The system should be configured for the shunt ratings used in the system. Shunt rating and millivolts full scale
can be configured for each of the selected battery & load current channels. The shunt rating is passed on to
the DCIF card by EC500 and the DCIF scales the measurement as per the settings. These settings are not
intended for channel calibration. All DCIF channels come calibrated from factory. Refer to DCIF specifications
for accuracy.
Parameter
Description
Default Value
Where to find:
Battery
n
Shunt
current rating
Current rating of respective shunt in
Amp. To be defined for individual
shunt. Setting range is from 50
–
5000A. The number battery shunts is
equal to
“
Number of Battery LVD
” set
above.
150A, (50
–
5000)
Configurator:
Main Menu>System
Config>DC Config>
Current Sensing
Web:
Home>System Config >
DC Config>Current
Sensing
Battery
n
Shunt
millivolt
Shunt millivolt at rated current rating,
set above. Number of Load shunts is
equal to “
Number of Load Paths
” set
above.
50mV, (30
–
50)
CABINET CONFIGURATION
Items related to cabinet configuration like Temperature sensor, Door sensor and cabinet Fans etc. are
configured as part of System Configuration.
The following settings are available.
Parameter
Description
Default Value
Where to find:
Cabinet Type
For enabling fan control, the system
can be defined as
Outdoor
.
Indoor
Configurator:
Main Menu>System
Config>Cabinet Config
Web:
Home>System Config
>Cabinet Config
Smoke Sensor
Define if Smoke Sensor is installed
or not. Consequent actions in case
of Fire sense are enabled if Smoke
Sensor is enabled.
Not Installed
Door Sensor
Define if Door Sensor is installed or
not. Consequent actions in case of
Door Open, like Image clicking (if
Camera is installed) are enabled if
Door Sensor is installed.
Not Installed
Temperature Sensor
n
Configure if temperature sensors
are
Installed
or
Not Installed
. Two
temperature sensors can be
installed per DCIF.
Sensor 1:
Installed
Sensor 2: Not
Installed
Main Menu>System
Config>Cabinet
Config>Temp Sensing
Number of fans
Configure if fans are
Installed
or
Not Installed.
Min: 0 Max: 4
Web: