background image

Pub 49004

Effective 9/00

Page 5

Providing Control Power

Name

Terminal Board

Default

Input

Designation

Common

-

-

Negative

Power

+

-

24VDC nominal

Permissive

P (24VDC only)

Hardwired Stop

24 VDC only

Input 1

1 (24VDC only)

Start

24VDC only

Input 2

2 (24VDC only)

Jog Forward

24VDC only

Input 3

3 (24VDC only)

Overload Disable

24VDC only

Input 4

4 (24VDC only)

Fault Reset

24VDC only

Common

13

-

Relay close connects to 14

NO Contact

14

-

3 Amps @ 120VAC/24VDC

in Bypass

10 Amps, Max (Resistive) Switching

Common

95

-

NC Connects to 96. Relay closure connects to 98.

Ready96

-

3 Amps @ 120VAC/24VDC

10 Amps, Max (Resistive) Switching

Fault

98

-

3 Amps @ 120VAC/24VDC

10 Amps, Max (Resistive) Switching

Control Wiring Inputs

13 and 14 - Closes when in bypass. Contact is normally open.
95 and 96  Close - System OK, Open Fault. Pins 95, 96, and

98 are Form C contact. 95 acts as the common, 96 is a normally

closed  contact, and 98 is a normally open contact. On any

fault that trips the unit or causes it not to start, 96 opens and

98 closes.
95 and 98  Open - System OK, Close - Fault
95 and 96  Open - Fault

The control wiring is connected to the soft starter by a

12-pin terminal strip connector located on the front of the

unit. Each connection is capable of holding one or two

#22 - #16 AWG wires, or one #14 or #12 AWG wire.

Each terminal should be tightened to 3.5 in-lb.

APPLY ONLY 24VDC TO CONTROL TERMINAL
BOARD UNLESS SPECIFIED OTHERWISE IN THIS
MANUAL. ALL CONTROL WIRING IS 22 - 12 AWG.
FAILURE TO FOLLOW THIS CAUTION COULD RE-
SULT IN SEVERE DAMAGE TO THE CONTROLLER.

CAUTION

APPLIQUER UNE TENSION DE 24V C.C. AUX BORNES
SAUF AVIS CONTRAIRE DANS CE MANUEL. TOUTE
LA FILERIE DE COMMANDE EST DE CALIBRE 22 A
12 AWG. L’INOBSERVATION DE CETTE MESURE
POURRAIT CAUSER DES DOMMAGES IMPORTANTS
AU CONTROLEUR.

ATTENTION

1. Connect DC common (negative) to pin -.

2. C24VDC positive to pin +.
3. Pin P, permissive circuit, must be energized (+24VDC)

to allow operation of unit. If power is removed from

permissive circuit at any time, unit will initiate a stop.

4. If 24VDC power is toggled to Input 1 while P is at 24V,

device will initiate a start.

5. Input 2 is Forward Jog. If 24VDC power is applied to

Input 2 while P is at 24V, the soft starter will initiate

motor jog.

6. Input 3 is Overload Disable. When Input 3 is toggled,

the overload will be disabled for the next start.

7. If +24VDC input power is applied to Input 4, the soft

starter is reset. Faults are cleared only if fault has

been corrected.

8. Pins 13 and 14 - 120VAC or 24VDC provide for the

integral bypass contact. The integral bypass contact

will close upon bypass and will remain closed until

stop is initiated. Motor may continue to run even after

stop is initiated during soft stop until programmed

ramp has been completed.

9. Pins 95, 96, and 98 provide alarm circuit NO-NC

change state on any fault. Form C Max. 24VDC,

120VAC, 3 amps.

NOTE -

 When control power (+24VDC) is first applied,

all the LEDs on the CIM will illuminate briefly. This is a

normal startup test that verifies communication to the

CIM. Pressing “Fault Reset” also momentarily lights all

the LEDs. This verifies the CIM board is functional, and

tests all LEDs for functionality.

Table 4

All manuals and user guides at all-guides.com

Содержание Cutler-Hammer S801TR

Страница 1: ...ll wave power bridge The voltage and current applied to the motor is controlled by varying the thyristor conduction period This in turn controls the torque supplied by the motor After the motor reache...

Страница 2: ...0 5 Standard 10 4 1 7 N m 65mm Lockwasher and 15 in lb 2 55 in Flat Washer S801R 1 4 20 x 0 625 Standard 1 4 4 2 8 N m 110mm Lockwasher and 25 in lb 4 33 in Flatwasher Required Mounting Hardware Fram...

Страница 3: ...cation as shown To mount the unit use all the hardware specified in Table 1 on page 2 of this leaflet Tighten to the torque specified TO AVOID SHOCK HAZ ARD DISCONNECT ALL POWER BEFORE ANY FUNCTIONS A...

Страница 4: ...AUX BORNES SAUF AVIS CONTRAIRE DANS CE MANUEL TOUTE LA FILERIE DE COMMANDE EST DE CALIBRE 22 A 12 AWG L INOBSERVATION DE CETTE MESURE POURRAIT CAUSER DES DOMMAGES IMPORTANTS AU CONTROLEUR ATTENTION T...

Страница 5: ...DAMAGE TO THE CONTROLLER CAUTION APPLIQUER UNE TENSION DE 24V C C AUX BORNES SAUF AVIS CONTRAIRE DANS CE MANUEL TOUTE LA FILERIE DE COMMANDE EST DE CALIBRE 22 A 12 AWG L INOBSERVATION DE CETTE MESURE...

Страница 6: ...d it will communicate with the CIM and load the program into the Soft Starter Allow the unit 2 seconds to ensure communication checks complete and values are set To verify CIM is operational press Fau...

Страница 7: ...41 24V power supply low 42 Timer system fault 43 Watchdog reset occurred 44 PLL DSP 45 Illegal address DSP Effective 9 00 Table 7 Fig 6 Soft Start Control Interface Module CIM TORQUE T2 T1 TORQUE T2...

Страница 8: ...40 50 50 S801R10N3S 80 22 40 45 25 20 30 25 60 50 75 60 R13N3S Three Phase Motor kW Rating 50 Hertz hp Rating 60 Hertz 200V 230V 460V 575V 15 Second Ramp 4 Starts per Hour 450 Current Limit 40o C Fra...

Страница 9: ...10 30 25 40 30 N66N3S 110 mm 65 15 30 33 15 15 20 15 50 40 50 50 S801R10N3S 80 22 40 45 25 20 30 25 60 50 75 60 R13N3S Three Phase Motor hp Rating 60 Hertz kW Rating 50 Hertz 200V 230V 460V 575V Cooli...

Страница 10: ...ce or start up assistance 24 hours day 7 days week please call 1 800 498 2678 Cutler Hammer Solid State Reduced Voltage Motor Starter Aftermarket Services Technical telephone support Resident service...

Отзывы: