Setting up parameters
Setting up, query and test functions can be achieved through
operations on the keys on the controller panel, such as “Function
”, , , “Enter
”, and “Return
”.
Press the functional key to cycle through the three states for
selection: setting up, query, and test; press and keys to
select a functional option or increment/decrement a parameter
value; press the “Enter” key to enter into the functioning state
or save the changed data; press the "Return" key to return to the
previous operation.
Step 1: Press the functional key until the “Setup” indicator is
flashing. Press the Enter key again. At this point, the “Setup”
indicator is still flashing, while an indicator for a specific protection
type is lit on, indicating entrance into the value setting up state.
Step 2: Press and keys to cyclically display the original set-
ting data of each setpoint. To modify a certain set point, press the
“Enter” key and the “Setup” indicator will always be lit on. Adjust
it with and keys until the required value is reached. Press the
“Enter” key and the “Save” indicator will be lit on once, indicating
that the modified value has been saved. Press the “Return” key to
exit the modification of the set point.
Step 3: Repeat Step 2 until all the set points are modified. Press
the “Return” key to exit the setup function.
To modify the set points of each protection characteristics, refer
to below tables.
Red light
Green light
Set point with , , “Enter” and “Return” keys to set up
δ
%
Three-phase imbalance set point
S
Delay time set point T
δ
Ig
A/KA
Ground current set point I
g
S
Ground inverse time delay set point T
g
(S green-light is always on)
Ground inverse time shear coeffi cient K (S green-light fl ashes)
L
A/KA
Over-load long delay current set point I
r
S
Over-load long delay inverse delay time set point T
r
S
A/KA
Short-circuit short delay inverse time current set point I
sd1
(S red-light is always on)
Short-circuit short delay fi xed time current set point I
sd2
(S red-light is always on)
S
Short-circuit short delay fi xed delay time set point T
sd
I
A/KA
Short-circuit instantaneous acting current set point I
i
I
C1
A/KA
Load monitoring I
C1
current set point
S
Load monitoring I
C1
inverse time delay set point T
C1
I
C2
A/KA
Load monitoring I
C2
current set point
S
Load monitoring I
C2
inverse time delay set point T
C2
Instruction Leafl et
Effective September 2022
IZM6 Series Air Circuit Breaker
Operating Instruction Leafl et