background image

e.

With the screwdrivers in position, gently rock the 

trip unit from side to side until it works free from the 

circuit breaker.

3.4 Trip Unit Replacement

Make sure the trip unit to be installed is suitable for the 

intended installation by comparing the trip unit catalog 

number with the nameplate on the circuit breaker frame 

located to the right of the handle. Rejection pins are used 

in the circuit breaker frame to prevent the installation of 

an incorrect trip unit.

a.

Remove any existing trip unit by following the 

procedures in paragraphs 3.3.a through e.

Note: The replacement trip unit should be installed 

before the circuit breaker cover is re-installed.

b. 

Position the replacement trip unit above the white 

terminal block to the left of the circuit breaker han-

dle. Align the protruding circuit board with the mat-

ing slot in the white terminal block (see Fig. 3.7).

c. 

Carefully press the trip unit into place. A sharp click 

will be heard as the retaining springs click into posi-

tion.

d. 

Install rating plug (see paragraphs 3.2.b through e).

e. 

Reinstall the circuit brea

k

er c over.

  Torque cover 

4.0 DIGITRIP RMS MODEL CONSIDERATIONS

4.1 Digitrip RMS 310

The Digitrip RMS 310 Trip Assembly consists of a Digitrip 

RMS 310 Trip Unit as described in I.L. 29C883, 3 or 4 

auxiliary current transformers and a stab-in trip unit ter-

minal block as shown in Figs. 4 and 5.

The fourth auxiliary current transformer is supplied when 

the optional ground fault or neutral protection function is 

selected in the trip unit. Also, a side mounted 4-point ter-

minal block is provided to pre-wire the mode of ground 

fault sensing used, i.e., residual or source ground. These 

connections are shown in Fig. 16.

Fig. 3.7. Installation of Trip Unit

IN A DRAWOUT MOUNTED BREAKER TESTING OF A 

CIRCUIT BREAKER BY INI

TI

ATING A TRIP OPERATION 

WHILE IN THE CELL " CONNECTED"  POSITION BY 

THE EXTERNAL TEST KIT OR THE INTEGRAL TEST 

PROVISIONS IN THE DIGITRIP RMS TRIP UNIT IS 

NOT RECOMMENDED.

THE TRIPPING OPERATION OF THE CIRCUIT 

BREAKER WILL CAUSE DISRUPTION OF SERVICE 

AND POSSIBLY PERSONAL INJURY RESULTING 

FROM UNNECESSARY SWITCHING OF CON-

NECTED EQUIPMENT.

TESTING OF A CIRCUIT BREAKER SHOULD BE 

DONE ONLY IN THE " TEST" ,  " DISCONNECTED"  OR 

“ WITHDRAWN"  CELL POSITIONS.

WHERE A CIRCUIT BREAKER TRIP OPERATION IS 

DESIRED FOR A FIXED MOUNTED CIRCUIT 

BREAKER, TESTING SHOULD BE CONDUCTED 

ONLY WHEN THE EQUIPMENT IN WHICH THE 

BREAKER IS MOUNTED IS COMPLETELY DE-ENER-

GIZED

.

CAUTION

 

EATON CORPORATION www.eaton.com 

 

 

 

 

 

 

 

                     Page 6

screws to 24 in-lbs.

Содержание Digitrip RMS

Страница 1: ...for Ground Fault Trip Units 14 6 2 1 Code Requirements 14 6 2 2 Standards Requirements 14 6 2 3 General Test Instructions 15 7 0 Record Keeping 16 8 0 References 16 8 1 R Frame 16 8 2 Digitrip RMS Tri...

Страница 2: ...eaker shunt trip when pre set current levels and time delay settings are exceeded In addition to the basic protection function Digitrip RMS Trip Unit models 510 610 810 910 and Digitrip OPTIM 750 and...

Страница 3: ...family of plugs is illustrated in Fig 3 1 This plug design will not mechanically fit into the other Digitrip models On the model 310 units the continous current rating Ir equals the rating plug ampere...

Страница 4: ...t and the cir cuit breaker are suitable for the intended installation by comparing nameplate data with any existing equipment Fig 3 6 Removal of Trip Unit and system requirements If both trip unit and...

Страница 5: ...can now be reset and switched to the ON and OFF positions 3 3 Trip Unit Removal Use the following instructions to remove a Digitrip trip unit from a circuit breaker THE VOLTAGES IN ENERGIZED EQUIPMENT...

Страница 6: ...RMS 310 The Digitrip RMS 310 Trip Assembly consists of a Digitrip RMS 310 Trip Unit as described in I L 29C883 3 or 4 auxiliary current transformers and a stab in trip unit ter minal block as shown i...

Страница 7: ...ns 4 3 Digitrip RMS 610 The Digitrip RMS 610 Trip Assembly consists of a Digitrip RMS 610 Trip Unit as described in l L 29 886 3 or 4 aux iliary current transformers a stab in trip unit terminal block...

Страница 8: ...e allows for remote tripping via the flux shunt trip and closing of the circuit breaker 4 5 Digitrip RMS 910 The Digitrip RMS 910 Trip Assembly is similar to the Dig itrip RMS 810 It is a communicatin...

Страница 9: ...ATION 5 1 General The circuit breaker is tripped automatically under fault current conditions by the combined action of three com ponents 1 The sensors which determine the current level 2 The Digitrip...

Страница 10: ...Table 1 Digitrip RMS and Digitrip OPTIM Trip Unit Characteristics for R Frame EATON CORPORATION www eaton com Page 10 Effective Date October 2010 Instruction Leaflet 29C713E Effective October 2010...

Страница 11: ...is same document IMPROPER POLARITY CONNECTIONS ON THE FLUX SHUNT TRIP COIL WILL VOID OVERLOAD AND SHORT CIRCUIT PROTECTION WHICH COULD RESULT IN PERSONAL INJURY OBSERVE POLARITY MARKINGS ON THE SHUNT...

Страница 12: ...ions Available ground fault pick up set tings employing Residual Sensing means are given in Table 3 5 4 3 Source Ground Sensing Depending upon the installation requirements alternate ground fault sens...

Страница 13: ...l L 29 C714 Each circuit breaker shipped from the factory includes a copy of the pages from this document that are applicable to the equipment included in the breaker 5 8 Trip Unit Settings Protectio...

Страница 14: ...30 95 C requires that any ground fault protection system be per formance tested when first installed The test shall be conducted in accordance with approved instructions pro vided with the equipment A...

Страница 15: ...st current of 125 of the Digitrip RMS Ground Fault Trip Unit pick up setting through one phase of the circuit breaker as shown in Fig 7 1 This should cause the breaker to trip in less than 1 second an...

Страница 16: ...es 8 and 9 can be used for record keeping This record should be filled in giving the indi cated reference information and initial time current trip function settings If desirable a copy could be made...

Страница 17: ...Fig 8 Typical Performance Test Record Form EATON CORPORATION www eaton com Page 17 Effective Date October 2010 Instruction Leaflet 29C713E Effective October 2010...

Страница 18: ...3 Time Current Curves Application Data 29 167R RD RDC 310 I t Shape SC 5629 93 RD RDC 310 FIat Response SC 5630 93 RD RDC 310 Ground SC 5631 93 RD RDC 510 610 810 910 Instantaneous SC 5626 93 RD RDC 5...

Страница 19: ...Fig 11 Master Connection Diagram Ground Fault 3 Pole Breaker EATON CORPORATION www eaton com Page 19 Effective Date October 2010 Instruction Leaflet 29C713E Effective October 2010...

Страница 20: ...ter Connection Diagram Ground Fault External Connections 3 Phase 4W Residual 3 Pole Breaker EATON CORPORATION www eaton com Page 20 Effective Date October 2010 Instruction Leaflet 29C713E Effective Oc...

Страница 21: ...Diagram Remote Alarms for use with Digitrip RMS Types 310 GF only 610 810 910 and Digitrip OPTIM 750 and 1050 EATON CORPORATION www eaton com Page 21 Effective Date October 2010 Instruction Leaflet 29...

Страница 22: ...Neutral Current Sensor Torque 1 2 13 Sensor bolts to 35 40 ft lbs EATON CORPORATION www eaton com Page 22 Effective Date October 2010 Instruction Leaflet 29C713E Effective October 2010 Torque to 15 20...

Страница 23: ...5 View of Installed Digitrip RMS Trip Unit with Sealed Cover Fig 16 Jumper Connections EATON CORPORATION www eaton com Page 23 Effective Date October 2010 Instruction Leaflet 29C713E Effective October...

Страница 24: ...108 United States 877 ETN CARE 877 386 2273 Eaton com 2010 Eaton Corporation All Rights Reserved Printed in USA Publication No 6605C99H06 October 2010 PowerChain Management is a registered trademark o...

Отзывы: