manualshive.com logo in svg
background image

External arrester

External surge arresters ordered with the transformer 

must be installed and connected in the field before the 

transformer is put into service.
Arrester and tank ground connections must be completed 

before the transformer is connected to the high-voltage or 

low-voltage lines. Proper connection places the arrester in a 

direct shunt relationship to the transformer insulation.

Maintenance

Exterior maintenance

On an annual or more frequent interval, inspect all exposed 

surfaces for evidence of tampering, battered metal, gouges, 

etc. Dents or deformities should be repaired at once. 

Scratched or weathered paint or protective coatings should 

be touched up promptly.
Keep the area around the transformer clean. Do not store 

tools, materials or equipment on or against the transformer.

Cabinet interior maintenance

Periodically inspect the terminal compartment interior and 

all operating equipment. Check all gauges and controls for 

proper operation. Repair or replace damaged or defective 

equipment.
Inspect drain cocks, plugs, fuse mountings, and switches. 

Look for evidence of insulating liquid seepage around tank-

wall gaskets, seals, etc. Repair as required.
Replacement of gaskets or seals in the tank wall may 

require that the tank be opened and the insulating liquid 

lowered to the appropriate level. For instruction on opening 

the tank and for draining and replacing the insulating liquid, 

refer to the 

Insulating Liquid Maintenance 

section in this 

manual.

Tank internal maintenance

(For Envirotran

®

 

Transformers see the Envirotran

 

Transformers section of this manual before continuing)

Service to bushings or equipment inside the transformer 

tank will require that the tank be opened and the insulating 

liquid lowered to the appropriate level. Before opening the 

transformer tank, read the 

Insulating Liquid Maintenance 

section in this manual. The 

Liquid Maintenance

 section 

explains safety precautions that should be taken and 

gives instructions on how to prevent insulating liquid 

contamination. Precautions must be taken to prevent dirt 

or moisture from entering the opened transformer tank. 

Contamination of the insulating liquid will prevent the 

transformer from operating properly and may cause serious 

damage to the transformer.
Three-phase pad-mounted transformers may have either 

bolt-on or weld-on main tank covers. Bolt-on covers can be 

removed to access the tank interior. Access to the interior 

of a transformer with a weld-on tank cover is typically 

through a manhole/handhole. To gain additional internal 

access to tanks with weld-on tank covers, the tank cover 

must be cut open.

Tank cover removal and installation

(For Envirotran Transformers see the Envirotran 

Transformers section of this manual before continuing)

WARNING 

Hazardous voltage. Can cause severe injury, death, or 

damage to equipment. De-energize transformer from 

a remote upstream source before opening cabinet 

and doing cabinet interior inspection or maintenance. 

Check that all transformer terminals and bushings have 

zero voltage. Ground transformer following industry 

accepted safe grounding practices.

CAUTION 

Elevated Pressure. Can cause personal injury or damage 

to transformer. Release internal pressure with pressure 

relief device before removing tank cover, manhole cover 

or handhole cover.

WARNING 

Hazardous voltage. Can cause severe injury, death, or 

damage to equipment. De-energize transformer from 

a remote upstream source before opening cabinet 

and doing internal tank inspection or maintenance. 

Check that all transformer terminals and bushings have 

zero voltage. Ground transformer following industry 

accepted safe grounding practices.

CAUTION 

Elevated Pressure. Can cause personal injury or damage 

to transformer. Release internal pressure with pressure 

relief device before removing tank cover, manhole cover 

or handhole cover.

WARNING 

Hazardous voltage. Can cause severe injury, death, or 

damage to equipment. De-energize transformer from 

a remote upstream source before opening cabinet 

and doing internal tank inspection or maintenance. 

Check that all transformer terminals and bushings have 

zero voltage. Ground transformer following industry 

accepted safe grounding practices.

19

Three-phase pad-mounted compartmental type installation and maintenance instructions

   

MN202001EN   August 2015

Содержание COOPER POWER SERIES

Страница 1: ...ER POWER SERIES Distribution Transformers MN202001EN Effective August 2015 Supersedes S210 12 1 August 2013 Three phase pad mounted compartmental type transformer installation and maintenance instruct...

Страница 2: ...NTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES In no event will Ea...

Страница 3: ...Loadbreak Switches 11 Tap Changer 12 Dual Voltage and Delta Wye Switch 14 Vacuum Fault Interrupter VFI 15 Air Switches Arc Strangler 16 Surge Arresters 17 MAINTENANCE Exterior Maintenance 19 Cabinet I...

Страница 4: ...ions when working around high voltage lines and equipment and support our Safety For Life mission Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe...

Страница 5: ...er capacity When using a forklift lift with the transformer tank closest to the mast of the forklift since most of the transformer weight is in the tank Pallet mounted equipment may also be moved by c...

Страница 6: ...abinet the installation will not provide the security needed to prevent tampering by the public Add a permanent mortar seal to fill the gaps Pre service inspection exterior New transformers or transfo...

Страница 7: ...e on underside of the tank cover or man hole cover 2 Loose shifted or damaged parts bushings fuse holders etc 3 Broken or loose connections 4 Contaminated insulating liquid sediment or foreign objects...

Страница 8: ...ransformer nameplate Transformer neutrals must be connected to system neutrals Leads and connections that are not used must be insulated from ground and all other leads Livefront transformer connectio...

Страница 9: ...furnished with the transformer Liquid temperature gauge Transformers may be furnished with a temperature gauge as optional equipment to indicate the top liquid temperature in the tank in degrees Cels...

Страница 10: ...sformer Pressure relief device Transformers may have a cover mounted pressure relief device PRD in addition to the faceplate mounted pressure relief valve PRV standard on all three phase pad mounted d...

Страница 11: ...minals following industry accepted safe grounding practices Grounding secondary terminals protects against situations such as a standby generator energizing transformer from the secondary circuit Foll...

Страница 12: ...valve to open valve Hold the valve open for 30 seconds after pressurized air can no longer be heard hissing through the valve 2 Close pressure relief valve and wait 30 seconds 3 Pull pressure relief...

Страница 13: ...from fuse cartridge 1 Use 3 4 inch and 1 2 inch wrenches to remove end plug see Figure 13 2 Use screwdriver or other tool to straighten tulip tip end of fuse link and push fuse link out of fuse cartri...

Страница 14: ...facturer s product literature for maximum interrupting ratings Internal cartridge fuse replacement 1 Verify that tank is grounded De energize transformer from a remote upstream source Ground all bushi...

Страница 15: ...n cause an explosion or fire Use a hotstick to operate transformer loadbreak equipment After operating transformer loadbreak equipment check that voltages at transformer terminals are the expected val...

Страница 16: ...clockwise to loop thru transformer open The transformer is now OPEN and the loop conductor is electrically connected 3 Move index plate between loop thru transformer open and line b only 4 Rotate swit...

Страница 17: ...e handle to desired position and allow pointer to drop into slot of index plate 5 Secure handle in its new position by tightening lock screw through index plate until it bottoms 6 Padlocking may be ac...

Страница 18: ...position as follows 1 Verify that tank is grounded De energize transformer from a remote upstream source Ground all bushings and terminals before operating dual voltage or delta wye switch 2 Back out...

Страница 19: ...Do not operate loadbreak equipment if a fault condition is suspected Doing so can cause an explosion or fire Use a hotstick to operate transformer loadbreak equipment After operating transformer load...

Страница 20: ...erly and that electrical circuit conditions are as expected Before servicing transformer secondary connected equipment verify that all transformer secondary terminals have zero voltage and ground the...

Страница 21: ...blished maximum continuous operating voltage MCOV values The transformer should not be tested impulse or applied potential with the arrester connected If connected during impulse tests the arrester wi...

Страница 22: ...by rotating handle 3 4 to 1 turn after handle has come in contact with seal gland Under oil arrester disconnection during test with out arrester disconnect switch To disconnect arresters without a dis...

Страница 23: ...nt dirt or moisture from entering the opened transformer tank Contamination of the insulating liquid will prevent the transformer from operating properly and may cause serious damage to the transforme...

Страница 24: ...aks Test pressure should not exceed 7 psig Established pressure should be main tained for at least four hours to insure that all seals are proper 4 Re install the nutguard using 25 ft lbs torque to ti...

Страница 25: ...t cover weld 10 Thoroughly clean tank cover to help prevent contamination of insulating liquid when removing cover Remove all dirt grease and moisture 11 Remove tank cover from tank Weld on tank cover...

Страница 26: ...ntenance on cabinet 2 Place one 1 4 to 3 8 inch shim directly below faceplate on both sides of tank at points A and A see Figure 28 3 Place one 1 1 2 inch wedge under each side of cabinet at points B...

Страница 27: ...nventional transformer oil mixed with R Temp fluid Conventional transformer oil content of 3 in R Temp fluid lowers the fire point below 300 C Measure the ASTM flash and fire points if the presence of...

Страница 28: ...uld be clean and dry large mouth glass bottles Make sure that the liquid being sampled is representative of the liquid in the unit Sufficient liquid must first be drawn off to ensure that the sample w...

Страница 29: ...y Cleveland Open Cup 2 ASTM D877 Standard Test Method for Dielectric Breakdown Voltage of Insulating Liquids Using Disk Electrodes 3 ASTM D923 Standard Practices for Sampling Electrical Insulating Liq...

Страница 30: ...reported and investigated Annual Cabinet Interior Maintenance Items to Inspect Points to be checked Remedial Action Frequency Gauges and Controls Check for proper operation Repair or replace damaged o...

Страница 31: ...g will achieve a rainbow coloring if a particular terminal is experiencing an over temperature condition Tighten any loose connections immediately Any damage or discoloration that is observed should b...

Страница 32: ...on com cooperpowerseries 2015 Eaton All Rights Reserved Printed in USA Publication No MN202001EN August 2015 For Eaton s Cooper Power series three phase pad mounted transformer product information cal...

Отзывы: