Catalog Steady State

Inrush

Input

Number

Wattage

Wattage

Voltage

PSS55A

55W

250W

115VAC

PSS55B

55W

250W

230VAC

PSS55C

55W

250W

360 - 480VAC

Protective Features, Cont’d

timer. If 24VDC power is removed, the soft starter remem-

bers the remaining cool-down time and will not reset until

the total cool-down time has elapsed.
The unit monitors these conditions for overload:

Thermal (current) Overload - monitors RMS, with a

5, 10, 20, or 30-second delay time based on Trip

Class setting.

Protective

Setting

Factory

Feature

Default

Overload 

32% - 100% of rated current

32%

(FLA Dial Range)
Trip Class

5, 10, 20, 30

5

Fault Reset

Auto, Manual

Manual

Jam

On, Disable

On

Stall

On, Disable

On

Phase Loss

On, Disable

On

Phase Reversal

On, Disable

On

Overload

On, Disable

On

Programming Settings

General

To program and operate the IT Soft Starter, a “Control

Interface Module” (CIM) is required (see Fig. 6). The CIM

(Catalog No. EMA71) is for use with all models: S801N,

S801R, S801T, and S801V. The CIM (Catalog No. EMA72)

is used with all model S801N, S801R, S801T and S801V

with the pump control option (see Fig. 7). The CIM serves

as the interface between the operator and the Soft Starter

control circuitry to program the Soft Starter. The CIM dip

switches and rotary controls are used to select the Soft

Starter settings. When making adjustment to the CIM

under normal operation, the LED’s will function as follows:
A change to any dip switch will cause all LED’s to flash

momentarily.
An adjustment to any POT will cause all LED’s to light

and stay lit until adjustment of POT has been completed.
While selecting these parameters, 24VDC power may be

applied to the Soft Starter, but it is not required.

NOTE:

 The IT Soft Starter does not have to be powered

to make adjustment to the control interface module. Once

the unit is energized, it will communicate with the CIM

and load the program into the Soft Starter. Allow the unit

2 seconds to ensure communication checks complete

and values are set. To verify CIM is operational, press

“Fault Reset.” If the CIM is powered and communicating,

all LED’s will momentarily flash.
See the user manual for additional detail on the standard

and pump control option.

Procedure for Starting

Application Note - Permissive (P)

(P) must be held high (24VDC) in order to START the

Soft Starter.
Remove 24VDC from terminal P to initiate a stop.
Run inputs (terminals 1 through 4) are a momentary

high (24VDC).
If the inputs (Input 1, 2, 3, 4) are high when the Per-

missive opens, the Soft Starter will STOP.
The Soft Starter will not start when 24VDC is applied

to the Permissive (P) until Input 1 changes from 0 volts

(open) to a high (+24V) condition. (Once P is at 24

volts, Input 1 must cycle from 0 volts to 24 volts to

start.)
On the larger soft starters when the bypass contactors

close, a sound similar to contactor chattering can be

heard. This sound is caused by more than one contactor

closing in a staggered manner over a very short period

of time. This is part of normal operation and should not

be misinterpreted as a dirty pickup.
For two-wire control, jumper permissive (P) and Input

1, together.

24VDC Power Requirements

When sizing a 24VDC power supply for your IT soft starter,

it must meet the following steady state and inrush charac-

teristics.
Steady State Minimum = 25 watts
Inrush Minimum = 240 watts for 150 msecs
Voltage on the unit cannot exceed 30VDC. The soft starter

will turn off at approximately 20.9VDC.
It is recommended that power supplies from Cutler-Hammer

be used.
The following C-H power supplies are available:

Table 5

Table 6

NOTE: 

A minimum of #14 AWG should be used between

the power supply and the 24V (+) and (-) terminals of the

soft starter.

Protective Features

The soft starter cannot be restarted until the calculated

cool-down time has passed. Cycling power does not reset

All manuals and user guides at all-guides.com

Содержание Cutler-Hammer S801TR

Страница 1: ...ll wave power bridge The voltage and current applied to the motor is controlled by varying the thyristor conduction period This in turn controls the torque supplied by the motor After the motor reache...

Страница 2: ...0 5 Standard 10 4 1 7 N m 65mm Lockwasher and 15 in lb 2 55 in Flat Washer S801R 1 4 20 x 0 625 Standard 1 4 4 2 8 N m 110mm Lockwasher and 25 in lb 4 33 in Flatwasher Required Mounting Hardware Fram...

Страница 3: ...cation as shown To mount the unit use all the hardware specified in Table 1 on page 2 of this leaflet Tighten to the torque specified TO AVOID SHOCK HAZ ARD DISCONNECT ALL POWER BEFORE ANY FUNCTIONS A...

Страница 4: ...AUX BORNES SAUF AVIS CONTRAIRE DANS CE MANUEL TOUTE LA FILERIE DE COMMANDE EST DE CALIBRE 22 A 12 AWG L INOBSERVATION DE CETTE MESURE POURRAIT CAUSER DES DOMMAGES IMPORTANTS AU CONTROLEUR ATTENTION T...

Страница 5: ...DAMAGE TO THE CONTROLLER CAUTION APPLIQUER UNE TENSION DE 24V C C AUX BORNES SAUF AVIS CONTRAIRE DANS CE MANUEL TOUTE LA FILERIE DE COMMANDE EST DE CALIBRE 22 A 12 AWG L INOBSERVATION DE CETTE MESURE...

Страница 6: ...d it will communicate with the CIM and load the program into the Soft Starter Allow the unit 2 seconds to ensure communication checks complete and values are set To verify CIM is operational press Fau...

Страница 7: ...41 24V power supply low 42 Timer system fault 43 Watchdog reset occurred 44 PLL DSP 45 Illegal address DSP Effective 9 00 Table 7 Fig 6 Soft Start Control Interface Module CIM TORQUE T2 T1 TORQUE T2...

Страница 8: ...40 50 50 S801R10N3S 80 22 40 45 25 20 30 25 60 50 75 60 R13N3S Three Phase Motor kW Rating 50 Hertz hp Rating 60 Hertz 200V 230V 460V 575V 15 Second Ramp 4 Starts per Hour 450 Current Limit 40o C Fra...

Страница 9: ...10 30 25 40 30 N66N3S 110 mm 65 15 30 33 15 15 20 15 50 40 50 50 S801R10N3S 80 22 40 45 25 20 30 25 60 50 75 60 R13N3S Three Phase Motor hp Rating 60 Hertz kW Rating 50 Hertz 200V 230V 460V 575V Cooli...

Страница 10: ...ce or start up assistance 24 hours day 7 days week please call 1 800 498 2678 Cutler Hammer Solid State Reduced Voltage Motor Starter Aftermarket Services Technical telephone support Resident service...

Отзывы: