background image

depicted on the face of the trip unit provide mode of trip 

indication for ground fault, overload and short circuit trip 

operations.

Digitrip RMS Models 510, 610, 810, and 910 that are not 

equipped with an adjustable instantaneous trip element 

(LS and LSG) are provided with a making current release 

which is referred to as a DIScriminator. The DIScrimina-

tor is switch selectable to disable this function. In addi-

tion, on all models, a high-level instantaneous override 

circuit is provided to ensure rapid circuit clearing under 

abnormal fault current conditions. The override is set for 

16,000A 

±

15%.

Digitrip RMS Trip Units are available in five basic models, 

as illustrated in Fig. 2a: 310, 510, 610, 810, and 910. 

Separate instruction leaflets referenced in Section 8.2 

cover the basic functions and features of each model.

Digitrip OPTIM Trip Units are available in two models as 

illustrated in Fig. 2b: 750 and 1050. A separate related 

series of 3 instruction leaflets, referenced in Section 8.0, 

cover the two trip unit models, the hand held OPTIMizer 

and the panel mounted BIM (Breaker Interface Module).

This instruction book is arranged to describe the unique 

features of each type as they relate to their application in 

R- Frame Circuit Brea

k

ers. Table 1 illust

r

ates the 

available functions and features of each of the trip unit 

models.

3.0 RATING PLUGS

3.0.1 Digitrip RMS Plugs 510, 610, 810, 910

Rating Plugs, as illustrated in Figures 3.2 thru 3.4, deter-

mine the maximum continuous current rating of the circuit 

breaker. All protection function settings on the face of the 

trip unit are expressed in per unit multiples of the plug 

ampere rating (

I

n

)

 

 

A fractional multiplier of the plug 

ampere rating is set by the long delay setting switch to 

further define the (l

r

 

continuous current rating for the 

long time and short time functions. See curve references 

in Section 8.3.

Available rating plugs are shown in Table 2b. Plugs must 

be selected to match the desired continuous current rat-

ing of the circuit breaker as well as the frame rating.

3.0.2 Digitrip RMS 310- Plugs

This family of plugs is illustrated in Fig. 3.1. This plug 

design will not mechanically fit into the other Digitrip 

models. On the model 310 units the continous current 

rating (I

r

)  equals the rating plug ampere rating (

l

 

). The 

Fig. 3.1 Typical Rating Plug for Digitrip RMS 310

plug scaled by the short delay pickup or instantaneous 

switch settings provides short circuit protection levels. 

See curve references in Section 8.3. Available rating 

plugs are shown in Table 2a. Plugs must be selected to 

match the desired continuous current rating of the circuit 

breaker as well as frame rating.

3.0.3 Digitrip RMS Plugs for OPTIM, 750 and 1050

The Digitrip OPTIM rating plugs are similar in construc-

tion to the plug family described in Section 3.0.1. The 

plugs are marked Digitrip RMS. The plug determines the 

maximum continuous current rating of the circuit breaker. 

The pickup settings are ultimally loaded via software into 

the trip unit in per unit but are displayed for user

'

s ease as 

an ampere value. The Long Delay Current Setting (Long 

Delay Pickup) loaded in amperes via an external device 

is actually a fractional multiplier of the plug ampere rating 

(I

n

) and in turn defines a (

l

 )

 

continuous current rating for 

the long time and short time functions. See curve refer-

ences in Section 8.3. Available rating plugs are shown in 

Table 2c. Plugs must be selected to match the desired 

continuous current rating of the circuit breaker as well as 

frame rating.

3.0.4 Rating Plugs Battery

For all models except Digitrip 310, rating plugs are 

equipped with a back-up battery to maintain the mode of 

trip operation following a circuit breaker tripping operation 

when external control power is not available. The battery 

is a long-life lithium type, that is replaceable from the front 

of the trip unit, when required, without removing the rat-

ing plug. See Figs. 3.2 thru 3.4. Replacement types and 

instructions are provided in the Digitrip RMS Trip Unit 

instruction leaflet referred to in Section 8.2 of this book.

Following a trip operation and with no supplementary 

control power available, the battery will maintain the 

mode of trip LED for approximately 60 hours.

Effective Date October 2010   

 

 

 

 

                  Instruction Leaflet 29C713E

 

 

 

 

 

 

 

 

 

 

 

Effective October 2010

EATON CORPORATION www.eaton.com 

 

 

 

 

 

 

 

                     Page

 3

n

 

r

Содержание Digitrip RMS

Страница 1: ...for Ground Fault Trip Units 14 6 2 1 Code Requirements 14 6 2 2 Standards Requirements 14 6 2 3 General Test Instructions 15 7 0 Record Keeping 16 8 0 References 16 8 1 R Frame 16 8 2 Digitrip RMS Tri...

Страница 2: ...eaker shunt trip when pre set current levels and time delay settings are exceeded In addition to the basic protection function Digitrip RMS Trip Unit models 510 610 810 910 and Digitrip OPTIM 750 and...

Страница 3: ...family of plugs is illustrated in Fig 3 1 This plug design will not mechanically fit into the other Digitrip models On the model 310 units the continous current rating Ir equals the rating plug ampere...

Страница 4: ...t and the cir cuit breaker are suitable for the intended installation by comparing nameplate data with any existing equipment Fig 3 6 Removal of Trip Unit and system requirements If both trip unit and...

Страница 5: ...can now be reset and switched to the ON and OFF positions 3 3 Trip Unit Removal Use the following instructions to remove a Digitrip trip unit from a circuit breaker THE VOLTAGES IN ENERGIZED EQUIPMENT...

Страница 6: ...RMS 310 The Digitrip RMS 310 Trip Assembly consists of a Digitrip RMS 310 Trip Unit as described in I L 29C883 3 or 4 auxiliary current transformers and a stab in trip unit ter minal block as shown i...

Страница 7: ...ns 4 3 Digitrip RMS 610 The Digitrip RMS 610 Trip Assembly consists of a Digitrip RMS 610 Trip Unit as described in l L 29 886 3 or 4 aux iliary current transformers a stab in trip unit terminal block...

Страница 8: ...e allows for remote tripping via the flux shunt trip and closing of the circuit breaker 4 5 Digitrip RMS 910 The Digitrip RMS 910 Trip Assembly is similar to the Dig itrip RMS 810 It is a communicatin...

Страница 9: ...ATION 5 1 General The circuit breaker is tripped automatically under fault current conditions by the combined action of three com ponents 1 The sensors which determine the current level 2 The Digitrip...

Страница 10: ...Table 1 Digitrip RMS and Digitrip OPTIM Trip Unit Characteristics for R Frame EATON CORPORATION www eaton com Page 10 Effective Date October 2010 Instruction Leaflet 29C713E Effective October 2010...

Страница 11: ...is same document IMPROPER POLARITY CONNECTIONS ON THE FLUX SHUNT TRIP COIL WILL VOID OVERLOAD AND SHORT CIRCUIT PROTECTION WHICH COULD RESULT IN PERSONAL INJURY OBSERVE POLARITY MARKINGS ON THE SHUNT...

Страница 12: ...ions Available ground fault pick up set tings employing Residual Sensing means are given in Table 3 5 4 3 Source Ground Sensing Depending upon the installation requirements alternate ground fault sens...

Страница 13: ...l L 29 C714 Each circuit breaker shipped from the factory includes a copy of the pages from this document that are applicable to the equipment included in the breaker 5 8 Trip Unit Settings Protectio...

Страница 14: ...30 95 C requires that any ground fault protection system be per formance tested when first installed The test shall be conducted in accordance with approved instructions pro vided with the equipment A...

Страница 15: ...st current of 125 of the Digitrip RMS Ground Fault Trip Unit pick up setting through one phase of the circuit breaker as shown in Fig 7 1 This should cause the breaker to trip in less than 1 second an...

Страница 16: ...es 8 and 9 can be used for record keeping This record should be filled in giving the indi cated reference information and initial time current trip function settings If desirable a copy could be made...

Страница 17: ...Fig 8 Typical Performance Test Record Form EATON CORPORATION www eaton com Page 17 Effective Date October 2010 Instruction Leaflet 29C713E Effective October 2010...

Страница 18: ...3 Time Current Curves Application Data 29 167R RD RDC 310 I t Shape SC 5629 93 RD RDC 310 FIat Response SC 5630 93 RD RDC 310 Ground SC 5631 93 RD RDC 510 610 810 910 Instantaneous SC 5626 93 RD RDC 5...

Страница 19: ...Fig 11 Master Connection Diagram Ground Fault 3 Pole Breaker EATON CORPORATION www eaton com Page 19 Effective Date October 2010 Instruction Leaflet 29C713E Effective October 2010...

Страница 20: ...ter Connection Diagram Ground Fault External Connections 3 Phase 4W Residual 3 Pole Breaker EATON CORPORATION www eaton com Page 20 Effective Date October 2010 Instruction Leaflet 29C713E Effective Oc...

Страница 21: ...Diagram Remote Alarms for use with Digitrip RMS Types 310 GF only 610 810 910 and Digitrip OPTIM 750 and 1050 EATON CORPORATION www eaton com Page 21 Effective Date October 2010 Instruction Leaflet 29...

Страница 22: ...Neutral Current Sensor Torque 1 2 13 Sensor bolts to 35 40 ft lbs EATON CORPORATION www eaton com Page 22 Effective Date October 2010 Instruction Leaflet 29C713E Effective October 2010 Torque to 15 20...

Страница 23: ...5 View of Installed Digitrip RMS Trip Unit with Sealed Cover Fig 16 Jumper Connections EATON CORPORATION www eaton com Page 23 Effective Date October 2010 Instruction Leaflet 29C713E Effective October...

Страница 24: ...108 United States 877 ETN CARE 877 386 2273 Eaton com 2010 Eaton Corporation All Rights Reserved Printed in USA Publication No 6605C99H06 October 2010 PowerChain Management is a registered trademark o...

Отзывы: