background image

Pub 49004

Effective 9/00

Page 4

Fig. 5   Terminal Board

APPLY ONLY 24VDC TO CONTROL TERMINAL
BOARD UNLESS SPECIFIED OTHERWISE IN THIS
MANUAL. ALL CONTROL WIRING IS 22 - 12 AWG.
FAILURE TO FOLLOW THIS CAUTION COULD RE-
SULT IN SEVERE DAMAGE TO THE CONTROLLER.

Power Wiring

Control Wiring Inputs

The controller on the IT Soft Starter has the inputs shown

in Table 4 on Page 5 of this leaflet.

Fig. 4    Elementary Diagram for Soft Starter with

HAND/OFF/AUTO/RESET with PLC Shown
with 120VAC Alarm and Run Indication

261349

CAUTION

APPLIQUER UNE TENSION DE 24V C.C. AUX BORNES
SAUF AVIS CONTRAIRE DANS CE MANUEL. TOUTE
LA FILERIE DE COMMANDE EST DE CALIBRE 22 A
12 AWG. L’INOBSERVATION DE CETTE MESURE
POURRAIT CAUSER DES DOMMAGES IMPORTANTS
AU CONTROLEUR.

ATTENTION

THERE CAN BE LINE VOLTAGE POTENTIAL AT THE
MOTOR LOAD TERMINALS EVEN WITH THE START-
ER IN THE OFF STATE. THIS IS DUE TO THE POSSI-
BLE LEAKAGE ACROSS SCRS. ALWAYS DISCON-
NECT INPUT POWER BEFORE SERVICING STARTER
MOTOR.

CAUTION

IL PEUT EXISTER UNE TENSION DE LIGNE AUX
BORNES DU COTE CHARGE DU MOTEUR BIEN QUE
LE MOTEUR SOIT ARRETE. CELAS’EXPLIQUE DU
FAIT DE FUITES POSSIBLES A TRAVERS LES RE-
DRESSEURS AU SILICIUM. TOUJOURS DEBRANCH-
ER L’ALIMENTATION AVANT D’EFFECTUER DES
TRAVAUX SUR LE DEMARREUR.

ATTENTION

All manuals and user guides at all-guides.com

Содержание Cutler-Hammer S801TR

Страница 1: ...ll wave power bridge The voltage and current applied to the motor is controlled by varying the thyristor conduction period This in turn controls the torque supplied by the motor After the motor reache...

Страница 2: ...0 5 Standard 10 4 1 7 N m 65mm Lockwasher and 15 in lb 2 55 in Flat Washer S801R 1 4 20 x 0 625 Standard 1 4 4 2 8 N m 110mm Lockwasher and 25 in lb 4 33 in Flatwasher Required Mounting Hardware Fram...

Страница 3: ...cation as shown To mount the unit use all the hardware specified in Table 1 on page 2 of this leaflet Tighten to the torque specified TO AVOID SHOCK HAZ ARD DISCONNECT ALL POWER BEFORE ANY FUNCTIONS A...

Страница 4: ...AUX BORNES SAUF AVIS CONTRAIRE DANS CE MANUEL TOUTE LA FILERIE DE COMMANDE EST DE CALIBRE 22 A 12 AWG L INOBSERVATION DE CETTE MESURE POURRAIT CAUSER DES DOMMAGES IMPORTANTS AU CONTROLEUR ATTENTION T...

Страница 5: ...DAMAGE TO THE CONTROLLER CAUTION APPLIQUER UNE TENSION DE 24V C C AUX BORNES SAUF AVIS CONTRAIRE DANS CE MANUEL TOUTE LA FILERIE DE COMMANDE EST DE CALIBRE 22 A 12 AWG L INOBSERVATION DE CETTE MESURE...

Страница 6: ...d it will communicate with the CIM and load the program into the Soft Starter Allow the unit 2 seconds to ensure communication checks complete and values are set To verify CIM is operational press Fau...

Страница 7: ...41 24V power supply low 42 Timer system fault 43 Watchdog reset occurred 44 PLL DSP 45 Illegal address DSP Effective 9 00 Table 7 Fig 6 Soft Start Control Interface Module CIM TORQUE T2 T1 TORQUE T2...

Страница 8: ...40 50 50 S801R10N3S 80 22 40 45 25 20 30 25 60 50 75 60 R13N3S Three Phase Motor kW Rating 50 Hertz hp Rating 60 Hertz 200V 230V 460V 575V 15 Second Ramp 4 Starts per Hour 450 Current Limit 40o C Fra...

Страница 9: ...10 30 25 40 30 N66N3S 110 mm 65 15 30 33 15 15 20 15 50 40 50 50 S801R10N3S 80 22 40 45 25 20 30 25 60 50 75 60 R13N3S Three Phase Motor hp Rating 60 Hertz kW Rating 50 Hertz 200V 230V 460V 575V Cooli...

Страница 10: ...ce or start up assistance 24 hours day 7 days week please call 1 800 498 2678 Cutler Hammer Solid State Reduced Voltage Motor Starter Aftermarket Services Technical telephone support Resident service...

Отзывы: