background image

w

x

yz

{|

}~

€‚ƒ

„…~"†

‡

ˆ

‡

†

‰

‚&…

†

ˆ

‚Š

‹

Œ



Ž





‘

’

Ž

“



”

•

’

–

—˜™8š›œ˜=žŸ8™8 =—š¡Až

¢

£

¤

¥

¦

¥

§

¨J©

ª

«

¬

­P®¯°

±²"³"°

´®®µ

·

¸

¹

·

º

»

¼

½"¾8¿AÀ¾Á

ÂfÃ

ÄiÅkÆÇÆÆÆÆÈÉÊËÈÆ

Ì

Í

Î

Ï

36

Ð

Ñ

48

Setting Parameters Using RS232 Serial Interface and PC

Remote operation or remote parameter adjustment may be executed through the RS232 serial
interface. The following transmission parameters are applicable:

Transmission rate:

19200 baud

Data format:

8 data-bits, 1 stop-bit, no parity

Terminal emulation:

TTY

Voltage level: 

12 V

The connection cable must meet the following requirements:

 

Use a null modem cable

 

The card connection is a 9-pole SUB-D female connector

 

For the connection use a 3-poled cable

 

Pins 1, 7 and 9 should be unassigned

 

RxD is assigned to pin 2

 

TxD is assigned to pin 3

 

GND is assigned to pin 5

 

The pins 4, 6 and 8 are internally shorted (null modem cable).

Table 4 Shows the pin assignments for the 9-pin socket on the front panel.

Pin

Signal

1

Reserved

2

RxD

3

TxD

4

Connected with Pin 6 and Pin 8

5

GND

6

Connected with Pin 4 and Pin 8

7

Reserved

8

Connected with Pin 4 and Pin 6

9

Reserved

Table 4: Pin connections

Wrong pin assignments will result in the following fault messages:

Display

 

---d

there is an error at pin 1 (wrong data)

 

---c

there is an error at pin 7 (time out)

 

no display possible error at pin 9 (short circuit at GND).

The proper cable to connect the ER9.3 card and a PC is also available from Eaton Fluid Power
GmbH, Germany (Order number: HC000000316911). The length of the cable is about 2.50 m.
Parameter editing can be done using the enclosed ER9.3-Tool. The tool allows editing, downloading,
uploading and saving single parameters or parameter sets. The software tool includes a
comprehensive online help.

Setting Values

The ER9.3 card offers the possibility to set three analog and 4 + 1 digital values.  Fig. 3 shows the
block structure and links between values.

Содержание ER9.3-10

Страница 1: ...o f i p m q r s tu tv w x y z 0 3 5 7 7 7 7 7 9 7 7 9 25 48 Digitaler Reglerverst rker ER9 3 10 zur elektrohydraulischen Pumpenreglung der EATON Axialkolbenpumpen X und W Design Digital Amplifier And...

Страница 2: ...ll Default Values of all Parameters 35 Setting Parameters Using RS232 Serial Interface and PC 36 Setting Values 36 Digital Set Values 37 Analog Set Values 37 Ramp Function 38 Controller Structure 38 T...

Страница 3: ...M N O P Q1R P S TVU WYX Z Z Z Z Z _ a b Z c d e f 27 g h 48 Adjustment of Zero Point on Swash Plate Angle Sensor 45 Verification of Control Behavior 47 Modifying Sensor Gain 47 Closed Loop Function 47...

Страница 4: ...ints in the range of 0 10V 14 bit resolution Additional single ended independent set point inputs one for the range of 0 10V 14 bit resolution the other for the range of 0 20 mA 4 20 mA 14 bit resolut...

Страница 5: ...The position of the swash plate angle the displacement and the pump outlet flow are proportionally changed to the set value In the static state condition i e set value is equal to actual swash plate a...

Страница 6: ...gold plated EMC Protection Burst on wires as per EN 61000 4 4 HF Field as per EN 61000 4 3 ESD as per EN 61000 4 2 Emissions Emissions depending on power as per EN 50011 Radiated emissions as per EN 5...

Страница 7: ...r Test jacks Solenoid current sensor 1 set value monitor and GND Auxiliary voltage 10 V max load 10 mA Interface RS232 with 9 pol Sub D connector on front panel and a second connector is available on...

Страница 8: ...lues 6 Digital set value 3 S1 03 DIO 3 0 Pulse Digital set value 4 S1 04 8 ENABLE DI 1 Reserved Digital set value 1 S1 01 10 Sensor 1 FB 1 UE IE Analog output RxD RS232 12 Analog set value 6 UE S1 06...

Страница 9: ...set point voltage At the socket FB1 the actual analog feedback value d10 can be measured The reading is proportional to the actual value and has the relation of 1 2 Element Function Status LED s disp...

Страница 10: ...troller and amplifier ER9 3 10 has a display and keypad to change the card parameters Additionally it is possible to change the card parameters using the enclosed ER9 3 Tool with a PC via the RS232 se...

Страница 11: ...87 9 5 868 4 7 A B C D EF EG HJI K L M NPO Q R S T U R V O O W X Y Z Y _ 8aAb c dfe gihkj l j j j j m n o p m j q r s t 35 u v 48 Recall Default Values of a Single Parameter Recall Default Values of a...

Страница 12: ...ocket on the front panel Pin Signal 1 Reserved 2 RxD 3 TxD 4 Connected with Pin 6 and Pin 8 5 GND 6 Connected with Pin 4 and Pin 8 7 Reserved 8 Connected with Pin 4 and Pin 6 9 Reserved Table 4 Pin co...

Страница 13: ...th binary combinations a total of 16 values can be selected When parameter S1 08 is activated 32 different set points can be selected Analog Set Values The set points S1 05 and S1 06 are designed for...

Страница 14: ...amp Parameters E08 0 effects only digital set points constant time base and linear E08 1 effects all set points constant rise rate and linear E08 2 not used The ramp function generator can be immediat...

Страница 15: ...P f f 1 3 1 39 48 Sensor adaption Solenoid A Solenoid B Swash plate angle Analogous const rise const time Prop Valve Vickers KDG4V Fig 6 Controller structure and definition of parameters...

Страница 16: ...mplifier card ER9 3 10 is used in connection with the fail safe function If the lag error value set value actual value is greater or less than the values set in parameters C1 21 and C1 22 for longer t...

Страница 17: ...on off C1 02 Linearization 1 0 5 off linear 1 5 curve 2 C1 03 Gain A V V 00 01 00 00 02 00 01 00 C1 04 Gain B V V 00 01 00 00 02 00 01 00 C1 05 Set value sign 1 1 1 negative off off 1 positive Custom...

Страница 18: ...nit Step Min Max Code Value E00 Operation mode Note 5 Reserved and 9 Reserved 1 1 11 1 Open loop one valve 2 Open loop two valves 3 Closed loop one valve 4 Closed loop one application 6 Closed loop va...

Страница 19: ...f max rated current 2 000 E14 Dither Frequency Hz 0001 0001 0300 0130 E15 Select load store 1 0 1 0 Store into goal 1 Load from goal 0 E16 Action load store 1 0 1 0 no action 1 Start action 0 E17 Set...

Страница 20: ...5 Signal A 0 001 9 999 9 999 d1 06 Signal B 0 001 9 999 9 999 d1 07 Current A A 0 001 0 000 5 000 d1 08 Current B A 0 001 0 000 5 000 d1 09 Total current A 0 001 0 000 5 000 d1 10 Desired value V 0 00...

Страница 21: ...o the fail safe valve solenoid NOTE The switching output 20b can drive an inductive load with 24V and1A max If the fail safe valve solenoid has variant electrical values the control needs to be done u...

Страница 22: ...z Monitor V 10d 26z 16z 10b 18b Comparator Error A B p Pilot p T 1 2 1 2 a b A B 1 2 3 B C A 18d 26db Digital GND Switching Output 1A 24V int Set P 1 01 int Set P 1 02 int Set P 1 03 int Set P 1 04 in...

Страница 23: ...oo small In this case increase the sensor gain C1 10 by 0 1V steps until the lag error D1 12 is set to zero Please pay attention that proper adjustment of the sensor gain is only possible for one maxi...

Страница 24: ...0 1 243 5 64 783 9 A B C D EGF H I J K L I M F F N O P QR P S T U V W X8Y W Z _ba c a a a aedgf h i dea j k l m 48 n o 48 nderung Revision BESCHREIBUNG DESCRIPTION p q r s r t p q rus ruvxw y p z p yu...

Отзывы: