background image

lever and a rotating trip lever to actuate the tripping action 

of the circuit breaker.

When the Flux Shunt Trip is reset by the handle moved to 

reset position, the moving core assembly is held in readi-

ness against the force of the compressed spring by the 

permanent magnet. When a tripping action is initiated, 

the Flux Shunt Trip coil receives a tripping pulse from the 

Digitrip RMS Trip Unit. This pulse overcomes the holding 

released to trigger the tripping operation via the rotating 

trip bar.

5.4 GROUND FAULT PROTECTION

5.4.1 General

When the Digitrip RMS Trip Assembly includes ground 

fault protection, the distribution system characteristics, 

i.e., system grounding, number of sources, number and 

location of ground points, etc. must be considered as well 

as the manner and location in which the circuit breaker is 

applied to the system.

Two modes of sensing ground fault currents are generally 

used: residual and source 

g

round. R-

F

rame 

Circuit

Brea kers are internally prewired to accommodate 

both types. A side mounted 4-point terminal block, as 

shown in Fig. 4, is provided to revise connections 

required to accommodate each method. A nameplate is 

provided on the side of the circuit breaker that illustrates 

the required connections. Applicable connection varia-

tions are illustrated in Fig. 11.

If the system neutral is grounded, but no phase-to-neutral 

loads are used, the Digitrip RMS Trip Assembly includes 

all of the components necessary for ground fault protec-

tion.

5.4.2 Residual Sensing

The standard mode of ground fault sensing in 

R-Frame Circuit Breakers is Residual Sensing. This 

mode utilizes one current sensor on each phase conduc-

tor and one on the neutral if 4-wire system. This mode of 

sensing vectorially sums the outputs of the three or four 

individual current sensors. As long as the vectorial sum is 

zero, then no ground fault exists. The neutral sensor must 

have characteristics which are identical to the three inter-

nally mounted phase current sensors. Available types of 

neutral sensors are illustrated in Fig. 14. Residual ground 

fault sensing means are adaptable to main and feeder 

breaker applications. Available ground fault pick-up set-

tings employing Residual Sensing means are given in 

Table 3.

5.4.3 Source Ground Sensing

Depending upon the installation requirements, alternate 

ground fault sensing schemes may be dictated. The 

ground return method is most applicable where ground 

fault protection is desired only on the main circuit breaker 

in a simple radial system. This method is also applicable 

on double-ended systems where a mid-point grounding 

electrode is employed. For this mode of sensing, a single 

current sensor mounted on the equipment bonding 

in the grounding electrode conductor and all other equip-

ment grounding conductors.

The values shown in Table 3 will apply when the neutral 

sensors shown in Fig. 14 are employed in a source 

ground sensing scheme provided the neutral sensor is 

the same as the frame rating.

Note: Regardless of the mode of sensing employed, 

the polarity of the sensor connections is critical. 

Always observe the polarity markings on the installa-

tion drawings. To insure correct ground fault equip-

National Electrical Code requirements under Article 

230-95(C).

5.4.4 Ground Fault Settings

The adjustment of the ground fault functional settings is 

illustrated in the applicable Digitrip RMS Trip Unit instruc-

ground fault Time-Current curves referenced in Section 6 

of this instruction book. Applicable residual ground fault 

pick-up settings and current values are given in Table 3 

as well as on the Time-Current curve.

5.5 Current Sensors

The three primary current sensors installed in the circuit 

breaker are located internally on the lower conducts 

which are normally on the load side of the main contacts.

The auxiliary current transformers are mounted as shown 

in Fig. 4. The ground fault auxiliary current transformer is 

supplied only when the ground fault protection function is 

supplied in the Digitrip RMS Trip Unit. The Neutral Auxil-

iary Current Transformer is supplied only with 4-pole 

breakers. A partial internal schematic is shown in Fig. 6 

as well as in the residual diagram shown in Fig. 8.

The primary current sensors produce an output propor-

tional to the load current and furnish the Digitrip RMS Trip 

Assembly with the intelligence and energy to trip the cir-

cuit breaker when functional protection settings are 

exceeded.

EATON CORPORATION www.eaton.com 

 

 

 

 

 

 

 

                     Page 12

Содержание Digitrip RMS

Страница 1: ...for Ground Fault Trip Units 14 6 2 1 Code Requirements 14 6 2 2 Standards Requirements 14 6 2 3 General Test Instructions 15 7 0 Record Keeping 16 8 0 References 16 8 1 R Frame 16 8 2 Digitrip RMS Tri...

Страница 2: ...eaker shunt trip when pre set current levels and time delay settings are exceeded In addition to the basic protection function Digitrip RMS Trip Unit models 510 610 810 910 and Digitrip OPTIM 750 and...

Страница 3: ...family of plugs is illustrated in Fig 3 1 This plug design will not mechanically fit into the other Digitrip models On the model 310 units the continous current rating Ir equals the rating plug ampere...

Страница 4: ...t and the cir cuit breaker are suitable for the intended installation by comparing nameplate data with any existing equipment Fig 3 6 Removal of Trip Unit and system requirements If both trip unit and...

Страница 5: ...can now be reset and switched to the ON and OFF positions 3 3 Trip Unit Removal Use the following instructions to remove a Digitrip trip unit from a circuit breaker THE VOLTAGES IN ENERGIZED EQUIPMENT...

Страница 6: ...RMS 310 The Digitrip RMS 310 Trip Assembly consists of a Digitrip RMS 310 Trip Unit as described in I L 29C883 3 or 4 auxiliary current transformers and a stab in trip unit ter minal block as shown i...

Страница 7: ...ns 4 3 Digitrip RMS 610 The Digitrip RMS 610 Trip Assembly consists of a Digitrip RMS 610 Trip Unit as described in l L 29 886 3 or 4 aux iliary current transformers a stab in trip unit terminal block...

Страница 8: ...e allows for remote tripping via the flux shunt trip and closing of the circuit breaker 4 5 Digitrip RMS 910 The Digitrip RMS 910 Trip Assembly is similar to the Dig itrip RMS 810 It is a communicatin...

Страница 9: ...ATION 5 1 General The circuit breaker is tripped automatically under fault current conditions by the combined action of three com ponents 1 The sensors which determine the current level 2 The Digitrip...

Страница 10: ...Table 1 Digitrip RMS and Digitrip OPTIM Trip Unit Characteristics for R Frame EATON CORPORATION www eaton com Page 10 Effective Date October 2010 Instruction Leaflet 29C713E Effective October 2010...

Страница 11: ...is same document IMPROPER POLARITY CONNECTIONS ON THE FLUX SHUNT TRIP COIL WILL VOID OVERLOAD AND SHORT CIRCUIT PROTECTION WHICH COULD RESULT IN PERSONAL INJURY OBSERVE POLARITY MARKINGS ON THE SHUNT...

Страница 12: ...ions Available ground fault pick up set tings employing Residual Sensing means are given in Table 3 5 4 3 Source Ground Sensing Depending upon the installation requirements alternate ground fault sens...

Страница 13: ...l L 29 C714 Each circuit breaker shipped from the factory includes a copy of the pages from this document that are applicable to the equipment included in the breaker 5 8 Trip Unit Settings Protectio...

Страница 14: ...30 95 C requires that any ground fault protection system be per formance tested when first installed The test shall be conducted in accordance with approved instructions pro vided with the equipment A...

Страница 15: ...st current of 125 of the Digitrip RMS Ground Fault Trip Unit pick up setting through one phase of the circuit breaker as shown in Fig 7 1 This should cause the breaker to trip in less than 1 second an...

Страница 16: ...es 8 and 9 can be used for record keeping This record should be filled in giving the indi cated reference information and initial time current trip function settings If desirable a copy could be made...

Страница 17: ...Fig 8 Typical Performance Test Record Form EATON CORPORATION www eaton com Page 17 Effective Date October 2010 Instruction Leaflet 29C713E Effective October 2010...

Страница 18: ...3 Time Current Curves Application Data 29 167R RD RDC 310 I t Shape SC 5629 93 RD RDC 310 FIat Response SC 5630 93 RD RDC 310 Ground SC 5631 93 RD RDC 510 610 810 910 Instantaneous SC 5626 93 RD RDC 5...

Страница 19: ...Fig 11 Master Connection Diagram Ground Fault 3 Pole Breaker EATON CORPORATION www eaton com Page 19 Effective Date October 2010 Instruction Leaflet 29C713E Effective October 2010...

Страница 20: ...ter Connection Diagram Ground Fault External Connections 3 Phase 4W Residual 3 Pole Breaker EATON CORPORATION www eaton com Page 20 Effective Date October 2010 Instruction Leaflet 29C713E Effective Oc...

Страница 21: ...Diagram Remote Alarms for use with Digitrip RMS Types 310 GF only 610 810 910 and Digitrip OPTIM 750 and 1050 EATON CORPORATION www eaton com Page 21 Effective Date October 2010 Instruction Leaflet 29...

Страница 22: ...Neutral Current Sensor Torque 1 2 13 Sensor bolts to 35 40 ft lbs EATON CORPORATION www eaton com Page 22 Effective Date October 2010 Instruction Leaflet 29C713E Effective October 2010 Torque to 15 20...

Страница 23: ...5 View of Installed Digitrip RMS Trip Unit with Sealed Cover Fig 16 Jumper Connections EATON CORPORATION www eaton com Page 23 Effective Date October 2010 Instruction Leaflet 29C713E Effective October...

Страница 24: ...108 United States 877 ETN CARE 877 386 2273 Eaton com 2010 Eaton Corporation All Rights Reserved Printed in USA Publication No 6605C99H06 October 2010 PowerChain Management is a registered trademark o...

Отзывы: