background image

plug-in unit as all the other Digitrip models. There are two 

style offerings –Phase Protection with Ground Fault Trip 

(Cat. P106LSIG) and Phase Protection with Ground Fault 

Alarm (Cat. P107LSIA).

The front panel of the unit has four cause of trip LEDs 

and a telephone type receptacle for programming set-

tings, testing and displaying phase currents via a sepa-

rate hand-held unit called the OPTIMizer. (The 

OPTIMizer is used primarily for initial setup of an indi-

vidual breaker.) There are up to ten trip functions that can 

be programmed which includes both a 

I

²

t and a 

I

 

curve for the Long-Time Slope. There is also typically ten 

times the number of setpoints compared to a front adjust-

able trip unit for each function.

All transmittable data as well as programming of the trip 

curve settings can also be communicated over a twisted 

pair wiring network via breaker

'

s secondary terminals 

C11, C12 to either a host computer or a panel mounted 

Breaker Interface Module (BIM).

Harmonics information including total Harmonic Distor-

tion, the individual harmonic currents involved up to the 

27th harmonic and waveform capture for the three phase 

currents and the neutral is accessible via communica-

tions.

The Digitrip OPTIM 1050 will also provide Power and 

Energy Monitoring functions via communications. The 

breaker requires the PT Module (Fig. 5) to provide this 

functionality. Also included is a Power/Relay module to 

provide power for communication functions and relay out-

puts for alarming.

4.8 Reset Operation

Following overload, short circuit, or ground fault tripping 

events on Digitrip Types 610, 810, and 910, the Digitrip 

“Trip Reset

 pushbutton must be depressed before the 

circuit breaker handle can be reset (trip/reclose feature).

The Digitrip RMS 310, 510 and Digitrip OPTIM 750 and 

1050 in R-frame do not require a trip reset push-button 

operation to reset the breaker

'

s mechanism. However, a 

trip reset push-button operation is required to clear cause 

of trip LED.

5.0 PRINCIPLE OF OPERATION

5.1 General

The circuit breaker is tripped automatically under fault 

current conditions by the combined action of three com-

ponents:

1. 

The sensors which determine the current level.

2. 

The Digitrip RMS Trip Unit, which provides a trip-

ping signal to the Flux Shunt Trip when current and 

time delay settings are exceeded.

3. 

The flux shunt trip which actually trips the circuit 

breaker.

Schematically, this may be represented as illustrated in 

Fig. 6. This arrangement provides a very flexible system 

covering a wide range of tripping characteristics. Not only 

is the Digitrip RMS Trip Unit adjustable, but selection of 

rating plugs provides a wide range of continuous current 

ratings.

The automatic overload and short circuit tripping charac-

teristics for a specific circuit breaker are determined by 

the ratings of the installed current sensors, rating plugs 

and the selected functional protection settings. Specific 

settings instructions are provided in the applicable trip 

unit instruction leaflet referenced in Section 8.2 of this 

instruction book.

When the functional protection settings are exceeded, 

the Digitrip RMS Trip Unit supplies a trip signal to the flux 

shunt trip. Thus all tripping operations initiated by the pro-

tection functions of the Digitrip RMS Trip Unit are per-

formed by secondary control circuitry, with no mechanical 

or direct magnetic action between the primary current 

and the mechanical tripping parts of the breaker and with 

no external control power required.

5.2 Digitrip RMS Trip Assembly

The basic Digitrip RMS Trip Assembly, as illustrated in 

Figs. 1, 2 and 4, includes the following which could vary 

slightly depending upon the exact model of the Digitrip 

Trip Unit installed:

1. 

Digitrip RMS or Digitrip OPTIM Trip Unit

2. 

Rating Plug

3. 

Auxiliary Current Transformers 

-

 3 or 4 depending 

upon whether or not ground fault or neutral protec-

tion is included. These are installed on back-

mounted PC board.

4. 

Stab-in Terminal Block for Trip Unit

5. 

Power/Relay module (Digitrip RMS Trip Unit Mod-

els 610, 810, 910 and Models 750 and 1050.)

EATON CORPORATION www.eaton.com 

 

 

 

 

 

 

 

                     Page 

9

Effective Date October 2010   

 

 

 

 

                  Instruction Leaflet 29C713E

 

 

 

 

 

 

 

 

 

 

 

Effective October 2010

4

Содержание Digitrip RMS

Страница 1: ...for Ground Fault Trip Units 14 6 2 1 Code Requirements 14 6 2 2 Standards Requirements 14 6 2 3 General Test Instructions 15 7 0 Record Keeping 16 8 0 References 16 8 1 R Frame 16 8 2 Digitrip RMS Tri...

Страница 2: ...eaker shunt trip when pre set current levels and time delay settings are exceeded In addition to the basic protection function Digitrip RMS Trip Unit models 510 610 810 910 and Digitrip OPTIM 750 and...

Страница 3: ...family of plugs is illustrated in Fig 3 1 This plug design will not mechanically fit into the other Digitrip models On the model 310 units the continous current rating Ir equals the rating plug ampere...

Страница 4: ...t and the cir cuit breaker are suitable for the intended installation by comparing nameplate data with any existing equipment Fig 3 6 Removal of Trip Unit and system requirements If both trip unit and...

Страница 5: ...can now be reset and switched to the ON and OFF positions 3 3 Trip Unit Removal Use the following instructions to remove a Digitrip trip unit from a circuit breaker THE VOLTAGES IN ENERGIZED EQUIPMENT...

Страница 6: ...RMS 310 The Digitrip RMS 310 Trip Assembly consists of a Digitrip RMS 310 Trip Unit as described in I L 29C883 3 or 4 auxiliary current transformers and a stab in trip unit ter minal block as shown i...

Страница 7: ...ns 4 3 Digitrip RMS 610 The Digitrip RMS 610 Trip Assembly consists of a Digitrip RMS 610 Trip Unit as described in l L 29 886 3 or 4 aux iliary current transformers a stab in trip unit terminal block...

Страница 8: ...e allows for remote tripping via the flux shunt trip and closing of the circuit breaker 4 5 Digitrip RMS 910 The Digitrip RMS 910 Trip Assembly is similar to the Dig itrip RMS 810 It is a communicatin...

Страница 9: ...ATION 5 1 General The circuit breaker is tripped automatically under fault current conditions by the combined action of three com ponents 1 The sensors which determine the current level 2 The Digitrip...

Страница 10: ...Table 1 Digitrip RMS and Digitrip OPTIM Trip Unit Characteristics for R Frame EATON CORPORATION www eaton com Page 10 Effective Date October 2010 Instruction Leaflet 29C713E Effective October 2010...

Страница 11: ...is same document IMPROPER POLARITY CONNECTIONS ON THE FLUX SHUNT TRIP COIL WILL VOID OVERLOAD AND SHORT CIRCUIT PROTECTION WHICH COULD RESULT IN PERSONAL INJURY OBSERVE POLARITY MARKINGS ON THE SHUNT...

Страница 12: ...ions Available ground fault pick up set tings employing Residual Sensing means are given in Table 3 5 4 3 Source Ground Sensing Depending upon the installation requirements alternate ground fault sens...

Страница 13: ...l L 29 C714 Each circuit breaker shipped from the factory includes a copy of the pages from this document that are applicable to the equipment included in the breaker 5 8 Trip Unit Settings Protectio...

Страница 14: ...30 95 C requires that any ground fault protection system be per formance tested when first installed The test shall be conducted in accordance with approved instructions pro vided with the equipment A...

Страница 15: ...st current of 125 of the Digitrip RMS Ground Fault Trip Unit pick up setting through one phase of the circuit breaker as shown in Fig 7 1 This should cause the breaker to trip in less than 1 second an...

Страница 16: ...es 8 and 9 can be used for record keeping This record should be filled in giving the indi cated reference information and initial time current trip function settings If desirable a copy could be made...

Страница 17: ...Fig 8 Typical Performance Test Record Form EATON CORPORATION www eaton com Page 17 Effective Date October 2010 Instruction Leaflet 29C713E Effective October 2010...

Страница 18: ...3 Time Current Curves Application Data 29 167R RD RDC 310 I t Shape SC 5629 93 RD RDC 310 FIat Response SC 5630 93 RD RDC 310 Ground SC 5631 93 RD RDC 510 610 810 910 Instantaneous SC 5626 93 RD RDC 5...

Страница 19: ...Fig 11 Master Connection Diagram Ground Fault 3 Pole Breaker EATON CORPORATION www eaton com Page 19 Effective Date October 2010 Instruction Leaflet 29C713E Effective October 2010...

Страница 20: ...ter Connection Diagram Ground Fault External Connections 3 Phase 4W Residual 3 Pole Breaker EATON CORPORATION www eaton com Page 20 Effective Date October 2010 Instruction Leaflet 29C713E Effective Oc...

Страница 21: ...Diagram Remote Alarms for use with Digitrip RMS Types 310 GF only 610 810 910 and Digitrip OPTIM 750 and 1050 EATON CORPORATION www eaton com Page 21 Effective Date October 2010 Instruction Leaflet 29...

Страница 22: ...Neutral Current Sensor Torque 1 2 13 Sensor bolts to 35 40 ft lbs EATON CORPORATION www eaton com Page 22 Effective Date October 2010 Instruction Leaflet 29C713E Effective October 2010 Torque to 15 20...

Страница 23: ...5 View of Installed Digitrip RMS Trip Unit with Sealed Cover Fig 16 Jumper Connections EATON CORPORATION www eaton com Page 23 Effective Date October 2010 Instruction Leaflet 29C713E Effective October...

Страница 24: ...108 United States 877 ETN CARE 877 386 2273 Eaton com 2010 Eaton Corporation All Rights Reserved Printed in USA Publication No 6605C99H06 October 2010 PowerChain Management is a registered trademark o...

Отзывы: