Instructional Leaflet

RLY-800 Radio Frequency Relay (Brazil)

Securing the RLY-800 to the Universal Bracket

As described in 

“RLY-800 Features and Functions” 

on page 4

, the RLY-800 can be mounted horizontally 

or vertically based on the installation location and if 
the RLY-800 uses an internal or external antenna. 
The mounting bracket must be oriented correctly 
when it is installed on the RLY-800 to allow the 
device to be properly mounted and secured.

Figure 7. Mounting Bracket

The standard RLY-800 and mounting bracket 
configuration is shown in 

Figure 8

. This mounting 

bracket alignment allows the RLY-800 to be 
mounted vertically on a pole or horizontally on a light 
pole arm.

Relays using an external antenna that is mounted 
separately and connected to the RLY-800 with a 
coaxial cable, will use the standard mounting bracket 
configuration that is shown in 

Figure 8

. An example 

of this type of antenna is the OD9-5 Omni Antenna.

The alternate RLY-800 and mounting bracket 
configuration is shown in 

Figure 9

. This mounting 

bracket alignment is used when the RLY-800 is 
equipped with an external antenna that is mounted 
directly on the box, such as the Laird Technologies 
mobile antenna or another similar antenna.

Figure 8. RLY-800 Bracket Positioned for Vertical 

Pole Mount or Light Pole Arm Mounting

Figure 9. RLY-800 and Bracket Positioned for 

Horizontal Pole Mount with External Antenna

Perform the following steps to install the mounting 
bracket on the RLY-800:

1. Orient the RLY-800 on the mounting bracket in 

the position that is required for your installation. 
Align the holes in the three RLY-800 mounting 
tabs with three holes in the mounting bracket.

2. Secure the RLY-800 to the mounting bracket with 

the three bolts and nuts provided with the relay.

3. Perform one of the following RLY-800 

installation procedures:

“Installing the RLY-800 on a Pole or Wall”

“Installing the RLY-800 on a Light Pole Arm”

Up/Top

(For Pole Mount)

Upper Lag 
Bolt Hole

Lower Lag 
Bolt Hole

Содержание Cooper Power Systems RLY-800

Страница 1: ...RF mesh network infrastructure in areas where end points are too spread out to effectively form a mesh network Extend RF communications into rural areas Build out a communications network for demand r...

Страница 2: ...specific tasks and procedures are located throughout the manual SAFETY FOR LIFE SAFETY FOR LIFE Hazard Statement Definitions This document may contain four types of hazard statements DANGER Indicates...

Страница 3: ...experienced radio TV technician for help NOTICE The installer of this radio equipment must ensure that the antenna is located or pointed such that it does not emit RF field in excess of Health Canada...

Страница 4: ...dance is 50 ohms Antennas that may be used with this product include HGV 906U 900 MHz Omnidirectional Antenna 6 dBi Gain OD9 5 900 to 928 MHz Omni Antenna 5 dBi Gain B8965CN Laird Technologies 896 970...

Страница 5: ...uring the RLY 800 to the Universal Bracket on page 8 Installing the RLY 800 on a Pole or Wall on page 9 or Installing the RLY 800 on a Light Pole Arm on page 10 Installing an External Remote Antenna o...

Страница 6: ...tions A RLY 800 with an external attached antenna can be mounted as follows Wall mounted Pole mounted horizontally Horizontally on the side of a light pole arm Figure 5 External Attached Antenna Devic...

Страница 7: ...3 Remove the knockout prior to mounting by using a drill and a conduit style step drill bit The dimple in the center of the knockout allows you to accurately position the step drill bit in the center...

Страница 8: ...his type of antenna is the OD9 5 Omni Antenna The alternate RLY 800 and mounting bracket configuration is shown in Figure 9 This mounting bracket alignment is used when the RLY 800 is equipped with an...

Страница 9: ...ting Options for the RLY 800 on page 6 for more information Figure 10 Internal and Remote External Antenna Pole or Wall Mounting Figure 11 External Attached Antenna Pole or Wall Mounting 3 If you are...

Страница 10: ...ntenna installed on the RLY 800 enclosure mount the device on the side of the light pole arm as shown in Figure 13 3 Secure the RLY 800 and mounting bracket assembly to the light pole arm using band c...

Страница 11: ...a 9 Install a copper grounding rod at the base of the utility pole below the lightening arrestor 10 Route a 10 AWG ground wire between the lightening arrestor and the copper grounding rod and secure w...

Страница 12: ...LY 800 by using a power adapter connected to a street light sensor 1 Remove electrical power from the street light that is to supply the RLY 800 2 Remove the street light sensor from the street light...

Страница 13: ...Receiver Sensitivity 104 dBm 1 PER 25 C 38 4 kbps 101 dBm 1 PER 25 C 76 8 kbps 98 dBm 1 PER 25 C 153 6 kbps Mode Frequency Hopping Spread Spectrum FHSS Operating Requirements Power Source 120 VAC or 2...

Страница 14: ...s operate under Part 15 of the FCC rules Modifications to these devices not expressly authorized by Cooper Power Systems may affect your ability to legally operate these devices DISCLAIMER OF WARRANTI...

Отзывы: