Installation Leaflet
Page 15 Effective: April 2003
Pow-R-Command 100
IL01412003
For More Information visit www.cutler-hammer.com
APPLICATION EXAMPLE 2: FIELD
TERMINATING DEVICES DIRECTLY TO
CONTROLLERS
The following examples show how
switches can be connected directly to a
controller. This is often desirable when
fewer than 12 switches are required.
The three position push-button switch, in
this example, contains pilot lights in each
position. As wired (directly across the 15
Volt supply) the pilot lights will always be
Figure 4-17: Application Example SOC Switch Inputs
on. The dotted lines imply that the pilot lights
are wired together inside the wall-box. As
shown there are NO current limiting
resistors as the specified switch has
internal current limiting. Also of interest is
that all the pilots and switches share a
single common. These can be combined in
the wall-box to reduce the number of
conductors required to pull.
The SOC has the same inputs as described
above for the USC. The differences being
the connectors are located along the left
edge of the controller.
SPECIAL NOTE: Notice that the momentary
switch is wired to ANALOG IN #1 (UI1).
This is because maintained closures during
power-up will force the controller into a
special override mode. SIMPLE RULE: When
connecting switches to analog inputs –
never use maintained contacts on Analog
Input #1, especially if there is a chance that
the contact will be closed during controller
power-up.
Leviton 1201-2 (equiv.)
SPST
Control Def.
Maintained
Input 1:11I “DINC”
Command “ON”
Leviton 1256 (equiv.)
SPDT Center Off
UP
Control Def
Momentary (3-wire)
Activation 1:187I “????”
Deactivation 1:17I “????”
Command “ON”
Touchplate
8219-3083-S101
Control Def
TOP
Momentary (ON|OFF)
Input 1:24I “????”
Command “ON”
MIDDLE
Momentary (ON|OFF)
Input 1:23I “????”
Command “ON”
BOTTOM
Momentary (ON|OFF)
Input 1:22I “????”
Command “ON”
SOC
USC
YEL/BLK Pilot PWR
WHT/BLK Pilot COM
WHT Switch COM
YEL Switch CNTL
WHT Switch COM
YEL Switch CNTL
WHT Switch COM
YEL Switch CNTL