16

Programming

EPCT FirE sEriEs FirE PumP ConTrollEr

   MN124016EN   August 2019   www.eaton.com

5.6.9  Low foam shutdown

The controller can be programmed to shutdown when a 

low foam condition is present. If this is desired, the user 

will select Enabled. There will also be a shutdown delay 

timer built in (Range: 0-99 Seconds, Default: 0 seconds) 

along with the selection of either a Manual or Automatic 

reset. If Manual Reset is selected, the “Press to Reset 

All Conditions” in the notification area must be activated 

to reset the alarm. If Automatic Reset is selected (default 

reset mode), a delay timer (Range: 0-99 Seconds, Default: 

0 Seconds) must be set. Once the input is closed, the 

controller will start the Low Foam Delay timer. When the 

timer expires, if the input for Low Foam is still closed, the 

controller will shutdown the motor. When the input has 

cleared, the controller will initiate the reset timer. After 

the reset timer has elapsed, the controller will resume 

automatic operation. All timers will be displayed in the 

notification area. Low Foam Shutdown will have no affect on 

Local Starts, Remote Manual Starts, or Emergency Starts.

ATTENTION 

Nfpa 20 specifically prohibits the installation of any device 

in the suction piping that will restrict starting or stopping 

of the fire pump. Eaton assumes no liability when this 

function is used.

5.6.10 Proof pressure switch

An external pressure switch can be activated on one of the 

inputs. Enabling this feature requires that the programmed 

input for Proof Pressure Switch is closed to allow the FPC 

to start the motor.

5.6.11 Pressure units

The user can select which pressure unit of measure is to 

be displayed. The units can be programmed for PSI, BAR, 

or kPa.

5.6.12 Pressure transducer

Some applications do not require a pressure sensor to sense 

the system pressure in order to start the pump motor when 

required. In order to accomplish this, the pressure sensor 

can be disabled through this menu item. Once disabled, the 

pressure start point, pressure stop point, low pressure alarm, 

and high pressure alarm set-points will be removed from the 

menu system. Refer to 4.3 for the Remote Auto Start input 

to use instead of the pressure sensor.

5.6.13 Calibrate transducer

The controller allows for three (3) different forms of calibration.
Full Calibration requires the system to be reduced to a 

known value, typically 0 psi. This value is then entered into 

the controller. The system pressure is then increased to a 

higher known value which is also entered into the controller. 

Calibrate Using Current Pressure is a partial calibration. The 

low pressure point is assumed to be correct. The high point 

is adjusted based on the actual system pressure. 
Reset to Factory Default resets the transducer calibration to 

the original factory settings.

5.7 Timer values tab

Refer to Appendix F for the menu structure of the Timer 

Values tab

5.7.1  Minimum run time (RPT)

The minimum run timer is used to automatically stop the 

controller after a programmed time. The timer will start 

timing once the pump has reached a running condition. If 

Automatic Shutdown is disabled, the RPT will not be active. 

It will not start on Remote Manual Starts, Local Starts, and 

Emergency Starts. While it is timing the amount of time left 

on the timer will be displayed in the notification area.

5.7.2  Acceleration timer (AT)

The acceleration timer can be programmed to allow the 

controller to run in a reduced voltage state for a period of 

time. This timer will start timing once a start signal has been 

received and the startup relay has energized.

5.7.3  Sequential start time

The sequential start timer can be set to delay the starting 

of the pump when a automatic starting condition exists. If, 

during the timing of the sequential timer, the pressure rises 

above the pressure start point, the timer will stop timing 

and the starting sequence will discontinue. When the SST 

is timing, the time left will be displayed in the notification 

area. The SST will not work on Remote Manual Starts, Local 

Starts, and Emergency Starts.

5.7.4  Fail to start timer (FTS)

The controller determines that the motor is successfully 

running when, at least, 20% of the programmed motor 

full-load current has been reached. If the controller initiates 

a start sequence, manual or automatic, and the calculated 

current has not reached 20% of the motor full-load current 

after the Fail To Start timer has timed out, the Fail to Start 

alarm will be generated.

5.7.5  Fail to stop timer

The controller determines that the motor has successfully 

stopped when the calculated current has dropped below 

the 20% threshold after a call-to-stop was initiated. If the 

controller initiates a stop sequence, manual or automatic, 

and the calculated current has not dropped below 20% of 

the motor full-load current after the Fail To Stop timer has 

timed out, the Fail to Stop alarm will be generated.

Содержание EPCT Fire Series

Страница 1: ...Installation manual EPCT Fire series Fire Pump Controller...

Страница 2: ...PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS D...

Страница 3: ...2 4 USB port 4 3 3 Power I O board 4 3 4 ATS board if equipped 4 3 5 Main isolating switch circuit interrupter 4 3 6 Contactor s 4 3 7 External pushbuttons 5 3 8 Transfer switch components 5 4 0 Opera...

Страница 4: ...4 5 4 Power phase failure 4CR 10 4 5 5 Phase reversal 5CR 10 4 5 6 Pump run 6CR 10 5 0 Programming 11 5 1 Introduction 11 5 2 Navigation 11 5 3 Startup tab 12 5 3 1 Quick setup 12 5 3 2 Setup phase r...

Страница 5: ...5 5 5 2 Service contact information 15 5 5 3 Factory contact information 15 5 6 Pressure settings tab 15 5 6 1 Start pressure 15 5 6 2 Stop pressure 15 5 6 3 Low pressure alarm 15 5 6 4 High pressure...

Страница 6: ...0 6 2 Main contacts 20 6 3 ATS electrical control circuit 20 6 4 Mechanical transfer mechanism 20 6 5 ATS control board touchscreen display 21 6 5 1 Inputs 21 6 5 2 Outputs 21 6 5 3 Touchscreen displa...

Страница 7: ...ture continued 34 Appendix F timer values tab menu structure 35 Appendix G a ATS settings tab menu structure 36 Appendix G b ATS settings tab menu structure continued 37 Appendix H a alarm setpoints t...

Страница 8: ...ulations must be strictly observed in the installation operation and maintenance of this device CAUTION Completely read and understand the material presented in this document before attempting install...

Страница 9: ...to the incoming AC power supply and motor wiring Install necessary conduit using proper methods and tools Recommend entry point is on the bottom of the enclosure Incoming AC line voltage is clearly ma...

Страница 10: ...sed for reduced in rush current controllers only The AT will be factory set but will automatically adjust depending on the starting method that the controller is programmed to If it is found that more...

Страница 11: ...Source 2 Disconnected Refer to the schematic diagram mounted on the inside of the controller door for all connection points specific to the controller 3 5 Main isolating switch circuit interrupter Th...

Страница 12: ...tart of the pump motor Stop The stop pushbutton will initiate the stopping sequence of the fire pump motor Releasing the stop button will put the controller back into the automatic mode If a starting...

Страница 13: ...r where when it expires the controller will exit the Welcome Screen to the Home tab and resume normal operation The three 3 buttons on this screen are CLOSE AND DISABLE WELCOME SCREEN CLOSE WELCOME SC...

Страница 14: ...7 Operation EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com 4 2 1 2 Home Tab without an ATS Fig 1 HOME tab idle Fig 2 HOME tab pump running...

Страница 15: ...Source 2 external disconnect handle and the motor The HOME tab will display the current system pressure reading along with the programmed Start and Stop setpoints At the bottom of the HOME tab is the...

Страница 16: ...is in the Connected state the EPCT controller will initiate an automatic start sequence If programmed to automatically shutoff the pump when the input is in a Disconnected state and the RPT has elapse...

Страница 17: ...ill delay all automatic starting means for the duration of the programmed timer 4 5 Output relays The primary control outputs of the EPCT controller are dry relay contacts These relays are comprised o...

Страница 18: ...ingle phase start Enabled Disabled Auto shutdown Enabled Disabled Motor HP 0 9999 HP Nominal voltage 200 7200V Phases Single Phase Three Phase Description Range System Frequency 50Hz 60Hz CT Ratio 50...

Страница 19: ...bled Dropout 100 999 Disabled Pickup Source 2 Under Frequency 0 100 Disabled Dropout 0 100 Disabled Pickup Description Range Source 2 Over Frequency 100 999 Disabled Dropout 100 999 Disabled Pickup In...

Страница 20: ...s message history startup and configuration files to a USB device 5 4 Panel setup tab Refer to Appendix C for the menu structure of the Panel Setup tab 5 4 1 Language Nine 9 languages are offered as s...

Страница 21: ...ion can then be used on other controllers that require the same configuration setup The configuration will not adjust functionality settings 5 4 21 Load configuration to USB A configuration file will...

Страница 22: ...oint can be selected that will be recorded in the controller s history and displayed in the notification area if enabled 5 6 4 High pressure alarm A high pressure alarm point can be selected that will...

Страница 23: ...to a known value typically 0 psi This value is then entered into the controller The system pressure is then increased to a higher known value which is also entered into the controller Calibrate Using...

Страница 24: ...ller be equipped with an ATS the screen will provide the ability to have different setpoints for either Source 5 8 7 Frequency alarm settings This menu item allows the user to adjust frequency dropout...

Страница 25: ...ory stats diag Tab history statistics diagnostics 5 10 1 Message history The EPCT controller will record a number of items in its memory to assist with troubleshooting of the system and or the fire pu...

Страница 26: ...cer information The input status page will display the state of each input contact Pressing the input buttons the controller will override the state of that input for one minute If the button is depre...

Страница 27: ...he ATS control board Energizing this relay will result in closure of the contact between terminals 72 73 on the ATS board Closing this contact will energize the ATS motor and the motor brake The motor...

Страница 28: ...graphic on the display will show the Source 1 ATS contact closed and the Source 2 ATS contact open When in the Source 2 position the single line graphic on the display will show the Source 2 ATS conta...

Страница 29: ...y start and run the generator at specific intervals The Weekly Timer is set by adjusting the day hour and minute of the desired weekly run time the length of time that this test shall be performed a t...

Страница 30: ...ted at 8A 250VAC and 30 VDC and it includes two 2 pull apart six 6 pin terminal blocks 7 2 1 Programming i Refer to Appendix L 7 3 MODBUS Board It includes an eight 8 pole dip switch bank designed to...

Страница 31: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix A menu structure Note N Pressing the Back or Cancel button when available will return the screen to the...

Страница 32: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix B startup tab menu structure Note N Pressing the Back or Cancel button when available will return the s...

Страница 33: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix C a panel setup tab menu structure Note N Pressing the Back or Cancel button when available will return...

Страница 34: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix C b panel setup tab menu structure continued Note N Pressing the Back or Cancel button when available w...

Страница 35: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix C c panel setup tab menu structure continued Note N Pressing the Back or Cancel button when available w...

Страница 36: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix C d panel setup tab menu structure continued Note N Pressing the Back or Cancel button when available w...

Страница 37: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix C e panel setup tab menu structure continued Note N Pressing the Back or Cancel button when available w...

Страница 38: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix D help tab menu structure Note N Pressing the Back or Cancel button when available will return the scre...

Страница 39: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix E a pressure settings tab menu structure Note N Pressing the Back or Cancel button when available will...

Страница 40: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix E b pressure settings tab menu structure continued Note N Pressing the Back or Cancel button when avail...

Страница 41: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix E c pressure settings tab menu structure continued Note N Pressing the Back or Cancel button when avail...

Страница 42: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix F timer values tab menu structure Note N Pressing the Back or Cancel button when available will return...

Страница 43: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix G a ATS settings tab menu structure Note N Pressing the Back or Cancel button when available will retur...

Страница 44: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix G b ATS settings tab menu structure continued Note N Pressing the Back or Cancel button when available...

Страница 45: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix H a alarm setpoints tab menu structure Note N Pressing the Back or Cancel button when available will re...

Страница 46: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix H b alarm setpoints tab menu structure continued Note N Pressing the Back or Cancel button when availab...

Страница 47: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix I a inputs outputs tab menu structure Note N Pressing the Back or Cancel button when available will ret...

Страница 48: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix I b inputs outputs tab menu structure continued Note N Pressing the Back or Cancel button when availabl...

Страница 49: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix J History stats diag Tab menu structure Note N Pressing the Back or Cancel button when available will r...

Страница 50: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix K Relay option board tab menu structure Note N Pressing the Back or Cancel button when available will r...

Страница 51: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix L a 4 20 mA device tab menu structure Note N Pressing the Back or Cancel button when available will ret...

Страница 52: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix L b 4 20 mA device tab menu structure continued Note N Pressing the Back or Cancel button when availabl...

Страница 53: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix M MODBUS board tab menu structure Note N Pressing the Back or Cancel button when available will return...

Страница 54: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix N Supervisory alarm option board tab menu structure Note N Pressing the Back or Cancel button when avai...

Страница 55: ...has failed MOTOR OVERLOAD The amperage draw has exceeded 125 of the programmed motor full load amps LOW RESERVOIR The controller has received a low reservoir signal HIGH RESERVOIR The controller has...

Страница 56: ...tage measured by the controller has exceeded the programmed over voltage alarm set point for the normal source S2 OVER VOLTAGE The voltage measured by the controller has exceeded the programmed over v...

Страница 57: ...rror There is no communication received from the display board 42 Frequency Error The frequency measurement is not receiving an accepted frequency 40 72Hz 43 Zero Cross Error The board did not receive...

Страница 58: ...AX HP 25 30 40 60 75 1 14 1 0 Per CU AL 1 14 2 0 CU AL 40 50 75 100 100 1 4 4 0 Per CU 1 4 350MCM CU AL 75 75 150 200 200 1 3 350MCM Per CU AL 1 4 350MCM CU AL 100 125 200 250 300 2 3 0 250MCM Per CU...

Страница 59: ...ay Burlington ON L7L 5Z1 Email chcfirepump eaton com Web www chfire com 2019 Eaton All Rights Reserved Printed in USA Publication No MN124016EN August 2019 Eaton is a registered trademark All trademar...

Отзывы: