40
EATON
www.eaton.com
4.10 Remote operation
The remote control can only be transmitted with Function 06. To ensure a response, first send out a preparatory
command, and then issue the action command.
Opening command: FF00;
Closing command: 00FF
[Example]: Carry out a remote operation on Controller 01:
Downstream command example for remote opening:
01 06 00 4D FF 00 58 2D………………Preparatory
command
01 06 00 4C FF 00 09 ED………………Action
command
Downstream command example for remote closing:
01 06 00 4D 00 FF 59 9D………………Preparatory
command
01 06 00 4C 00 FF 08 5D………………Action
command
If the control command is acquired as 0, this means the preparatory command has not been issued yet
[Note]: A certain delay time is required between the preparatory and action commands, which is not less than
100ms
4.11 Circuit breaker model table
No.
0
1
2
3
4
5
6
7
8
CB model
IZM65
IZM67
IZM69
Undefi ned
Instruction Leafl et
Effective September 2022
IZM6 Series Air Circuit Breaker
Operating Instruction Leafl et