EC500 Controller Handbook
Copyright © 2019 Eaton Corporation. All Rights Reserved.
Issue A March 2019
Page 77 of 107
Parameter
Description
Default Value
Where to find:
Mapping>Battery>
Battery
n
LVD Channel
Web:
Home>System
Config>Hardware
Mapping>Battery>
Battery
n
LVD Channel
Battery
Temperature
For battery temperature
measurement, required only if
Temperature compensation is
enabled. Only one temperature
measurement is used for all
batteries.
DCIF1_TEMP_CH1
Configurator:
Main Menu>System
Config>Hardware
Mapping>Battery> Batt
Temperature Channel
Web:
Home>System
Config>Hardware
Mapping>Battery>Batt
Temperature Channel
Battery
n
Mid-
Point
For battery
n
mid-point sense,
required only if respective battery
mid-point monitoring is required.
None
Battery
n
Quarter Point
x
For battery
n
quarter point sense,
required only if respective battery
quarter point monitoring is
required. Requires three channels
one for each quarter node.
None
LOAD CHANNEL MAPPINGS
Voltage channels, current channels and LVD drives shall be defined for each battery string, if configured.
Parameter
Description
Default Value
Where to find:
Load Voltage
Voltage channel 1 of DCIF 1 is used as
fixed Bus voltage channel. Channel 1 of
all other DCIF boards shall be wired to
Bus Voltage and cannot be mapped.
DCIF1_VOLT_CH1
Configurator:
Main Menu>System
Config>Load>Load
n
Voltage Channel
Web:
Home>System
Config>Load>Load
n
Voltage Channel
Load MCB Trip
Sense
Single Load MCB trip using diode string
is sensed on PFC input. Any available
PFC input can be mapped.
None
Load
n
Current
For load
n
current measurement,
required only if respective load current
path is enabled.
DCIF1_CURR_CH1
Configurator:
Main Menu>System
Config>Load>Load n
Current Channel
Web: