24
EATON
www.eaton.com
PXR6.1 Intelligent Controller
Panel Description
CAUTION
PROTECTION PARAMETERS MUST NOT BE CROSS SET AND REQUIRE
I
r
<I
sd
<Ii.
Controller model
Rated current
LCD interface display
There is a red LED indicator hidden in the curve.
During a fault tripping, the corresponding LED light
flashes to indicate the fault type; during protection
parameter setting up, the LED light is always on to
indicate the item being set
Fault and alarm reset button
Fault / alarm indicator
The LED light is not lit on during normal operation;
the red LED light flashes quickly during a fault trip,
and remains lit on in the event of an alarm
Normal status indicator
The green LED light keeps flashing when the
controller is powered on and in normal operating
status
Protection curve
Test port
A 10-pin testing portal is available at the bottom of
the front panel. A plug-in portable power source box
or a detection unit can be inserted
Measurement: Function Key 1, to switch to
default main menu under Measurement (which is,
the Left key in the password input interface)
Set up: Function Key 2, to switch to the main
menu of parameter setting up (which is, the Right
key in the password input interface)
Protection: Function Key 3, to switch to the main
menu of protection parameter setting up
Information: Function Key 4, to switch to the main
menu of history record and maintenance
Up: Move up the menu content from the current
level, or change the selected parameter up
Down: Move down the menu content from the
current level, or change the selected parameter down
Exit: Exit to the previous-level menu from the current
level, or cancel the selection of the current parameter
Select: Enter the next-level menu from the current
level, or select the current parameter to save the
modified value
1
2
3
4
5
7
8
11
12
13
14
15
16
10
9
6
1
3
2
4
5
6
7
8
9
11
15
12
16
10
14
13
Instruction Leafl et
Effective September 2022
IZM6 Series Air Circuit Breaker
Operating Instruction Leafl et