background image

- 1 - 

The ELCM-TC04ANNN temperature measurement module supports 4 
channels of thermocouple temperature sensors (J-type, K-type, R-type, 
S-type, T-type, E-type, N-type, 

±

80mV) and converts these signals into 

16-bit digital data. You can select temperatures in Celsius (resolution: 0.1°C) 
or Fahrenheit (resolution: 0.1°F). The data in the module may be accesses 
using the FROM/TO instructions, or you may read the average value of 
channels directly by using the MOV instruction (Please refer to allocation of 
special registers D9900 ~ D9999).   

 This instruction sheet provides only information on the electrical 

specification, general functions, installation and wiring. It should be read 
and understood before attempting to install or use the module. 

 Further information can be found in the 

“ELC Programming Manual” and 

“ELC Special Modules Operation Manual”. 

 

This module is a part of an OPEN TYPE control system. The ELCM 

should be kept in an enclosure away from airborne dust, humidity, 
electric shock risk and vibration. Your application may require that the 
enclosure be locked to prevent non-maintenance staff from operating the 
controller (e.g. key or specific tools that are required for opening the 
enclosure) in cases where danger and damage to equipment or 
personnel may occur. Do NOT touch the terminals while power is 
applied. 

 

DO NOT connect AC input power to any of the input terminals; otherwise 

serious damage may occur. Check all the wiring before switching on the 
power. 

 

Ensure that the ground terminal 

  is properly grounded in order to 

prevent electromagnetic interference 

 This manual is subject to change without notice. 

 Product Profile & Dimension 

Removable I/O terminal

Panel mounting hole

DIN rail 
mounting slot 
(35mm)

Power / A->D / Error indicators

I/O module 
connection port

I/O terminal No.

Module Name

I/O module clip

I/O module connection port

ELCM-T C04ANNN

4A I-T C

 

Содержание ELCM TC Series

Страница 1: ...Eaton Logic Controller ELCM TC Temperature Modules INSTRUCTION SHEET Applicable Temperature modules ELCM TC04ANNN IL05004006E 002 1300620 02 2010 12 10 5011699301 MTN1...

Страница 2: ...Manual This module is a part of an OPEN TYPE control system The ELCM should be kept in an enclosure away from airborne dust humidity electric shock risk and vibration Your application may require that...

Страница 3: ...hielded cables to minimize the effects of noise Temperature inputs should be separated from power cable or other wiring that may cause interference Note 2 Connect the terminal on both power supply and...

Страница 4: ...Applicable sensor type J type K type R type S type T type E type N type thermocouple 80mV voltage input Range of input J type 100 C 1 150 C K type 100 C 1 350 C R type 0 C 1 750 C S type 0 C 1 750 C T...

Страница 5: ...e 150 C 980 C Mode 6 H 0006 N type 150 C 1 280 C Mode 7 H 0007 80mV 80mV Mode 1 H FFFF Close 3 O R W CH2 Input mode setting 4 O R W CH3 Input mode setting 5 O R W CH4 Input mode setting 7 O R W Temper...

Страница 6: ...ble Disable limit detection Enable Disable the upper and lower bound detection function Default H 0000 101 X R W Upper and lower bound status Display the upper and lower bound value Default H 0000 102...

Страница 7: ...limit of I value Default K0 127 147 167 187 X R I value Current accumulated offset value 128 148 168 188 O R W Heating cooling 0 Heater 1 Cooler Default K0 129 149 169 189 O R W Upper limit of output...

Страница 8: ...set to K1 the values displayed in D9900 D9999 are current values You can use 1 ELCM_AIO Configuration Function of ELCSoft or 2 FROM TO instructions CR 8 CR 11 to set the average times as K1 Adjust TC...

Страница 9: ...Measured temperature input 12 800 23 360 1 500 2 380 1 280 150 0 C C 2 336 F 238 F Digital output Measured input impedance Mode 0 of CR 2 CR 5 100 C 1150 C 1000 11500 148 F 2102 F 1480 21020 Mode 1 o...

Страница 10: ...9 Mode 7 Voltage input 8 000 80mV 8 000 80mV 0 Digital output Mode 7 of CR 2 CR 5 80mV 80mV 8000 8000 Offset CR 34 CR 37 Deviation digital value corresponds to 0mv...