ELC Distributed I/O Adapters
MN05002003E
For More Information visit:
www.eaton.com
105
2. Bit
device
For setting up the addresses for the bit type serial slave device and reading the
contents from the designated slave.
Station
address:
Enter the address of the slave to be monitored. (Max. 16 slaves)
MODBUS
(Hex):
Enter the 4-digit hex Modbus address of the slave data to be monitored.
MODBUS
(Dec):
Enter the 6-digit decimal Modbus address of the slave data to be monitored.
Account:
Enter the number of consecutive bits to be monitored (Max. 100).
3. Word
device
For setting up the addresses for the word type serial slave device and reading the
contents from the designated slave.
Station
address:
Enter the address of slave to be monitored. (Max. 16 slaves)
MODBUS
(Hex):
Enter the 4-digit hex Modbus address of the slave data to be monitored.
MODBUS
(Dec):
Enter the 6-digit decimal Modbus address of the slave data to be monitored.
Account:
Enter the number of consecutive words to be monitored (Max. 100).
f
Once the information of slave monitoring is set, click "Apply" to save the
setting and start the monitoring. Incomplete device information will be deleted.