18
Programming
EPCT FirE sEriEs FirE PumP ConTrollEr
MN124016EN August 2019 www.eaton.com
Table 3
Programmable output alarms
Startup
Acceleration
Pressure Below
Pressure Above
Common Alarm
Engine Start Contacts
Power ON
Pump Running
Local Start
Emergency Start
Below Start Pressure
Start Above Pressure
Low Pressure Alarm
High Pressure Alarm
Remote Manual Start
Remote Auto Start
Deluge Valve Start
Hardware Fault
Transducer Failure
Motor Overload
Low Reservoir
High Reservoir
Low Room Temp
High Room Temp
Low Suction
Low Foam Level
Fail to Start
Fail to Stop
Load Shed
Input 1
Input 2
Input 3
Input 4
Input 5
Input 6
Input 7
Input 8
Input 9
Input 10
Engine Test Run
Engine Test Fail
Motor Test Run
Motor Test Fail
ATS Transfer Failure
Source 2 Disconnected
S1 Available
Programmable output alarms
S2 Available
S1 Phase Failure
S2 Phase Failure
S1 Under Voltage
S2 Under Voltage
S1 Over Voltage
S2 Over Voltage
S1 Under Frequency
S2 Under Frequency
S1 Over Frequency
S2 Over Frequency
S1 Phase Reversal
S1 Phase Reversal
ATS Connected to S1
ATS Connected to S2
Disabled
5.10
History stats diag. Tab (history statistics
diagnostics)
5.10.1 Message history
The EPCT controller will record a number of items in its
memory to assist with troubleshooting of the system
and/or the fire pump controller. The controller will record
up to 65,000 alarm/status messages in its memory that
can be viewed on the main display or saved to a USB
storage device. Up to ten (10) events can be viewed on
the Message History screen. Event dates and times are
also displayed.
Pressing the Up or Down arrow buttons will advance
through messages saved in the memory one at a time.
Pressing the Page up or Page down arrow buttons will
advance through messages saved in the memory 10
messages at a time.
Pressing and holding the Up, Down, Page Up or Page
Down arrows, allows the messages to scroll continuously
through all messages saved in the memory; scrolling speed
increases the longer the button is held for .
Message History data is stored in a comma separated value
(CSV) format.
5.10.2 Controller statistics
The EPCT controller will record several statistical values that
can be viewed on the main display or saved onto a USB
storage device. The statistics can be cleared by pressing the
“Clear All Controller Statistics” button. Please refer to Table
4 for the statistical values that are recorded.