Channel Utilization, Background noise, Tx Retry % and Tx Failed % (average of the last 60 minutes)
30420 – 30423
Channel Utilization, Background noise, Tx Retry % and Tx Failed % (average of the last 60 hours)
30424 – 30493
Spare - General purpose word storage used for: Staging area for data concentrator; Fieldbus mappings storage;
30494 – 30500
Internal information registers: serial number, firmware version and patch level
30494
First four digits of serial number (Encodes Manufacture Month & Year
30495
Next three digits of serial number (Encodes Manufactured Firmware version)
30496
Remaining four digits of the serial number
30497
First part of Current Firmware version
30498
Second part of Current Firmware version
30499
Third part of Current firmware version
30500
Patch Level of current firmware version
30501 – 32000
General purpose word storage used for: Staging area for data concentrator; Fieldbus mappings storage;
32001 - 32255
RSSI List: When configured as an Base, Repeater, or Manual AP. The RSSI of each connected downstream is added to an I/O register according to
the last byte of that device’s IP Address. For example, a downstream device with IP Address 192.168.0.199 will have its RSSI stored in I/O register
32000 + 199 = 32199. If no device is connected with that IP address, the corresponding register has the value Zero.
32256 – 36000
General purpose word storage used for: Staging area for data concentrator; Fieldbus mappings storage;
36001 - 36008
Local pulsed inputs 1–4, big endian format Most significant word at lower/odd address
36009 – 36040
Spare space for 32-bit register values
36041 – 38000
Not Available
38001 - 38032
Local analog inputs as floating point values. ModScan format (sign + ex most significant 7 bits of significant at even/higher addressed
location; lower 16 bits of significant at lower/odd addressed location)
(example: Analog input 1 at 12.3 mA gives registers 38001=CCCD, 38002=4144)
38033 – 38040
Spare space for floating point values
38041 – 40000
Not Available
Output registers (holding registers)
Address range
Description
40001 – 40002
Local AO1 and AO2:analog outputs
40003 – 40020
Spare
40021 – 40400
Space for locally attached 115s expansion I/O modules. Twenty registers per module address, maximum number of modules is 19.
40401 – 46000
General purpose word storage area used for: Staging area for data concentrator; Fieldbus mappings storage
46001 – 46008
Local pulsed outputs 1–4. Big endian format. Most significant word at lower/odd address
46009 – 46040
Spare 32-bit registers
46041 – 48000
Not Available
48001 – 48004
Local analog outputs as floating point values. ModScan format (sign + ex most significant 7 bits of significant at even/higher addressed
location) Lower 16 bits of significant at lower/odd addressed location
(example: Analog output 1 at 12.3 mA gives registers 48001=CCCD, 48002=4144)
48005 – 48040
Spare space for floating point values
48041 Onwards
Not available
Address range
Description
30409 – 30410
Radio Receive Frequency (Same as Transmit Frequency)
30411
Module uptime: The time (in hours) that this module has been up and running
30412
Channel Utilization % (average of last 60 seconds)
30413
Background Noise (average of last 60 seconds)
30414
Tx retry % (average of last 60 seconds): The percentage of total transmissions that required at least one retry
30415
Tx failed % (average of last 60 seconds): The percentage of total transmissions that failed to get an acknowledgement after all retries exhausted.