background image

Pub 49004

Page 7

Soft Starter Flash Codes Sent to CIM

To obtain flash codes from the CIM, hold the RESET

button down and count the number of times all the LEDs

on the CIM flash.
For example, if you see three flashes, and then two more

flashes after a short pause, the flash code is 32.
The CIM can provide multiple flash codes, if more than

one error condition caused a stop. Once you see the

same flash code repeated, you have seen all the flash

codes for the error conditions that caused the stop.
For example, if you see three flashes, a pause, then two

flashes, a pause, then four flashes, a pause, then one

flash, the flash codes are 32 and 41. If you then see three

flashes, a pause, then two flashes, you are seeing the

first code again. This means you have seen all the flash

codes for this stop. You may now release the RESET

button.
A list of flash codes and the faults they represent is shown

below.

Code

Fault

11

Thermal overload trip

12

Motor stall

13

Motor jam

14

Phase sequence ACB

15

Pole over-temperature

16

SCR failed to fire

21

15V Power supply low

22

Phase loss

23

Bypass dropout

24

SCR/Contactor overcurrent

25

Phase imbalance

26

Non-volatile memory error

31

Zero voltage cross failure

32

Short SCR, phase loss, load disconnect

33

Serial communication lost

34

SCR instantaneous overcurrent

41

24V power supply low

42

Timer system fault

43

Watchdog reset occurred

44

PLL (DSP)

45

Illegal address (DSP)

Effective 9/00

Table 7

Fig. 6   Soft Start Control Interface Module (CIM)

TORQUE (%)

T

2

T

1

TORQ

UE

 

(

T

2

)

T

1

T

1

TORQUE

 

(

T

2

)

45

5          85

65

25

45

5          85

65

25

30

0          60

B        C

A         D

FLA

CLASS

TRIP

TIME (Sec.)

t

k

0          2

OVLD

RAMP START

MANUAL RESET

JAM

STALL

PH. REV.

PH. LOSS

ON

ON

ON

ON

DISABLE
DISABLE
DISABLE

AUTO RESET

CURRENT LIMIT

DISABLE

START

Made in U.S.A.

ON

DISABLE

OVERLOAD -

20

0.5

EMA71

S.S. TRIP

60

15           45

5   10  20  30

B Y P A S S

B Y P A S S

t

r

t

s

t

k

t

r

t

s

t

k

t

r

t

s

TRIP

10

1

1.5

0.5

180

40

15

120

5

Auto Reset

Select auto or manual reset on the Control Interface

Module.
When a fault is present, the auto-reset will attempt to

reset the fault every 2.5 seconds. If the fault is clear, the

system resets the fault(s). The soft starter is ready for

use, and may be restarted by selecting “Run 1” (assuming

power is present.)
The motor does NOT automatically restart after a fault is

reset.

Fig. 7   Soft Starter Pump Control Interface Module (CIM)

TORQUE (%)

T

2

T

1

TORQ

UE

 

(

T

2

)

T

1

T

1

TORQUE

 

(

T

2

)

45

5          85

65

25

45

5          85

65

25

30

0          60

B        C

A         D

FLA

CLASS

TRIP

TIME (Sec.)

t

k

0          2

OVLD

RAMP START

MANUAL RESET

JAM

STALL

PH. REV.

PH. LOSS

ON

ON

ON

ON

DISABLE
DISABLE
DISABLE

AUTO RESET

CURRENT LIMIT

DISABLE

START

Made in U.S.A.

ON

DISABLE

OVERLOAD -

20

0.5

EMA72

S.S. TRIP

60

15           45

5   10  20  30

B Y P A S S

B Y P A S S

t

r

t

s

t

k

t

r

t

s

t

k

t

r

t

s

S.F.  -   ENABLE

DISABLE

TRIP

10

1

1.5

0.5

180

40

15

120

5

Stop Ramp ts = dial setting x 2

All manuals and user guides at all-guides.com

Содержание Cutler-Hammer S801TR

Страница 1: ...ll wave power bridge The voltage and current applied to the motor is controlled by varying the thyristor conduction period This in turn controls the torque supplied by the motor After the motor reache...

Страница 2: ...0 5 Standard 10 4 1 7 N m 65mm Lockwasher and 15 in lb 2 55 in Flat Washer S801R 1 4 20 x 0 625 Standard 1 4 4 2 8 N m 110mm Lockwasher and 25 in lb 4 33 in Flatwasher Required Mounting Hardware Fram...

Страница 3: ...cation as shown To mount the unit use all the hardware specified in Table 1 on page 2 of this leaflet Tighten to the torque specified TO AVOID SHOCK HAZ ARD DISCONNECT ALL POWER BEFORE ANY FUNCTIONS A...

Страница 4: ...AUX BORNES SAUF AVIS CONTRAIRE DANS CE MANUEL TOUTE LA FILERIE DE COMMANDE EST DE CALIBRE 22 A 12 AWG L INOBSERVATION DE CETTE MESURE POURRAIT CAUSER DES DOMMAGES IMPORTANTS AU CONTROLEUR ATTENTION T...

Страница 5: ...DAMAGE TO THE CONTROLLER CAUTION APPLIQUER UNE TENSION DE 24V C C AUX BORNES SAUF AVIS CONTRAIRE DANS CE MANUEL TOUTE LA FILERIE DE COMMANDE EST DE CALIBRE 22 A 12 AWG L INOBSERVATION DE CETTE MESURE...

Страница 6: ...d it will communicate with the CIM and load the program into the Soft Starter Allow the unit 2 seconds to ensure communication checks complete and values are set To verify CIM is operational press Fau...

Страница 7: ...41 24V power supply low 42 Timer system fault 43 Watchdog reset occurred 44 PLL DSP 45 Illegal address DSP Effective 9 00 Table 7 Fig 6 Soft Start Control Interface Module CIM TORQUE T2 T1 TORQUE T2...

Страница 8: ...40 50 50 S801R10N3S 80 22 40 45 25 20 30 25 60 50 75 60 R13N3S Three Phase Motor kW Rating 50 Hertz hp Rating 60 Hertz 200V 230V 460V 575V 15 Second Ramp 4 Starts per Hour 450 Current Limit 40o C Fra...

Страница 9: ...10 30 25 40 30 N66N3S 110 mm 65 15 30 33 15 15 20 15 50 40 50 50 S801R10N3S 80 22 40 45 25 20 30 25 60 50 75 60 R13N3S Three Phase Motor hp Rating 60 Hertz kW Rating 50 Hertz 200V 230V 460V 575V Cooli...

Страница 10: ...ce or start up assistance 24 hours day 7 days week please call 1 800 498 2678 Cutler Hammer Solid State Reduced Voltage Motor Starter Aftermarket Services Technical telephone support Resident service...

Отзывы: