATIONS MAY CAUSE HEATING PROBLEMS.  BREAKER LUGS 

ONLY MOUNT TO THE BREAKER, WHILE TRANSFER SWITCH LUGS 

MOUNT TO BOTH THE BREAKER AND THE BUS BAR BEHIND THE 

BREAKER.  FOR INSTALLATION INSTRUCTIONS, REFER TO THE 

INSTRUCTION LEAFLET SUPPLIED FOR THE SPECIFIC LUGS.

 

CAUTION

TO HELP PREVENT COMPONENT DAMAGE OR FUTURE MALFUNC-

TIONS, USE EXTREME CARE TO KEEP CONTAMINANTS OUT OF THE 

TRANSFER SWITCH EQUIPMENT WHEN MAKING POWER CABLE 

CONNECTIONS.

DEVICE

SWITCH

RATING

(AMPS)

CABLES

PER

PHASE

RANGE

WIRING SIZE

Switch

800-2000

6

3/0-750 MCM

Switch

2500-3200

9

3/0-750 MCM

Neutral

800-2000

24

4/0-500 MCM

Neutral

2500-3200

36

4/0-500 MCM

 

CAUTION

IMPROPER POWER CABLE CONNECTIONS CAN CAUSE EXCESSIVE 

HEAT AND SUBSEQUENT EQUIPMENT FAILURE.

Содержание Magnum Transfer Switch

Страница 1: ...ction Booklet New Information Description Page Introduction 3 Receiving Handling and Storage 10 Equipment Description 10 Installation and Wiring 16 Operation 20 Drawout and Fixed Switching Devices 22...

Страница 2: ...RISE DURING INSTALLATION OPERATION OR MAINTENANCE AND ALL DETAILS AND VARIA TIONS OF THIS EQUIPMENT DO NOT PURPORT TO BE COVERED BY THESE INSTRUCTIONS IF FURTHER INFORMATION IS DESIRED BY THE PURCHASE...

Страница 3: ...t from the Source 1 power source the transfer switch transfers the load to the Source 2 power source This transfer can be automatic or manual depending upon the type of transfer switch equipment being...

Страница 4: ...The ATS non automatic transfer switch electrically operated and bypass isolation transfer switch are the available types for the configuration described in this manual Operation of the ATS and the by...

Страница 5: ...ing device short time rating Contact factory for details SOURCE 1 SOURCE 1 SOURCE 1 SOURCE 1 BYPASS SOURCE 1 SOURCE 1 SOURCE 1 AVAILABLE SOURCE 2 ISOLATED ISOLATED POSITION SOURCE 2 POSITION SOURCE 2...

Страница 6: ...g con figurations Table 2 Magnum Transfer Switch Configurations All Magnum switching devices are 100 rated Underwriters Lab oratories UL listed and are built and tested in an ISO 9002 certi fied facil...

Страница 7: ...is connects to provide for the drawout functioning The operating mechanism is a two step stored energy mechanism either manu ally or electrically operated When withdrawn on the extendable carriage rai...

Страница 8: ...ted mounting holes to facilitate mounting 1 4 Transfer Switch Catalog Number Identification Transfer switch equipment catalog numbers provide a significant amount of relevant information that pertains...

Страница 9: ...Position 9 12 0200 200A 0300 300A 0400 400A 0600 600A 0800 800A 1000 1000A 1200 1200A 1600 1600A 2000 2000A 2500 2500A 3200 3200A ENCLOSURE Position 14 K Open S NEMA 1 R NEMA 3R T Thru Door Design LIS...

Страница 10: ...2 2 Handling As previously mentioned the transfer switch equipment is pack aged for fork lift movement Protect the equipment from impact at all times and DO NOT double stack Once the equipment is at t...

Страница 11: ...rmal and short circuit protection in either or both switching devices is available Section 3 6 These continuous duty devices are rated for all classes of loads In addition they have high dielectric st...

Страница 12: ...witching device has been closed and an indicator on the switch shows whether it is in the OPEN or CLOSED posi tion and the status of the stored energy mechanism The switching device is closed by energ...

Страница 13: ...15 Voltage Selection Panel Figure 16 North American Market Voltage Selection Terminals Shown Connected to the 120 Vac Taps 3 3 2 International Voltage Selection 208 220 240 380 415 and 600 V 50 60 Hz...

Страница 14: ...the logic scheme refer to the specific logic document associated with the type of logic selected 14 Relay Auxiliary Contacts Provides Form C relay auxiliary contacts E Source 1 Available Provides one...

Страница 15: ...1 Source 2 and Load Circuit rear accessible bus stabs with provision for bus bar connection 21A Optional Power Cable Connection Terminals Provides alternate power cable connection terminals Consult E...

Страница 16: ...witches are factory wired and tested Installation requires solidly mounting the enclosed unit and connecting the power cables and auxiliary pilot circuits Physical mounting proce dures and power cable...

Страница 17: ...ing side and rear covers when applicable See Section 9 3 for cover removal instructions Step 2 Gently maneuver the switch into its location using all of the supplied lift brackets Step 3 Bolt the enc...

Страница 18: ...odate the power cables being used Also verify that the cables comply with local electrical codes Standard trans fer switch equipment as supplied from the factory will accommo date the wire sizes shown...

Страница 19: ...r changing the taps on both transformers replace the trans former pack cover and tighten all four screws 4 7 Mounting the Switching Device in the Drawout Mechanism In structures equipped for drawout c...

Страница 20: ...tarts timing when both sources are paralleled Refer to the IQ Transfer instruction book for additional alarms Section 5 Operation 5 1 General A transfer switch provides main contacts to connect and di...

Страница 21: ...PTION 6H IT CAN BE TURNED TO THE OFF POSITION MAKING IT UNNECESSARY TO UNPLUG THE LOGIC IN THE CASE OF THE ATS DESIGN ANY ATTEMPT TO OPERATE THE MANUAL HANDLE WITHOUT FIRST ISOLATING THE CONTROL CIRCU...

Страница 22: ...be completed 6 1 1 Switching Device Positioning The Magnum drawout switching device has four normal positions REMOVE Withdrawn Figure 28 DISCONNECT Figure 31 TEST Figure 30 CONNECT Figure 29 The REMO...

Страница 23: ...om Instructional Booklet Effective March 2007 Page 23 Fixed and Drawout Magnum Transfer Switches Figure 29 Switching Device in the CONNECT Position Figure 30 Switching Device in the TEST Position Figu...

Страница 24: ...ors See Figure 29 through 32 Red Connect Yellow Test and Green Disconnect To remove the switching device from its compartment follow the procedure just described using a counter clockwise ratcheting m...

Страница 25: ...replacement The bypass isolation switch has two operator panels with switches and lights Figure 35 The following descriptions are for those features that are standard with the bypass isolation switch...

Страница 26: ...luminate 3 Open and rack out the Source 1 switching device see Section 6 The Source 1 isolated light will illuminate and the Source 1 position energized light will no longer be illuminated 4 Inspect a...

Страница 27: ...Cutler Hammer Phase Phase Phase Phase Ground Digitrip 3000 Operatio High Commun Time Overcurrent Curve Shape Pickup x In Time Multiplier Time Program Phase Ground RMS Settings Test Time Trip Cause Sho...

Страница 28: ...elector switch to the OFF position to avoid nuisance starting of the generator while work is being performed on the Source 2 switching device 3 Open the Source 2 switching device 4 Close the Source 1...

Страница 29: ...he electrical operation of the switch IF A TEST SWITCH IS PROVIDED ALWAYS RETURN THE SWITCH TO THE AUTO POSITION AFTER THE TEST IS COMPLETE 8 2 Problem Solving A basic problem solving effort is the fi...

Страница 30: ...Source 1 switching device charged If YES Continue with the other procedures If NO Go through section 8 2 4 first before continuing Step 3 Is the Source 2 switch OPEN If YES Proceed to Step 5 If NO Pr...

Страница 31: ...ontrol power is switched off and the logic plugs are disconnected b Inspect the structure area for any safety hazards or potential mainte nance problems Inspect the area especially where switching dev...

Страница 32: ...eplacement instructions 9 3 1 Cover Removal and Replacement A 3 8 wrench or socket and ratchet is required to perform this procedure Cover Removal Step 1 Locate the bolts used to secure the cover to t...

Страница 33: ...efer to Figure 42 through 45 for assistance with selecting and ordering selected ATS renewal parts Example To order Logic Harness for an ATVIMGB33200XRU transfer switch order Catalog Number T5MGH01 as...

Страница 34: ...e March 2007 Fixed and Drawout Magnum Transfer Switches Figure 43 Figure 44 SERVICE ENTRANCE FUSE BLOCK HARNESS TSMGH16 CLOSED TRANSITION HARNESS TSMGH04 MAGNUM NON AUTO TRANSFORMER PACK TSMGT01 MAGNU...

Страница 35: ...on visit www Eaton com Instructional Booklet Effective March 2007 Page 35 Fixed and Drawout Magnum Transfer Switches Figure 45 SENSING HARNESS TSMGH02 500 KCMIL NEUTRAL TERMINAL I80C046G02 OR 750 KCMI...

Страница 36: ...ntract between the pur chaser and Eaton NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WAR RANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MER CHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEALING OR...

Отзывы: