background image

2

Installation and electrical connections

EPCT FirE sEriEs FirE PumP ConTrollEr

   MN124016EN   August 2019   www.eaton.com

2.0   Installation and electrical connections

2.1 Mounting

Carefully unpack the controller and inspect thoroughly.
The controller should be located as close as is practical to 

the motor it controls and shall be within sight of the electric 

motor, preferably ten feet or less.
The EPCT controller is designed for either wall or floor 

mounting; use Grade 5 bolts. Note that the controller is 

not free standing and must be mounted with feet or bolted 

securely to a wall. For dimensional and weight data please 

refer to the respective data sheets for the various types of 

Fire Pump Controllers.

2.2 Pressure switch connections

NOTICE

Water lines to the pressure switch must be free from dirt 

and contamination

The EPCT is equipped with a pressure sensor. The controller 

is provided with a 1/2” NPT female system pressure 

connection located on the bottom, external side of the 

enclosure. The connection should be installed as per NFPA, 

pamphlet no. 20.
The actual pressure is displayed on the main display. Precise 

start and stop pressure set points can be programmed in the 

controller. Refer to Section 5 for programming instructions.
The maximum operating pressure of the pressure sensor 

and internal plumbing components is listed on the 

controller nameplate.

2.3 Electrical connections

NOTICE

All conduit connections to the controller are recommended 

to be installed on the bottom of the controller. Refer to the 

assoicated dimensional drawing for reference. Drilling or 

installing conduit above the microprocessor boards may 

void warranty.

All electrical connections should meet national and local 

electrical codes and standards.
The controller should be located or so protected that it will 

not be damaged by water escaping from pumps or pump 

connections. Current carrying parts of controllers shall be a 

minimum of 12 inches (305mm) above the floor.
Prior to starting, verify all data on the nameplate such as: 

catalog number, AC line voltage, horsepower, and frequency.
Inspect all electrical connections, components, and wiring 

for any visible damage. Correct as necessary. Ensure that all 

electrical connections are tightened before energizing.

Refer to the wiring schematic affixed to the enclosure door 

for all wiring information pertaining to the incoming AC 

power supply and motor wiring.
Install necessary conduit using proper methods and tools. 

Recommend entry point is on the bottom of the enclosure.
Incoming AC line voltage is clearly marked L1, L2, L3, and 

ground, located at the top of the enclosure.

2.3.1  Wire sizes

For control wiring, use #14 AWG wire for all electrical 

connections.
For power wiring sizes refer to Appendix Q.

2.3.2  Electrical checkout instructions

The EPCT controller is designed to be phase sensitive. L1, 

L2 & L3 should be connected to A, B & C respectively. 

Energize the controller by closing the isolation switch 

(MIS) and circuit breaker (CB). If the phases are connected 

incorrectly, the ‘Phase Reversal’ alarm and graphic will be 

displayed on the screen. To correct this condition, refer to 

Appendix H to correct the phase reversal setting. 
The EPCT has a phase reversal setup procedure that guides 

the user through a step by step process to program the 

phase rotation. With the controller energized, operate the 

‘Bump Motor’ feature through the Setup Phase Reversal in 

the Startup tab on the display to check the rotation of the 

motor. If the rotation is incorrect, disconnect power and 

reverse the connection of the load terminals of the motor 

contactor T1, T2 & T3. If the controller is equipped with an 

automatic transfer switch (ATS), the guide will prompt the 

user to start the generator, transfer and bump the motor. 

ote:

N

On models Primary Resistor (FD/FT40), Wye Delta 

(Star-Delta) Open (FD/FT70) and Wye Delta (Star-

Delta) Closed (FD/FT80) models, the connection 

must be changed on both contactors, 1M and 2M.

Adjust the pressure set points detailed in Appendix E.
With the controller isolated and the ‘Start Pressure’ and 

‘Stop Pressure’ values programmed, energize the controller. 

If the system water pressure is lower than the start 

pressure, the controller will start the pump. If the controller 

is set up for fully automatic operation, the controller will 

stop the pump when the pressure is above the stop point 

and the running period timer (RPT) has completed its timed 

interval. The system pressure must be equal to or greater 

than the programmed stop pressure value, otherwise the 

pump will stop only when the pushbutton is pushed. If the 

controller is not setup for automatic shutdown operation 

(programmed for manual stop mode), the stop pushbutton 

must be operated to stop the pump.

The circuit breaker setting is factory set and should not 

be adjusted.
If required, the running period timer (RPT) must be set 

for a minimum of ten (10) minutes. Refer to Appendix F 

for programming of the RPT.

Содержание EPCT Fire Series

Страница 1: ...Installation manual EPCT Fire series Fire Pump Controller...

Страница 2: ...PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS D...

Страница 3: ...2 4 USB port 4 3 3 Power I O board 4 3 4 ATS board if equipped 4 3 5 Main isolating switch circuit interrupter 4 3 6 Contactor s 4 3 7 External pushbuttons 5 3 8 Transfer switch components 5 4 0 Opera...

Страница 4: ...4 5 4 Power phase failure 4CR 10 4 5 5 Phase reversal 5CR 10 4 5 6 Pump run 6CR 10 5 0 Programming 11 5 1 Introduction 11 5 2 Navigation 11 5 3 Startup tab 12 5 3 1 Quick setup 12 5 3 2 Setup phase r...

Страница 5: ...5 5 5 2 Service contact information 15 5 5 3 Factory contact information 15 5 6 Pressure settings tab 15 5 6 1 Start pressure 15 5 6 2 Stop pressure 15 5 6 3 Low pressure alarm 15 5 6 4 High pressure...

Страница 6: ...0 6 2 Main contacts 20 6 3 ATS electrical control circuit 20 6 4 Mechanical transfer mechanism 20 6 5 ATS control board touchscreen display 21 6 5 1 Inputs 21 6 5 2 Outputs 21 6 5 3 Touchscreen displa...

Страница 7: ...ture continued 34 Appendix F timer values tab menu structure 35 Appendix G a ATS settings tab menu structure 36 Appendix G b ATS settings tab menu structure continued 37 Appendix H a alarm setpoints t...

Страница 8: ...ulations must be strictly observed in the installation operation and maintenance of this device CAUTION Completely read and understand the material presented in this document before attempting install...

Страница 9: ...to the incoming AC power supply and motor wiring Install necessary conduit using proper methods and tools Recommend entry point is on the bottom of the enclosure Incoming AC line voltage is clearly ma...

Страница 10: ...sed for reduced in rush current controllers only The AT will be factory set but will automatically adjust depending on the starting method that the controller is programmed to If it is found that more...

Страница 11: ...Source 2 Disconnected Refer to the schematic diagram mounted on the inside of the controller door for all connection points specific to the controller 3 5 Main isolating switch circuit interrupter Th...

Страница 12: ...tart of the pump motor Stop The stop pushbutton will initiate the stopping sequence of the fire pump motor Releasing the stop button will put the controller back into the automatic mode If a starting...

Страница 13: ...r where when it expires the controller will exit the Welcome Screen to the Home tab and resume normal operation The three 3 buttons on this screen are CLOSE AND DISABLE WELCOME SCREEN CLOSE WELCOME SC...

Страница 14: ...7 Operation EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com 4 2 1 2 Home Tab without an ATS Fig 1 HOME tab idle Fig 2 HOME tab pump running...

Страница 15: ...Source 2 external disconnect handle and the motor The HOME tab will display the current system pressure reading along with the programmed Start and Stop setpoints At the bottom of the HOME tab is the...

Страница 16: ...is in the Connected state the EPCT controller will initiate an automatic start sequence If programmed to automatically shutoff the pump when the input is in a Disconnected state and the RPT has elapse...

Страница 17: ...ill delay all automatic starting means for the duration of the programmed timer 4 5 Output relays The primary control outputs of the EPCT controller are dry relay contacts These relays are comprised o...

Страница 18: ...ingle phase start Enabled Disabled Auto shutdown Enabled Disabled Motor HP 0 9999 HP Nominal voltage 200 7200V Phases Single Phase Three Phase Description Range System Frequency 50Hz 60Hz CT Ratio 50...

Страница 19: ...bled Dropout 100 999 Disabled Pickup Source 2 Under Frequency 0 100 Disabled Dropout 0 100 Disabled Pickup Description Range Source 2 Over Frequency 100 999 Disabled Dropout 100 999 Disabled Pickup In...

Страница 20: ...s message history startup and configuration files to a USB device 5 4 Panel setup tab Refer to Appendix C for the menu structure of the Panel Setup tab 5 4 1 Language Nine 9 languages are offered as s...

Страница 21: ...ion can then be used on other controllers that require the same configuration setup The configuration will not adjust functionality settings 5 4 21 Load configuration to USB A configuration file will...

Страница 22: ...oint can be selected that will be recorded in the controller s history and displayed in the notification area if enabled 5 6 4 High pressure alarm A high pressure alarm point can be selected that will...

Страница 23: ...to a known value typically 0 psi This value is then entered into the controller The system pressure is then increased to a higher known value which is also entered into the controller Calibrate Using...

Страница 24: ...ller be equipped with an ATS the screen will provide the ability to have different setpoints for either Source 5 8 7 Frequency alarm settings This menu item allows the user to adjust frequency dropout...

Страница 25: ...ory stats diag Tab history statistics diagnostics 5 10 1 Message history The EPCT controller will record a number of items in its memory to assist with troubleshooting of the system and or the fire pu...

Страница 26: ...cer information The input status page will display the state of each input contact Pressing the input buttons the controller will override the state of that input for one minute If the button is depre...

Страница 27: ...he ATS control board Energizing this relay will result in closure of the contact between terminals 72 73 on the ATS board Closing this contact will energize the ATS motor and the motor brake The motor...

Страница 28: ...graphic on the display will show the Source 1 ATS contact closed and the Source 2 ATS contact open When in the Source 2 position the single line graphic on the display will show the Source 2 ATS conta...

Страница 29: ...y start and run the generator at specific intervals The Weekly Timer is set by adjusting the day hour and minute of the desired weekly run time the length of time that this test shall be performed a t...

Страница 30: ...ted at 8A 250VAC and 30 VDC and it includes two 2 pull apart six 6 pin terminal blocks 7 2 1 Programming i Refer to Appendix L 7 3 MODBUS Board It includes an eight 8 pole dip switch bank designed to...

Страница 31: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix A menu structure Note N Pressing the Back or Cancel button when available will return the screen to the...

Страница 32: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix B startup tab menu structure Note N Pressing the Back or Cancel button when available will return the s...

Страница 33: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix C a panel setup tab menu structure Note N Pressing the Back or Cancel button when available will return...

Страница 34: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix C b panel setup tab menu structure continued Note N Pressing the Back or Cancel button when available w...

Страница 35: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix C c panel setup tab menu structure continued Note N Pressing the Back or Cancel button when available w...

Страница 36: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix C d panel setup tab menu structure continued Note N Pressing the Back or Cancel button when available w...

Страница 37: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix C e panel setup tab menu structure continued Note N Pressing the Back or Cancel button when available w...

Страница 38: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix D help tab menu structure Note N Pressing the Back or Cancel button when available will return the scre...

Страница 39: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix E a pressure settings tab menu structure Note N Pressing the Back or Cancel button when available will...

Страница 40: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix E b pressure settings tab menu structure continued Note N Pressing the Back or Cancel button when avail...

Страница 41: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix E c pressure settings tab menu structure continued Note N Pressing the Back or Cancel button when avail...

Страница 42: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix F timer values tab menu structure Note N Pressing the Back or Cancel button when available will return...

Страница 43: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix G a ATS settings tab menu structure Note N Pressing the Back or Cancel button when available will retur...

Страница 44: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix G b ATS settings tab menu structure continued Note N Pressing the Back or Cancel button when available...

Страница 45: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix H a alarm setpoints tab menu structure Note N Pressing the Back or Cancel button when available will re...

Страница 46: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix H b alarm setpoints tab menu structure continued Note N Pressing the Back or Cancel button when availab...

Страница 47: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix I a inputs outputs tab menu structure Note N Pressing the Back or Cancel button when available will ret...

Страница 48: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix I b inputs outputs tab menu structure continued Note N Pressing the Back or Cancel button when availabl...

Страница 49: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix J History stats diag Tab menu structure Note N Pressing the Back or Cancel button when available will r...

Страница 50: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix K Relay option board tab menu structure Note N Pressing the Back or Cancel button when available will r...

Страница 51: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix L a 4 20 mA device tab menu structure Note N Pressing the Back or Cancel button when available will ret...

Страница 52: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix L b 4 20 mA device tab menu structure continued Note N Pressing the Back or Cancel button when availabl...

Страница 53: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix M MODBUS board tab menu structure Note N Pressing the Back or Cancel button when available will return...

Страница 54: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix N Supervisory alarm option board tab menu structure Note N Pressing the Back or Cancel button when avai...

Страница 55: ...has failed MOTOR OVERLOAD The amperage draw has exceeded 125 of the programmed motor full load amps LOW RESERVOIR The controller has received a low reservoir signal HIGH RESERVOIR The controller has...

Страница 56: ...tage measured by the controller has exceeded the programmed over voltage alarm set point for the normal source S2 OVER VOLTAGE The voltage measured by the controller has exceeded the programmed over v...

Страница 57: ...rror There is no communication received from the display board 42 Frequency Error The frequency measurement is not receiving an accepted frequency 40 72Hz 43 Zero Cross Error The board did not receive...

Страница 58: ...AX HP 25 30 40 60 75 1 14 1 0 Per CU AL 1 14 2 0 CU AL 40 50 75 100 100 1 4 4 0 Per CU 1 4 350MCM CU AL 75 75 150 200 200 1 3 350MCM Per CU AL 1 4 350MCM CU AL 100 125 200 250 300 2 3 0 250MCM Per CU...

Страница 59: ...ay Burlington ON L7L 5Z1 Email chcfirepump eaton com Web www chfire com 2019 Eaton All Rights Reserved Printed in USA Publication No MN124016EN August 2019 Eaton is a registered trademark All trademar...

Отзывы: