Appendix Q: Power wire cable reference
EPCT FirE sEriEs FirE PumP ConTrollEr
MN124016EN August 2019 www.eaton.com
Appendix Q: Power wire cable reference
line terminals on main isolation switch (incoming cables)
line voltage
Qty. & Cable sizes
service entrance GnD. luG
QTY. & Cable sizes
200-208V
220-240V
*380-415V 440-480V
550-600V
mAX HP
25
30
40
60
75
(1)#14-1/0 Per Ø (CU/AL)
(1)#14-2/0 (CU/AL)
40
50
75
100
100
(1)#4-4/0 Per Ø (CU)
(1)#4-350MCM (CU/AL)
75
75
150
200
200
(1)#3-350MCM Per Ø (CU/AL)
(1)#4-350MCM (CU/AL)
100
125
200
250
300
(2)3/0-250MCM Per Ø (CU/AL)
(2)1/0-750MCM (CU/AL)
150
200
300
400
400
(2)250-350MCM Per Ø (CU/AL)
(2)1/0-750MCM (CU/AL)
200
-
350
450
550
(2)#1-500MCM PER Ø (CU/AL)
(2)1/0-750MCM (CU/AL)
250
300
500
600
700
(3)3/0-400MCM PER Ø (CU/AL)
(2)1/0-750MCM (CU/AL)
*Coils available: 380V-50Hz, 380V-60Hz, 415V-50Hz, 415V-60Hz
*For proper cable size, refer to the National Electrical Code NFPA-70