ELC Distributed I/O Adapters
MN05002003E
For More Information visit:
www.eaton.com
143
z
Local
Logic:
Timer
Application
Local Logic Timer function in ECISoft. After RY0 is On for 1 second, it will turn
Off for 500 ms. This will repeat every cycle.
Steps
(1) Set up the timer: Timer 0 1s, Timer 1 500ms.
(2) Set up IF-THEN: When the timing reaches the target, RY0 will be On or Off.
1. Open the setup page for the ELC-CAENET module and click the “Smart PLC” tab, then
the “Timer” tab.
2. Check the “Enable” box for Timer 0 and Timer 1 and set Timer 0 to “1s” and Timer 1 to
“500ms”. Click “Apply” to write the settings into the ELC-CAENET module.
z
Local Logic: Counter
Application
Local Logic counters function in ECISoft. Once RX#1 toggles 5 times, output
RY0 will energize
Steps
(1) Set up counter C0: RX#1 toggles 5 times and reaches the target.
(2) Set up IF-THEN: When the counting reaches the target, RY0 will output.
1. Open the setup page for the ELC-CAENET module and click the “Smart PLC” tab, then
the “Counter” tab.
2. Check to “Enable” Counter 0, select “Count Up”, set the Up Bound limit to “5” and Count
Source RX NO. to RX”1”. Click "Apply” to write these settings into the ELC-CAENET
module.