background image

Installation Leaflet

Page 7                  Effective: April 2003

Pow-R-Command 100

IL01412003

      For More Information visit www.cutler-hammer.com

SECTION 3: LOW-VOLTAGE DEVICE
TERMINATION

All open areas in the panels are considered
as low-voltage/class-2 termination areas.
No voltages above 28VAC are permitted in
this area. Inputs are designed so that only
dry contact devices are accepted.

NO EXTERNAL VOLTAGES SHOULD BE
APPLIED TO THE LOW-VOLTAGE
TERMINAL BLOCKS. ALL NECESSARY
POWER IS PROVIDED BY THE PANEL.

Low-voltage devices should be terminated
using a minimum #22AWG twisted pair
wire. Shielding is generally not required.
Low-voltage device cables should not be
located in the same conduit with the high-
voltage load wires. Be sure the wire type
you use is rated properly, especially for
plenum or hazardous applications.

3-1 PANELBOARD

In most cases, Application Specific Cards
will be located in the 7X Expansion Chassis
installed in the panel. Power supply and
Network connections will be provided in the
factory.

In rare case of the 7X-Expansion Chassis
located externally to the panel, the network
cable and the power supply cable should
be installed between the panel and the 7X-
Expansion Chassis. For Network termina-
tion, please refer to SECTION 5.

The personnel installing the panel are
responsible for providing and termination
wiring of all external low-voltage devices.
Use knockouts provided on the bottom and
sides of the chassis to enter the low-
voltage termination area.

All low-voltage (dry closure) devices
should be terminated on the 7X board
terminal blocks TB1, TB2, and TB3. Terminal
blocks 

TB1

 and 

TB3

 are designated

locations for inputs from low-voltage
devices—numbered respectively 

1-24

 and

25-48

. Terminal block 

TB2

 is a 

COMMON

(ground) terminal for all low-voltage
devices terminated in the panel.

Network “Out”
Connector

Power Supply

Connector

Network “In”

Connector

Low-Voltage Device

Terminals COMMON

Application Specific
Controller Connectors

Low-Voltage Device
Terminals 1-24

Low-Voltage Device
Terminals 25-48

Figure 3-1: 7X-Expansion Chassis Back-Plane Board

Содержание Cuttler-Hammer Pow-R-Command 100

Страница 1: ...April 2003 Pow R CommandTM PRCTM 100 Instruction Leaflet IL01412003 For More Information visit www cutler hammer com...

Страница 2: ...EME CAUTION WHEN OPERATING THE SYSTEM DANGEROUS VOLTAGES MAY EXIST INSIDE THE UNITS Failure to follow any or all warnings and instructions contained herein may cause severe injury or death and or dama...

Страница 3: ...CTION 4 APPLICATION SPECIFIC CARD TERMINATION 10 4 1 UNIVERSAL SYSTEM CONTROLLER 10 4 2 SWITCH OVERRIDE CONTROLLER 10 4 3 UNIVERSAL I O MODULE 11 4 4 LOW VOLTAGE INPUTS OUTPUTS 11 4 5 LOW VOLTAGE WIRI...

Страница 4: ...GHBS or BABR breakers using the time schedules or the console Panelboard with 5X Controller Chassis and 7X Expansion Chassis see Fig 1 2 2 Combining the 5X Controller Chassis the 7X Expansion Chassis...

Страница 5: ...s mounted in the panel For low voltage device termination please refer to SECTION 3 Subsection 3 2 For remote controlled breaker termination please refer to SECTION 3 Subsection 3 3 1 3 RELAY PANEL A...

Страница 6: ...sible for providing and terminating the power wires to these panels If the trim is installed remove the trim for the Expansion Control Cabinet remove the door and the power supply cover There are two...

Страница 7: ...Power supply and Network connections will be provided in the factory In rare case of the 7X Expansion Chassis located externally to the panel the network cable and the power supply cable should be ins...

Страница 8: ...ly described enclosure types to attach conduit and provide access to the low voltage termination area Panels using Expansion Cabinet might or might not contain 5X Controller Chassis For panels with a...

Страница 9: ...e connectors are numbered 1 24 on the left side of the board and 25 48 on the right side of the board see Fig 3 3 On the Panel side the pigtails are connected to the low voltage connectors on the back...

Страница 10: ...of an Expansion Control Cabinet The SOC will accept only dry contact closure devices i e switches occupancy sensors Building Management System relay etc Contact closure is processed by the SOC card re...

Страница 11: ...e 100 mA for powering external devices The 24VAC used to power controllers can also be used for powering external devices Although each controller may differ in the number of low voltage control point...

Страница 12: ...onnectors The input can be defined at start up as a variety of maintained and momentary contact configurations One special use for these inputs is a counter function This function can be used for a va...

Страница 13: ...itch 24VDC or 24VAC The outputs are defined at start up as normally open or closed and maintained or pulsed The pilot lamp digital outputs on an SOC controller provide a 24VDC half wave rectified sign...

Страница 14: ...an be wired adjacent to each other In this case the lower number represents the DOWN lower position or OFF action while the higher number represents the UP or TOP action Figure 4 16 Application Exampl...

Страница 15: ...reduce the number of conductors required to pull The SOC has the same inputs as described above for the USC The differences being the connectors are located along the left edge of the controller SPECI...

Страница 16: ...the LED Wiring the Pilot s as described in this note would allow for two modes of operation The Pilot could act as feedback showing the resulting state of a remote load In other words when the load is...

Страница 17: ...the difference being the location of the connectors The CO2 Sensor shows all modes con nected This sensor could provide direct analog input through the 250 Ohm resistor and can also provide closures...

Страница 18: ...bly better to make any adjustment using the control lers built in type definitions The CES Series sensors are supplied from the factory with the following calibrated ranges CES I 0 to 100 FC 1 to 5 V...

Страница 19: ...Occupancy sensor would have the load controlling the 120VAC to the light fixtures as its control output The switches control dimming and the sensor controls on off There are many alternatives to this...

Страница 20: ...These timers delay keep the lights on for an adjustable period of time AFTER sensing no activity For best results with lighting control systems it is recom mended that this delay be set to minimum an...

Страница 21: ...n Loops are not allowed on the network The ends of the Network should be terminated with the End of the Line Resistors A 12 Ohm resistors must be placed on the furthest two panels on the network One e...

Страница 22: ...cable S bottom pin on the connector shield of the network cable Network In Terminals Network Out Terminals Figure 5 3 Panelboard 5X Controller Chassis Network Terminations Knockouts Note As mentioned...

Страница 23: ...al Connect shield of the cable to the SHLD terminal see Fig 5 4 For the panel in the middle of the network connect the end of the incoming cable to the IN IN and SHLD and the end of the outgoing cable...

Страница 24: ...ctly to the RIB board see Fig 5 7 The connectors for the network are provided at the factory Remove the plug from the socket on the RIB board Terminate the network cable in the plug and push it back i...

Страница 25: ...ll offer greater protection against this interference This text is intended as a guideline for the use of repeaters it is in no way all inclusive Because of the nature of the PRC100 implementation of...

Страница 26: ...ected to the terminal The shield is connected to the third terminal If the NIB is located at the end of the Network a 120 ohm termination resistor should be connected between the and terminals 6 1 NIB...

Страница 27: ...ork to a PC using a standard Ethernet connection but also allow for remote access via a phone line In this case the Ethernet Server need not be physically located near the PC but rather near the Ether...

Страница 28: ...or one person to perform this by pre addressing all cards at one panel This would require a temporary connection of the NIB to a panel and a PC connected to the NIB Each card is then added to the netw...

Страница 29: ...yed right of center at the top of the window beneath the text Step 4 of 5 This time out will count down from 30 seconds and then explain that the RESET button must be pressed before clicking the Finis...

Страница 30: ...system table The following steps briefly describe this procedure STEP 1 Connect the network test tool to the four pin test connector on the controller or nearby networked controller STEP 2 Launch the...

Страница 31: ...t parameter screen enter the desired address for this controller Remember that controller addresses must be unique DO NOT choose an address already assigned to another controller STEP 12 Tap OK in the...

Страница 32: ...ssistance Please Contact Your Cutler Hammer Representative Eaton Corporation Cutler Hammer business unit 1000 Cherrington Parkway Moon Township PA 15108 United States tel 1800 525 2000 www cutler hamm...

Отзывы: