Fig. 2a

View of Five Basic Models of the Digitrip RMS Trip Unit

1.0 SUPPLEMENTARY INFORMATION

The instructions contained in this book supplement the 

instructions  for R- Frame Circuit Brea

k

ers c

o

v

ered

in l.L. 29C107 and Connection Dia

g

ram 290714.

2.0 DIGITRIP RMS AND DIGITRIP OPTIM TRIP UNITS

This instruction book specifically covers the application of 

Digitrip RMS and Digitrip OPTIM Trip Units installed in 

R- Frame Circuit Brea

k

ers as illust

r

ated in Fig. 1.

Digitrip RMS and Digitrip OPTIM Trip Units are ac 

devices that employ microprocessor-based technology 

that provides true rms current sensing means for proper 

correlation with thermal characteristics of conductors and 

equipment. The primary function of the Digitrip Trip Unit is 

circuit protection. This is achieved by analyzing the sec-

ondary current signals received from the circuit breaker 

current sensors and initiating trip signals to the circuit 

breaker shunt trip when pre-set current levels and time 

delay settings are exceeded.

In addition to the basic protection function, Digitrip RMS 

Trip Unit models 510, 610, 810, 910 and Digitrip OPTIM 

750 and 1050, provide mode of trip information and inte-

gral test provisions. 

The protection section of the Digitrip Trip Unit can be 

equipped with a maximum of five phase and two ground 

(time current) curve shaping adjustments. The exact

Fig. 2b

View of the Two Basic Models of the Digitrip 

OPTIM Trip Unit

selection of the available protection function adjustments 

is optional to satisfy the protection needs of any specific 

installation. The short delay and ground fault pick-up 

adjustments can be set for either flat or I

²

t response. A 

pictorial representation of the applicable time-current 

curve for the selected protection functions is provided on 

the face of the trip unit for user reference.

On the Digitrip Models 510, 610, 810, 910, 750 and 1050 

red LEDs that are imbedded in the Time-Current curves 

Effective Date October 2010   

 

 

 

 

                  Instruction Leaflet 29C713E

 

 

 

 

 

 

 

 

 

 

 

Effective October 2010

EATON CORPORATION www.eaton.com 

 

 

 

 

 

 

 

                     Page 2

Содержание Digitrip RMS

Страница 1: ...for Ground Fault Trip Units 14 6 2 1 Code Requirements 14 6 2 2 Standards Requirements 14 6 2 3 General Test Instructions 15 7 0 Record Keeping 16 8 0 References 16 8 1 R Frame 16 8 2 Digitrip RMS Tri...

Страница 2: ...eaker shunt trip when pre set current levels and time delay settings are exceeded In addition to the basic protection function Digitrip RMS Trip Unit models 510 610 810 910 and Digitrip OPTIM 750 and...

Страница 3: ...family of plugs is illustrated in Fig 3 1 This plug design will not mechanically fit into the other Digitrip models On the model 310 units the continous current rating Ir equals the rating plug ampere...

Страница 4: ...t and the cir cuit breaker are suitable for the intended installation by comparing nameplate data with any existing equipment Fig 3 6 Removal of Trip Unit and system requirements If both trip unit and...

Страница 5: ...can now be reset and switched to the ON and OFF positions 3 3 Trip Unit Removal Use the following instructions to remove a Digitrip trip unit from a circuit breaker THE VOLTAGES IN ENERGIZED EQUIPMENT...

Страница 6: ...RMS 310 The Digitrip RMS 310 Trip Assembly consists of a Digitrip RMS 310 Trip Unit as described in I L 29C883 3 or 4 auxiliary current transformers and a stab in trip unit ter minal block as shown i...

Страница 7: ...ns 4 3 Digitrip RMS 610 The Digitrip RMS 610 Trip Assembly consists of a Digitrip RMS 610 Trip Unit as described in l L 29 886 3 or 4 aux iliary current transformers a stab in trip unit terminal block...

Страница 8: ...e allows for remote tripping via the flux shunt trip and closing of the circuit breaker 4 5 Digitrip RMS 910 The Digitrip RMS 910 Trip Assembly is similar to the Dig itrip RMS 810 It is a communicatin...

Страница 9: ...ATION 5 1 General The circuit breaker is tripped automatically under fault current conditions by the combined action of three com ponents 1 The sensors which determine the current level 2 The Digitrip...

Страница 10: ...Table 1 Digitrip RMS and Digitrip OPTIM Trip Unit Characteristics for R Frame EATON CORPORATION www eaton com Page 10 Effective Date October 2010 Instruction Leaflet 29C713E Effective October 2010...

Страница 11: ...is same document IMPROPER POLARITY CONNECTIONS ON THE FLUX SHUNT TRIP COIL WILL VOID OVERLOAD AND SHORT CIRCUIT PROTECTION WHICH COULD RESULT IN PERSONAL INJURY OBSERVE POLARITY MARKINGS ON THE SHUNT...

Страница 12: ...ions Available ground fault pick up set tings employing Residual Sensing means are given in Table 3 5 4 3 Source Ground Sensing Depending upon the installation requirements alternate ground fault sens...

Страница 13: ...l L 29 C714 Each circuit breaker shipped from the factory includes a copy of the pages from this document that are applicable to the equipment included in the breaker 5 8 Trip Unit Settings Protectio...

Страница 14: ...30 95 C requires that any ground fault protection system be per formance tested when first installed The test shall be conducted in accordance with approved instructions pro vided with the equipment A...

Страница 15: ...st current of 125 of the Digitrip RMS Ground Fault Trip Unit pick up setting through one phase of the circuit breaker as shown in Fig 7 1 This should cause the breaker to trip in less than 1 second an...

Страница 16: ...es 8 and 9 can be used for record keeping This record should be filled in giving the indi cated reference information and initial time current trip function settings If desirable a copy could be made...

Страница 17: ...Fig 8 Typical Performance Test Record Form EATON CORPORATION www eaton com Page 17 Effective Date October 2010 Instruction Leaflet 29C713E Effective October 2010...

Страница 18: ...3 Time Current Curves Application Data 29 167R RD RDC 310 I t Shape SC 5629 93 RD RDC 310 FIat Response SC 5630 93 RD RDC 310 Ground SC 5631 93 RD RDC 510 610 810 910 Instantaneous SC 5626 93 RD RDC 5...

Страница 19: ...Fig 11 Master Connection Diagram Ground Fault 3 Pole Breaker EATON CORPORATION www eaton com Page 19 Effective Date October 2010 Instruction Leaflet 29C713E Effective October 2010...

Страница 20: ...ter Connection Diagram Ground Fault External Connections 3 Phase 4W Residual 3 Pole Breaker EATON CORPORATION www eaton com Page 20 Effective Date October 2010 Instruction Leaflet 29C713E Effective Oc...

Страница 21: ...Diagram Remote Alarms for use with Digitrip RMS Types 310 GF only 610 810 910 and Digitrip OPTIM 750 and 1050 EATON CORPORATION www eaton com Page 21 Effective Date October 2010 Instruction Leaflet 29...

Страница 22: ...Neutral Current Sensor Torque 1 2 13 Sensor bolts to 35 40 ft lbs EATON CORPORATION www eaton com Page 22 Effective Date October 2010 Instruction Leaflet 29C713E Effective October 2010 Torque to 15 20...

Страница 23: ...5 View of Installed Digitrip RMS Trip Unit with Sealed Cover Fig 16 Jumper Connections EATON CORPORATION www eaton com Page 23 Effective Date October 2010 Instruction Leaflet 29C713E Effective October...

Страница 24: ...108 United States 877 ETN CARE 877 386 2273 Eaton com 2010 Eaton Corporation All Rights Reserved Printed in USA Publication No 6605C99H06 October 2010 PowerChain Management is a registered trademark o...

Отзывы: