background image

The Power/Relay module will maintain the cause of trip 

LEDs history and trip history as long as the control power 

supply is available. With loss of the control power supply, 

only the cause of trip LEDs will be maintained by the 

back-up battery located in the rating plug.

The High-Load message and remote alarm switch are 

pre-set at 85% of the value of the long delay setting. The 

High-Load relay operates and the LED turns

 "

ON ” when 

the 85% level is exceeded only after an approximate 40 

second delay to ride through momentary High-Load con-

ditions.

4.4 Digitrip RMS 810

The Digitrip RMS 810 Trip Assembly is similar to the Dig-

itrip RMS 610 Trip Assembly with the addition of a four-

digit display, three-phase (

I  

, I

B

, I

C

) and one ground cur-

rent (l

G

) or one neutral current (l

                            

), green pointer LEDs 

along with a stepping push button, peak demand, present 

demand and energy consumed green pointer LEDs along 

with a peak demand reset push button as illustrated in 

Table 1. The Digitrip RMS 810 Trip Unit is described in 

l.L. 29-888.

The Trip Assembly provides for both local displays on the 

face of the trip unit and remote communications via an 

IMPACC communication network signal link as illustrated 

in Table 1.

In addition, if desired, an Assemblies Electronic Monitor 

(AEM) as described in l.L. 17-216, may also be installed 

to show the parameters in Table 1 covered under Note 2.

A communicating panel mounted device, the Breaker 

Interface Module (BIM), as described in l.L. 29C893 can 

be used to display metering and other transmittable data.

Interconnections for the IMPACC circuit must be con-

nected as shown in l.L. 29-888 and wiring diagram using 

twisted pair (shielded) No. 18 AWG conductors.

The three-digit IMPACC address must be set on each trip 

unit per instructions given in l.L. 29-888. To insure that 

each circuit breaker in an assembly is properly located 

after the address is set, the breaker should be identified 

with its proper cell location and that reference along with 

the breaker IMPACC address marked on the face of the 

trip unit in the spaces provided.

In addition to the communication of the breaker data, the 

IMPACC module allows for remote tripping (via the flux 

shunt trip) and closing of the circuit breaker.

4.5 Digitrip RMS 910

The Digitrip RMS 910 Trip Assembly is similar to the Dig-

itrip RMS 810. It is a communicating trip unit that pro-

vides all the functions described in Section 4.4 plus the 

addition of the following features both locally displayed 

and remotely communicated:

1.

Phase-to-phase voltages -

  

 V

              

                           

      ,              

V

BC

, V

CA

2.

System power factor - PF

3.

Total harmonic distortion THD for  I 

  , 

I

B

, I

C

The THD calculation also includes the individual har-

monic currents up to the 27 harmonic as a percentage of 

the fundamental. Also included with the THD is provi-

sions for waveform capture information via a host com-

puter. Detailed information is provided in l.L. 29-889.

4.6 Digitrip OPTIM 750

The Digitrip OPTIM 750 is a programmable communicat-

ing microprocessor-based RMS current sensing trip unit. 

For the R-Frame breaker it is physically the same plug-in 

trip unit as all the other Digitrip models. There are two 

style offerings  – Phase Protection with Ground Fault Trip 

(Cat. P76LSIG) and Phase Protection with Ground Fault 

Alarm (Cat. P77LSIA).

The front panel of the unit has 3 or 4 causes of trip LEDs 

and a telephone type receptacle for purposes of pro-

gramming settings, testing and displaying phase currents 

via a separate hand-held unit called the OPTIMizer. 

There are up to 10 trip functions that can be programmed 

which includes both a 1

2

 

 

and 1

4

t curve for the Long-Time 

slope. There are also typically ten times the number of 

setpoints compared to a front adjustable trip unit. All 

transmittable data as well as programming of the trip 

curve settings can also be communicated over a twisted 

pair cable via the breaker

'

s secondaries (terminals C11, 

C12) to either a host computer or a panel mounted 

Breaker Interface Module (BIM).

The breaker includes a Power/Relay module per Fig. 5 to 

provide power for the communications function and delay 

output for alarming.

Detail information on Digitrip OPTIM trip units is in 

l.L. 29C891.

4.7 Digitrip OPTIM 1050

The Digitrip OPTIM 1050 is a programmable communi-

cating microprocessor-based RMS current sensing trip 

unit. For the R-Frame breaker it is physically the same 

Effective Date October 2010   

 

 

 

 

                  Instruction Leaflet 29C713E

 

 

 

 

 

 

 

 

 

 

 

Effective October 2010

EATON CORPORATION www.eaton.com 

 

 

 

 

 

 

 

                     Page 8

A

D

 AB 

A

Содержание Digitrip RMS

Страница 1: ...for Ground Fault Trip Units 14 6 2 1 Code Requirements 14 6 2 2 Standards Requirements 14 6 2 3 General Test Instructions 15 7 0 Record Keeping 16 8 0 References 16 8 1 R Frame 16 8 2 Digitrip RMS Tri...

Страница 2: ...eaker shunt trip when pre set current levels and time delay settings are exceeded In addition to the basic protection function Digitrip RMS Trip Unit models 510 610 810 910 and Digitrip OPTIM 750 and...

Страница 3: ...family of plugs is illustrated in Fig 3 1 This plug design will not mechanically fit into the other Digitrip models On the model 310 units the continous current rating Ir equals the rating plug ampere...

Страница 4: ...t and the cir cuit breaker are suitable for the intended installation by comparing nameplate data with any existing equipment Fig 3 6 Removal of Trip Unit and system requirements If both trip unit and...

Страница 5: ...can now be reset and switched to the ON and OFF positions 3 3 Trip Unit Removal Use the following instructions to remove a Digitrip trip unit from a circuit breaker THE VOLTAGES IN ENERGIZED EQUIPMENT...

Страница 6: ...RMS 310 The Digitrip RMS 310 Trip Assembly consists of a Digitrip RMS 310 Trip Unit as described in I L 29C883 3 or 4 auxiliary current transformers and a stab in trip unit ter minal block as shown i...

Страница 7: ...ns 4 3 Digitrip RMS 610 The Digitrip RMS 610 Trip Assembly consists of a Digitrip RMS 610 Trip Unit as described in l L 29 886 3 or 4 aux iliary current transformers a stab in trip unit terminal block...

Страница 8: ...e allows for remote tripping via the flux shunt trip and closing of the circuit breaker 4 5 Digitrip RMS 910 The Digitrip RMS 910 Trip Assembly is similar to the Dig itrip RMS 810 It is a communicatin...

Страница 9: ...ATION 5 1 General The circuit breaker is tripped automatically under fault current conditions by the combined action of three com ponents 1 The sensors which determine the current level 2 The Digitrip...

Страница 10: ...Table 1 Digitrip RMS and Digitrip OPTIM Trip Unit Characteristics for R Frame EATON CORPORATION www eaton com Page 10 Effective Date October 2010 Instruction Leaflet 29C713E Effective October 2010...

Страница 11: ...is same document IMPROPER POLARITY CONNECTIONS ON THE FLUX SHUNT TRIP COIL WILL VOID OVERLOAD AND SHORT CIRCUIT PROTECTION WHICH COULD RESULT IN PERSONAL INJURY OBSERVE POLARITY MARKINGS ON THE SHUNT...

Страница 12: ...ions Available ground fault pick up set tings employing Residual Sensing means are given in Table 3 5 4 3 Source Ground Sensing Depending upon the installation requirements alternate ground fault sens...

Страница 13: ...l L 29 C714 Each circuit breaker shipped from the factory includes a copy of the pages from this document that are applicable to the equipment included in the breaker 5 8 Trip Unit Settings Protectio...

Страница 14: ...30 95 C requires that any ground fault protection system be per formance tested when first installed The test shall be conducted in accordance with approved instructions pro vided with the equipment A...

Страница 15: ...st current of 125 of the Digitrip RMS Ground Fault Trip Unit pick up setting through one phase of the circuit breaker as shown in Fig 7 1 This should cause the breaker to trip in less than 1 second an...

Страница 16: ...es 8 and 9 can be used for record keeping This record should be filled in giving the indi cated reference information and initial time current trip function settings If desirable a copy could be made...

Страница 17: ...Fig 8 Typical Performance Test Record Form EATON CORPORATION www eaton com Page 17 Effective Date October 2010 Instruction Leaflet 29C713E Effective October 2010...

Страница 18: ...3 Time Current Curves Application Data 29 167R RD RDC 310 I t Shape SC 5629 93 RD RDC 310 FIat Response SC 5630 93 RD RDC 310 Ground SC 5631 93 RD RDC 510 610 810 910 Instantaneous SC 5626 93 RD RDC 5...

Страница 19: ...Fig 11 Master Connection Diagram Ground Fault 3 Pole Breaker EATON CORPORATION www eaton com Page 19 Effective Date October 2010 Instruction Leaflet 29C713E Effective October 2010...

Страница 20: ...ter Connection Diagram Ground Fault External Connections 3 Phase 4W Residual 3 Pole Breaker EATON CORPORATION www eaton com Page 20 Effective Date October 2010 Instruction Leaflet 29C713E Effective Oc...

Страница 21: ...Diagram Remote Alarms for use with Digitrip RMS Types 310 GF only 610 810 910 and Digitrip OPTIM 750 and 1050 EATON CORPORATION www eaton com Page 21 Effective Date October 2010 Instruction Leaflet 29...

Страница 22: ...Neutral Current Sensor Torque 1 2 13 Sensor bolts to 35 40 ft lbs EATON CORPORATION www eaton com Page 22 Effective Date October 2010 Instruction Leaflet 29C713E Effective October 2010 Torque to 15 20...

Страница 23: ...5 View of Installed Digitrip RMS Trip Unit with Sealed Cover Fig 16 Jumper Connections EATON CORPORATION www eaton com Page 23 Effective Date October 2010 Instruction Leaflet 29C713E Effective October...

Страница 24: ...108 United States 877 ETN CARE 877 386 2273 Eaton com 2010 Eaton Corporation All Rights Reserved Printed in USA Publication No 6605C99H06 October 2010 PowerChain Management is a registered trademark o...

Отзывы: