background image

- 6 - 

Description 

bit4 

K16 (H’10) 

CH2 Conversion 
error 

bit12   

K4096(H’1000) 

Set value changing 
prohibited 

bit5 

K32 (H’20) 

CH3 Conversion 
error 

bit13   K81

92(H’2000) 

Communication 
breakdown on next 
module 

 Note: Each error status is determined by the corresponding bit (b0 ~ b13) and there may 

be more than 2 errors occurring at the same time. 0 = normal; 1 = error

 

 PID Control Registers 

CR# 

Save 

Register content 

Description 

CH1  CH2  CH3  CH4 

#120  #140  #160  #180  O  R/W 

Set temperature 
value 

Please set the temperature value 
according to proper range of 
each sensor type. Default = K0 

#121  #141  #161  #181  O  R/W  Sampling time (s)   Range: K1 ~ K30. Default = K2 

#122  #142  #162  #182  O  R/W  K

P

 

Proportional control constant. 
Default = K121 

#123  #143  #163  #183  O  R/W  K

I

 

Integral constant. Default = 
K2,098 

#124  #144  #164  #184  O  R/W  K

D

 

Derivative constant. Default = 
K-29 

#125  #145  #165  #185  O  R/W 

Upper limit of I 
value 

Upper limit of I value. Default = 
K0 

#126  #146  #166  #186  O  R/W 

Lower limit of I 
value 

Lower limit of I value. Default = 
K0 

#127  #147  #167  #187  X 

I value   

Current accumulated offset value 

#128  #148  #168  #188  O  R/W  Heating/cooling 

0: Heater, 1: Cooler. Default = K0 

#129  #149  #169  #189  O  R/W 

Upper limit of 
output 

Upper limit of output. Default = 
K32,000 

#130  #150  #170  #190  O  R/W 

Lower limit of 
output   

Lower limit of output. Default = 
K0 

#131  #151  #171  #191  X 

Output 
percentage   

Output percentage (Unit: 0.1%) 

#132  #152  #172  #192  X 

Output width   

Width of control output. Unit: ms 

#133  #153  #173  #193  X 

Output cycle 

Cycle of control output. Unit: ms 

#134  #154  #174  #194  X 

Output volume 

Output volume 

#135  #155  #175  #195  X  R/W  PID_RUN/STOP    0: STOP, 1: RUN. Default = K0 

#136  #156  #176  #196  X  R/W  Auto-tuning   

0: Disabled, 1: Auto-tuning. 
Default = K0 

Symbols: O: When CR#41 is set to H’5678, the set value of CR will be saved.   

X: set value will not be saved.   
R: able to read data by using FROM instruction.   
W: able to write data by using TO instruction. 

 

Explanation on Special Registers D9900~D9999 

When ELCM-PH/ELCM-PA controllers use expansion I/O modules, 
registers D9900~D9999 will be reserved for storing values from these 
modules. You can apply the MOV instruction to access values in 
D9900~D9999. 

Содержание ELCM TC Series

Страница 1: ...Eaton Logic Controller ELCM TC Temperature Modules INSTRUCTION SHEET Applicable Temperature modules ELCM TC04ANNN IL05004006E 002 1300620 02 2010 12 10 5011699301 MTN1...

Страница 2: ...Manual This module is a part of an OPEN TYPE control system The ELCM should be kept in an enclosure away from airborne dust humidity electric shock risk and vibration Your application may require that...

Страница 3: ...hielded cables to minimize the effects of noise Temperature inputs should be separated from power cable or other wiring that may cause interference Note 2 Connect the terminal on both power supply and...

Страница 4: ...Applicable sensor type J type K type R type S type T type E type N type thermocouple 80mV voltage input Range of input J type 100 C 1 150 C K type 100 C 1 350 C R type 0 C 1 750 C S type 0 C 1 750 C T...

Страница 5: ...e 150 C 980 C Mode 6 H 0006 N type 150 C 1 280 C Mode 7 H 0007 80mV 80mV Mode 1 H FFFF Close 3 O R W CH2 Input mode setting 4 O R W CH3 Input mode setting 5 O R W CH4 Input mode setting 7 O R W Temper...

Страница 6: ...ble Disable limit detection Enable Disable the upper and lower bound detection function Default H 0000 101 X R W Upper and lower bound status Display the upper and lower bound value Default H 0000 102...

Страница 7: ...limit of I value Default K0 127 147 167 187 X R I value Current accumulated offset value 128 148 168 188 O R W Heating cooling 0 Heater 1 Cooler Default K0 129 149 169 189 O R W Upper limit of output...

Страница 8: ...set to K1 the values displayed in D9900 D9999 are current values You can use 1 ELCM_AIO Configuration Function of ELCSoft or 2 FROM TO instructions CR 8 CR 11 to set the average times as K1 Adjust TC...

Страница 9: ...Measured temperature input 12 800 23 360 1 500 2 380 1 280 150 0 C C 2 336 F 238 F Digital output Measured input impedance Mode 0 of CR 2 CR 5 100 C 1150 C 1000 11500 148 F 2102 F 1480 21020 Mode 1 o...

Страница 10: ...9 Mode 7 Voltage input 8 000 80mV 8 000 80mV 0 Digital output Mode 7 of CR 2 CR 5 80mV 80mV 8000 8000 Offset CR 34 CR 37 Deviation digital value corresponds to 0mv...

Отзывы: