Appendix O: Alarm/Status messages 

EPCT FirE sEriEs FirE PumP ConTrollEr

   MN124016EN   August 2019   www.eaton.com

Appendix O: Alarm/Status messages 

message

Description 

ATS CONNECTED TO S2 

The automatic transfer switch is in the emergency position 

ATS CONNECTED TO S1

The automatic transfer switch is in the normal position

DELUGE VALVE START 

The controller started the motor after it received a deluge valve start signal

EMERGENCY START 

The emergency start handle was pressed in and the motor started

FAIL TO START 

There was a call to start the motor, however, the amperage draw did not reach 20% of the programmed motor full load amps

FAIL TO STOP 

If the amperage draw has not dropped below 20% of the programmed motor full load amps two (2) seconds after a stop 

command, this alarm will be triggered

INTERLOCK 

The interlock signal has been received 

POWER ON

Notification will appear when the controller has power within the range of 200 – 600 VAC

PUMP RUNNING

The amperage draw on the motor has reached at least 20% of the programmed motor full load amps

LOCAL START

The start pushbutton on the enclosure flange was pressed initiating a start sequence

LOCAL STOP

The stop pushbutton on the enclosure flange was pressed initiating a stop sequence

BELOW START PRESSURE

The pump has started running because of a low-pressure condition

START ABOVE PRESSURE

The pump has started running because the pressure has exceeded the start above pressure set point 

LOW PRESSURE ALARM

The system pressure is lower than the programmed low-pressure alarm set point

HIGH PRESSURE ALARM

The system pressure is above the programmed high-pressure alarm set point

REMOTE MANUAL START

The pump has stated via a remote start signal

REMOTE MANUAL STOP

The pump has stated via a remote stop signal

REMOTE AUTO START

The remote auto start signal has been received 

HARDWARE FAULT

Controller detects a hardware fault in any of the three boards, ATS board, I/O board or logic board

TRANSDUCER FAILURE

The controller has detected that the transducer has failed

MOTOR OVERLOAD

The amperage draw has exceeded 125% of the programmed motor full load amps

LOW RESERVOIR

The controller has received a low reservoir signal

HIGH RESERVOIR

The controller has received a high reservoir signal 

LOW ROOM TEMP

The controller has received a low room temperature signal

HIGH ROOM TEMP

The controller has received a high room temperature signal

LOW SUCTION 

The controller has received a low suction signal

LOW FOAM LEVEL 

The controller has received a low foam signal

LOAD SHED

The load shed timer has started timing and the load shed output has closed

INPUT 1

A signal from input 1 was received 

INPUT 2 

A signal from input 2 was received 

INPUR 3

A signal from input 3 was received 

INPUT 4

A signal from input 4 was received 

INPUT 5

A signal from input 5 was received 

INPUT 6

A signal from input 6 was received 

INPUT 7

A signal from input 7 was received 

INPUT 8

A signal from input 8 was received 

INPUT 9

A signal from input 9 was received 

INPUT 10

A signal from input 10 was received 

LOCKED ROTOR TRIP

The controller has tripped on the built in locked rotor over current protection

AUTOMATIC SHUTDOWN

Automatic shutdown is enabled if the LED on the alarm is green 

RUN PERIOD TIMER

The minimum time a motor will run for after a start from an automatic means 

ACCELERATION TIMER

Delays energizing 2 CR relay for whatever It is connected for

SEQUENTIAL START TIMER 

A start sequence has been started, however, it is delayed due to the programmed sequential start timer

LOW SUCTION RESET TIMER

Once the input for low suction clears, controller will start the timer and once elapsed will allow the restart of the motor if 

the starting condition exists 

LOAW FOAM RESET TIMER

Once the input for low foam clears, controller will start the timer and once elapsed will allow the restart of the motor if 

the starting condition exists 

FAIL TO START TIMER

A timer has been started to detect 20% of the programmed motor full load amps after a call to start is initiated 

FAIL TO STOP TIMER

A timer has been started to detect less than 20% of the programmed motor full load amps after a call to stop is initiated

TD S1 TO S2

Timer for the delay between transfer of transfer switch from S1 to S2

Содержание EPCT Fire Series

Страница 1: ...Installation manual EPCT Fire series Fire Pump Controller...

Страница 2: ...PARTICULAR PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS D...

Страница 3: ...2 4 USB port 4 3 3 Power I O board 4 3 4 ATS board if equipped 4 3 5 Main isolating switch circuit interrupter 4 3 6 Contactor s 4 3 7 External pushbuttons 5 3 8 Transfer switch components 5 4 0 Opera...

Страница 4: ...4 5 4 Power phase failure 4CR 10 4 5 5 Phase reversal 5CR 10 4 5 6 Pump run 6CR 10 5 0 Programming 11 5 1 Introduction 11 5 2 Navigation 11 5 3 Startup tab 12 5 3 1 Quick setup 12 5 3 2 Setup phase r...

Страница 5: ...5 5 5 2 Service contact information 15 5 5 3 Factory contact information 15 5 6 Pressure settings tab 15 5 6 1 Start pressure 15 5 6 2 Stop pressure 15 5 6 3 Low pressure alarm 15 5 6 4 High pressure...

Страница 6: ...0 6 2 Main contacts 20 6 3 ATS electrical control circuit 20 6 4 Mechanical transfer mechanism 20 6 5 ATS control board touchscreen display 21 6 5 1 Inputs 21 6 5 2 Outputs 21 6 5 3 Touchscreen displa...

Страница 7: ...ture continued 34 Appendix F timer values tab menu structure 35 Appendix G a ATS settings tab menu structure 36 Appendix G b ATS settings tab menu structure continued 37 Appendix H a alarm setpoints t...

Страница 8: ...ulations must be strictly observed in the installation operation and maintenance of this device CAUTION Completely read and understand the material presented in this document before attempting install...

Страница 9: ...to the incoming AC power supply and motor wiring Install necessary conduit using proper methods and tools Recommend entry point is on the bottom of the enclosure Incoming AC line voltage is clearly ma...

Страница 10: ...sed for reduced in rush current controllers only The AT will be factory set but will automatically adjust depending on the starting method that the controller is programmed to If it is found that more...

Страница 11: ...Source 2 Disconnected Refer to the schematic diagram mounted on the inside of the controller door for all connection points specific to the controller 3 5 Main isolating switch circuit interrupter Th...

Страница 12: ...tart of the pump motor Stop The stop pushbutton will initiate the stopping sequence of the fire pump motor Releasing the stop button will put the controller back into the automatic mode If a starting...

Страница 13: ...r where when it expires the controller will exit the Welcome Screen to the Home tab and resume normal operation The three 3 buttons on this screen are CLOSE AND DISABLE WELCOME SCREEN CLOSE WELCOME SC...

Страница 14: ...7 Operation EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com 4 2 1 2 Home Tab without an ATS Fig 1 HOME tab idle Fig 2 HOME tab pump running...

Страница 15: ...Source 2 external disconnect handle and the motor The HOME tab will display the current system pressure reading along with the programmed Start and Stop setpoints At the bottom of the HOME tab is the...

Страница 16: ...is in the Connected state the EPCT controller will initiate an automatic start sequence If programmed to automatically shutoff the pump when the input is in a Disconnected state and the RPT has elapse...

Страница 17: ...ill delay all automatic starting means for the duration of the programmed timer 4 5 Output relays The primary control outputs of the EPCT controller are dry relay contacts These relays are comprised o...

Страница 18: ...ingle phase start Enabled Disabled Auto shutdown Enabled Disabled Motor HP 0 9999 HP Nominal voltage 200 7200V Phases Single Phase Three Phase Description Range System Frequency 50Hz 60Hz CT Ratio 50...

Страница 19: ...bled Dropout 100 999 Disabled Pickup Source 2 Under Frequency 0 100 Disabled Dropout 0 100 Disabled Pickup Description Range Source 2 Over Frequency 100 999 Disabled Dropout 100 999 Disabled Pickup In...

Страница 20: ...s message history startup and configuration files to a USB device 5 4 Panel setup tab Refer to Appendix C for the menu structure of the Panel Setup tab 5 4 1 Language Nine 9 languages are offered as s...

Страница 21: ...ion can then be used on other controllers that require the same configuration setup The configuration will not adjust functionality settings 5 4 21 Load configuration to USB A configuration file will...

Страница 22: ...oint can be selected that will be recorded in the controller s history and displayed in the notification area if enabled 5 6 4 High pressure alarm A high pressure alarm point can be selected that will...

Страница 23: ...to a known value typically 0 psi This value is then entered into the controller The system pressure is then increased to a higher known value which is also entered into the controller Calibrate Using...

Страница 24: ...ller be equipped with an ATS the screen will provide the ability to have different setpoints for either Source 5 8 7 Frequency alarm settings This menu item allows the user to adjust frequency dropout...

Страница 25: ...ory stats diag Tab history statistics diagnostics 5 10 1 Message history The EPCT controller will record a number of items in its memory to assist with troubleshooting of the system and or the fire pu...

Страница 26: ...cer information The input status page will display the state of each input contact Pressing the input buttons the controller will override the state of that input for one minute If the button is depre...

Страница 27: ...he ATS control board Energizing this relay will result in closure of the contact between terminals 72 73 on the ATS board Closing this contact will energize the ATS motor and the motor brake The motor...

Страница 28: ...graphic on the display will show the Source 1 ATS contact closed and the Source 2 ATS contact open When in the Source 2 position the single line graphic on the display will show the Source 2 ATS conta...

Страница 29: ...y start and run the generator at specific intervals The Weekly Timer is set by adjusting the day hour and minute of the desired weekly run time the length of time that this test shall be performed a t...

Страница 30: ...ted at 8A 250VAC and 30 VDC and it includes two 2 pull apart six 6 pin terminal blocks 7 2 1 Programming i Refer to Appendix L 7 3 MODBUS Board It includes an eight 8 pole dip switch bank designed to...

Страница 31: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix A menu structure Note N Pressing the Back or Cancel button when available will return the screen to the...

Страница 32: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix B startup tab menu structure Note N Pressing the Back or Cancel button when available will return the s...

Страница 33: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix C a panel setup tab menu structure Note N Pressing the Back or Cancel button when available will return...

Страница 34: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix C b panel setup tab menu structure continued Note N Pressing the Back or Cancel button when available w...

Страница 35: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix C c panel setup tab menu structure continued Note N Pressing the Back or Cancel button when available w...

Страница 36: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix C d panel setup tab menu structure continued Note N Pressing the Back or Cancel button when available w...

Страница 37: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix C e panel setup tab menu structure continued Note N Pressing the Back or Cancel button when available w...

Страница 38: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix D help tab menu structure Note N Pressing the Back or Cancel button when available will return the scre...

Страница 39: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix E a pressure settings tab menu structure Note N Pressing the Back or Cancel button when available will...

Страница 40: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix E b pressure settings tab menu structure continued Note N Pressing the Back or Cancel button when avail...

Страница 41: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix E c pressure settings tab menu structure continued Note N Pressing the Back or Cancel button when avail...

Страница 42: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix F timer values tab menu structure Note N Pressing the Back or Cancel button when available will return...

Страница 43: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix G a ATS settings tab menu structure Note N Pressing the Back or Cancel button when available will retur...

Страница 44: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix G b ATS settings tab menu structure continued Note N Pressing the Back or Cancel button when available...

Страница 45: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix H a alarm setpoints tab menu structure Note N Pressing the Back or Cancel button when available will re...

Страница 46: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix H b alarm setpoints tab menu structure continued Note N Pressing the Back or Cancel button when availab...

Страница 47: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix I a inputs outputs tab menu structure Note N Pressing the Back or Cancel button when available will ret...

Страница 48: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix I b inputs outputs tab menu structure continued Note N Pressing the Back or Cancel button when availabl...

Страница 49: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix J History stats diag Tab menu structure Note N Pressing the Back or Cancel button when available will r...

Страница 50: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix K Relay option board tab menu structure Note N Pressing the Back or Cancel button when available will r...

Страница 51: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix L a 4 20 mA device tab menu structure Note N Pressing the Back or Cancel button when available will ret...

Страница 52: ...re continued EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix L b 4 20 mA device tab menu structure continued Note N Pressing the Back or Cancel button when availabl...

Страница 53: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix M MODBUS board tab menu structure Note N Pressing the Back or Cancel button when available will return...

Страница 54: ...nu structure EPCT Fire series Fire Pump Controller MN124016EN August 2019 www eaton com Appendix N Supervisory alarm option board tab menu structure Note N Pressing the Back or Cancel button when avai...

Страница 55: ...has failed MOTOR OVERLOAD The amperage draw has exceeded 125 of the programmed motor full load amps LOW RESERVOIR The controller has received a low reservoir signal HIGH RESERVOIR The controller has...

Страница 56: ...tage measured by the controller has exceeded the programmed over voltage alarm set point for the normal source S2 OVER VOLTAGE The voltage measured by the controller has exceeded the programmed over v...

Страница 57: ...rror There is no communication received from the display board 42 Frequency Error The frequency measurement is not receiving an accepted frequency 40 72Hz 43 Zero Cross Error The board did not receive...

Страница 58: ...AX HP 25 30 40 60 75 1 14 1 0 Per CU AL 1 14 2 0 CU AL 40 50 75 100 100 1 4 4 0 Per CU 1 4 350MCM CU AL 75 75 150 200 200 1 3 350MCM Per CU AL 1 4 350MCM CU AL 100 125 200 250 300 2 3 0 250MCM Per CU...

Страница 59: ...ay Burlington ON L7L 5Z1 Email chcfirepump eaton com Web www chfire com 2019 Eaton All Rights Reserved Printed in USA Publication No MN124016EN August 2019 Eaton is a registered trademark All trademar...

Отзывы: