29
User Manual
MN032006EN
Effective December 2017
415U Condor-long-range
wireless I/O and gateway
EATON
www.eaton.com
Analog outputs
To configure analog outputs, click
Analog Outputs
under
IO
in
the project tree. Select an analog output from the list on the right,
and click
Edit
(see
Figure 45
). This displays the IO Edit screen
(
Figure 46
) where you can change settings.
Figure 45. Analog outputs
Figure 46. IO edit (analog outputs)
Name
Enter a name for the analog output or leave
the default name. The name can be up to 30
characters, including spaces.
Fail-safe Time (sec)
Sets the time the output needs to count down
before activating the fail-safe state. Receiving
an update or a COS message will reset the
fail-safe timer to its starting value. When the
fail-safe time elapses, the output is set to the
fail-safe value (mA).
It is recommend the fail-safe time be
configured for a little more than twice the
update time of the input that is mapped to
it. That way the output will reset if it fails to
receive two update messages. Entering a zero
as the fail-safe time will disable fail-safe.
Fail-safe Value (mA)
Sets the value that the output will be set to
when the fail-safe time elapses.
You can configure the following parameters for 415U-2
analog outputs.