36
EATON
www.eaton.com
Address
Defi nition
Variable type
Unit
Attribute
Variable format
16H
Phase B current imbalance (fault)
Uint
R
%
17H
Phase C current imbalance (fault)
Uint
R
%
18H
Fault delay time (low word)
Uint
S
R
/50
19H
Fault delay time (high word)
Uint
S
R
/50
1AH
Reserved for future
1BH
Fault type
Uint
R
See 4.1
Equipment diagnosis and power grid status
1CH
Self-diagnostic information
Uint
R
See 4.2
1DH
Grid status information
Uint
R
See 4.3
Protection setting and system parameter setting
28H
Output contact 1, 2
Uint
See 4.4
29H
Output contact 3, 4
Uint
See 4.4
2AH
Load Monitoring 1 setting current
Uint
A
R/W
×1 or ×2
Note 1
2BH
Load Monitoring 1 setting time
Uint
S
R/W
See Table 4.8.1
2CH
Load Monitoring 2 setting current
Uint
A
R/W
×1 or ×2
Note 1
2DH
Load Monitoring 2 setting time
Uint
S
R/W
See Table 4.8.1
2EH
Long delay setting current
Uint
A
R/W
×1 or ×2
Note 1
2FH
Long delay setting time
Uint
S
R/W
See Table 4.8.1
30H
Short delay inverse time setting current
Uint
A
R/W
×1 or ×2
Note 1
31H
Short delay fi xed time setting current
Uint
A
R/W
×1 or ×2
Note 1
32H
Short delay fi xed time setting time
Uint
S
R/W
See Table 4.8.4
33H
Ground residual current setting current
Uint
A
R/W
Ground: ×1 or ×2
Note 1
Residual current: ×0.01
34H
Ground residual current setting time
Uint
S
R/W
See 4.8.2
35H
Ground setting shear coeffi cient
Uint
R/W
See 4.8.3
36H
Instantaneous setting current
Uint
A
×1 or ×2
Note 1
37H
Imbalance action value
Uint
R/W
%
38H
Imbalance action time
Uint
S
See 4.8.5
System parameter setting
39H
System function switch
Uint
R/W
See 4.5
3AH
Protection curve type
Uint
R/W
See 4.6
3BH
Rated current
Uint
A
R/W
See 4.7
3DH
Circuit breaker model
Uint
R
See 4.11
42H
Communication address
Uint
R/W
44H
System clock: minute, second
BCD
R/W
See 4.9
45H
System clock: day, hour
BCD
R/W
46H
System clock: year, month
BCD
R/W
47H
Contact wear
Uint
R/W
%, Can only write 1000
4AH
Number of operations
Uint
R/W
/10, Can only write 0
4CH
Open/closed command --- action command
Uint
W
See 4.10
4DH
ON/OFF command --- preparatory command
Uint
W
4EH
Fault time: minute, second
BCD
R
See 4.9
4FH
Fault time: day, hour
BCD
R
50H
Fault time: year, month
BCD
R
[Note 1]:
×2 when rated current
2000A; otherwise ×1.
Instruction Leafl et
Effective September 2022
IZM6 Series Air Circuit Breaker
Operating Instruction Leafl et